| ▶ 전선, 케이블, 전로용품 |
| ANSI/NEMA C29.2B:2013 |
Insulators - Wet-process porcelain and toughened glass – Transmission Suspension type 8.2.1 Low-frequency dry flashover test 8.2.2 Low-frequency wet flashover test 8.2.3 Critical impulse flashover tests-Positive and Negative 8.2.4 Radio-influence voltage test 8.2.5 Thermal-mechanical load cycle test 8.2.6 Thermal shock test 8.2.7 Residual-strength test 8.3.1 Visual and dimensional tests 8.3.4 Combined mechanical and electrical-strength tests |
8.2.1 Max. 960 kV 8.2.2 Max. 520 kV 8.2.3 Max. 2 600 kV 8.2.4 Max. 600 kV, 0.5 MHz ~ 2 MHz 8.2.5 (-50 ~ 100) ℃ Max. 300 kN 8.2.6 (2 ~ 99) ℃ 8.2.7 Max. 500 kN 8.3.4 Max. 100 kV 500 kN |
소재지 |
| ES-5680-0006:2023 |
FRP 저압접속함 뚜껑 5.3.1 외관검사 5.3.2 구조검사 5.3.4 상용주파 건조내전압시험 5.3.5 내후성시험 5.3.6 염색용액 침투시험 5.3.7 패킹재료시험 6 표시 |
인장: 4.9 kN 이하 전압: 100 kV 이하 |
소재지-1 |
| ES-5920-0012:2016 |
리드선 부착형 배전용 폴리머 피뢰기 7.2.1 구조검사 7.2.2 하우징 절연내력시험 7.2.3 제한전압시험 7.2.4 장시간충격전류시험 7.2.5 동작책무시험 7.2.6 단로기시험 7.2.7 단락회로내력시험 7.2.8 부분방전시험 7.2.9 휨모멘트 7.2.11 기후노화시험 7.2.12 누설전류시험 7.2.13 기준전압측정 7.2.14.1 내트래킹시험 7.2.15 기밀시험 7.2.16 절연행거시험 7.2.17 특성요소의 V-I특성시험[참고시험] 7.2.18 리드선고정력시험 7.2.19 피뢰기본체 굽힘하중시험 7.2.20 리드선의 성능특성시험(내트래킹시험제외) 7.2.22 복합가속열화시험 |
7.2.2 Max. 300 kV 7.2.3 Max. 20 kA 7.2.4 Max. 3 kA 7.2.5 Max. 100 kA 7.2.6 Max. 800 A 7.2.7 Max. 80 kA 7.2.8 Min. 1 pC 7.2.9 Max. 100 kN 7.2.11 1 000 h 7.2.12 Max. 10 mA 7.2.13 Max. 300 kV 7.2.14.1 1 000 h 7.2.15 70 ℃, 14 d 7.2.16 Max. 300 kV 7.2.17 Min. 1 μA, Max. 100 kA 7.2.18 Max. 100 kN 7.2.19 Max. 100 kN 7.2.20 Max. 300 kV 7.2.22 Max. 33 kV 2A (-20 ~ 80) ℃ UV B lamp 50 kN |
소재지 |
| ES-5935-0001:2022 |
알루미늄선용 분기슬리브 5.3.3 전기저항시험 5.3.4 인장시험 5.3.5 히트사이클 시험 5.3.6 염수분무시험 6 표시 |
인장력 : Max. 270 kN 저항 : 1 mΩ ~ 10 Ω 중성시험: pH (6.5 ~ 7.2) |
소재지-1 |
| ES-5935-0005:2022 |
알루미늄선용 압축슬리브 5.2.2 히트 사이클시험 5.2.3 염수분무시험 6 표시 |
중성시험: pH (6.5 ~ 7.2) |
소재지-1 |
| ES-5935-0008:2023 |
지중 저압케이블 접속재 5.3.1 외관검사 5.3.2 구조검사 5.3.3 침수시험 5.3.4 절연저항 측정시험 5.3.5 절연내력시험 5.3.6 굴곡시험 5.3.7 전류 사이클 및 침수시험 5.3.8 누설전류시험 5.3.9 내열성 및 내한성 시험 5.3.10 난연성 시험 5.3.11 슬리브 시험 5.3.13 내후성시험 5.3.14 접속재 열성능 시험 5.3.15 열조건 굴곡시험 |
케이블 : (22 ~ 325) mm² AC: Max. 300 kV 60 Hz IR: Max. 2 000 MΩ 온도상승 : 8 000 A 60 Hz |
소재지-1 |
| ES-5935-0009:2024 |
23 kV 케이블 종단 및 직선 접속재 5.1.1 종단접속재, 표 3 - 외관 및 구조검사 - 부분방전시험 - 상용주파 건조내전압시험(1분) - 상용주파 건조내전압시험(6시간) - 상용주파 주수내전압시험(10초) - 직류건조내전압시험(15분) - 충격내전압시험(130 ℃) - RIV시험 - Cyclic aging시험 - 접속재의 열적, 기계적강도 - 단시간전류시험
5.1.1.2 인공오손시험 5.1.1.4 수밀시험
5.1.2 직선접속재, 표 4 - 외관 및 구조시험 - 부분방전시험 - 상용주파 건조내전압시험(1분) - 직류건조내전압시험(15분) - 충격내전압시험(상온) - 충격내전압시험(130 ℃) - Cyclic aging시험 - 장시간 상용주파 내전압시험 - 단시간전류시험 - Shield시험 - 접속재의 열적, 기계적강도 5.1.2.1 침수시험 |
5.1.1 종단접속재, 표 3 - Min. 0.001 mm, 1 mm - ≤ 5 pC - ≤ 100 kV 60 Hz - ≤ 100 kV 60 Hz - ≤ 100 kV 60 Hz - ≤ DC 150 kV - ≤ LI 200 kV - ≤ 100 kV 60 Hz, Min. 1 μV - ≤ 50 kV 60 Hz, ≤ 3 000 A, ≤ 200 ℃ - ≤ 3 000 A, ≤ 50 kN, ≤ 200 ℃ - ≤ 180 kA 5.1.1.2 ≤ 100 kV 60 Hz 5.1.1.4 ≤ 3 000 A, ≤ 200 ℃
5.1.2 직선접속재, 표 4 - Min. 0.001 mm, 1 mm - ≤ 3 pC - ≤ 100 kV 60 Hz - ≤ DC 150 kV - ≤ LI 200 kV - ≤ 50 kV 60 Hz, ≤ 3 000 A, ≤ 200 ℃ - ≤ 100 kV 60 Hz - ≤ 180 kA - ≤ 130 ℃ - ≤ 3 000 A, ≤ 50 kN, ≤ 200 ℃ 5.1.2.1 ≤ 0.1 MPa |
소재지 |
| ES-5935-0009:2024 |
23 kV 케이블 종단접속재 및 직선접속재 5.1.1 종단접속재 표 3 - 외관 및 구조검사 - 부분방전시험 - 상용주파 건조내전압시험(1분) - 상용주파 건조내전압시험(6시간) - 상용주파 주수내전압시험(10초) - 직류건조내전압시험(15분) - 충격내전압시험(130℃) - RIV시험 - Cyclic aging 시험
5.1.1.1 Track Resistance 시험 5.1.1.3 내후성 시험
5.1.2 직선접속재 표 4 - 외관 및 구조검사 - 부분방전시험 - 상용주파 건조내전압시험(1분) - 직류건조내전압시험(15분) - 충격내전압시험(상온) - 충격내전압시험(130℃) - Cyclic Aging 시험 - 장시간 상용주파내전압시험 |
케이블: (60 ~ 600) mm² RIV: Min. 6.5 μV AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ 주수율: (0 ~ 5) mm/min |
소재지-1 |
| ES-5935-0010:2014 |
케이블 엘보접속재 6.1 시험순서 표5 시험 및 검사 1. 외관 및 구조검사 2. 부분방전시험 3. 교류내전압시험 4. 직류내전압시험 5. 충격내전압시험 7. 개폐시험 9. 비절연부의 전류주기시험 10. 절연부의 전류주기시험 11. 가속기밀성시험 12. 케이블 접속력시험 19. 가열노화시험 |
케이블: (60 ~ 600) mm² AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ DC: Max. 100 kV |
소재지-1 |
| ES-5935-0012:2024 |
알루미늄 케이블 종단접속재 및 직선접속재 5.1.1 종단접속재, 표 3 - 외관 및 구조검사 - 부분방전시험 - 상용주파 건조내전압시험(1분) - 상용주파 건조내전압시험(6시간) - 상용주파 주수내전압시험(10초) - 직류건조내전압시험(15분) - 충격내전압시험(130 ℃) - RIV시험 - Cyclic aging시험 - 접속재의 열적, 기계적강도 - 단시간전류시험 - 재질시험 5.1.1.2 인공오손시험 5.1.1.4 수밀시험 5.1.2 직선접속재, 표 4 - 외관 및 구조시험 - 부분방전시험 - 상용주파 건조내전압시험(1분) - 직류건조내전압시험(15분) - 충격내전압시험(상온) - 충격내전압시험(130 ℃) - Cyclic aging시험 - 장시간 상용주파 내전압시험 - 단시간전류시험 - Shield시험 - 접속재의 열적, 기계적강도 5.1.2.1 침수시험 |
5.1.1 종단접속재, 표 3 - Min. 0.001 mm, 1 mm - ≤ 5 pC - ≤ 100 kV 60 Hz - ≤ 100 kV 60 Hz - ≤ 100 kV 60 Hz - ≤ DC 150 kV - ≤ LI 200 kV - ≤ 100 kV 60 Hz, Min. 1 μV - ≤ 50 kV 60 Hz, ≤ 3 000 A, ≤ 200 ℃ - ≤ 3 000 A, ≤ 50 kN, ≤ 200 ℃ - ≤ 180 kA 5.1.1.2 ≤ 100 kV 60 Hz 5.1.1.4 ≤ 3 000 A, ≤ 200 ℃ 5.1.2 직선접속재, 표 4 - Min. 0.001 mm, 1 mm - ≤ 3 pC - ≤ 100 kV 60 Hz - ≤ DC 150 kV - ≤ LI 200 kV - ≤ 50 kV 60 Hz, ≤ 3 000 A, ≤ 200 ℃ - ≤ 100 kV 60 Hz - ≤ 180 kA - ≤ 130 ℃ - ≤ 3 000 A, ≤ 50 kN, ≤ 200 ℃ 5.1.2.1 ≤ 0.1 MPa |
소재지 |
| ES-5935-0013:2014 |
알루미늄 케이블 엘보접속재 6.1 시험순서 표5 시험 및 검사 1. 외관 및 구조검사 2. 부분방전시험 3. 교류내전압시험 4. 직류내전압시험 5. 충격내전압시험 7. 개폐시험 9. 비절연부의 전류주기시험 10. 절연부의 전류주기시험 11. 가속기밀성시험 19. 가열노화시험 |
케이블: (60 ~ 600) mm² AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ DC: Max. 100 kV |
소재지-1 |
| ES-5935-0019:2014 |
절연관통형 콘넥타 5.2.1 접속시험 5.2.2 토크 시험 5.2.3 Shear head 파단시험 5.2.4 인장력 시험 5.2.5 온도상승 시험 5.2.6 도금시험 5.2.7 상용주파 수중 내전압시험 5.2.8 통전부 시험 |
케이블: (2.0 ~ 100) mm² 부착량: Max. 1 533 μm (10 900 g/m²) 인장력: Max. 270 kN 온도상승 : 8 000 A 60 Hz |
소재지-1 |
| ES-5935-0029:2022 |
분기접속용 동슬리브 5.3.1 겉모양검사 5.3.2 구조 및 치수검사 5.3.4 전기저항시험 5.3.5 인장시험 5.3.6 도금두께시험 5.3.7 염수분무시험 6 표시 |
인장력 : Max. 270 kN 저항 : 1 mΩ ~ 10 Ω 중성시험: pH (6.5 ~ 7.2) |
소재지-1 |
| ES-5970-0003:2016 |
라인포스트 애자 6.2.1 외관검사 6.2.2 구조검사 6.2.3 상용주파 건조섬락 전압시험 6.2.4 상용주파 주수섬락 전압시험 6.2.5 뇌충격 내전압시험(정, 부) 6.2.6 냉열시험 6.2.7 흡습시험 6.2.9 도금시험 6.2.11 전파장애 전압시험 |
온도상승: 단상 Max 40 A IR: Max. 2 000 MΩ AC: Max. 42 kV 60 Hz LI: Max. 125 kV 30 kJ 주수율: (0 ~ 5) mm/min 냉열: - 냉수조: (0 ~ 20) ℃ - 온수조: (60 ~ 100) ℃ 단시간: 1 000 A 이하 조임토크: Max. 4.9 kN·cm |
소재지-1 |
| ES-5970-0008:2019 |
초고압용 볼소켓형 현수애자 6.1.1 구조검사 6.1.2 전파장해 전압시험 6.1.3 잔류강도시험 6.1.4 상용주파 건조섬락전압시험 6.1.5 상용주파 주수섬락전압시험 6.1.6 뇌충격 건조섬락전압시험 6.1.8 (과전)파괴하중시험 6.1.10 냉열시험(자기애자만 시행) 6.1.14 경년변화시험 6.1.17 급준파 전압시험 6.1.18 내 아크시험 6.3.1 외관검사 6.3.2 섬락시험(자기애자만 시행) |
6.1.2 Max. 600 kV, 0.5 MHz ~ 2 MHz 6.1.3 Max. 500 kN 6.1.4 Max. 960 kV 6.1.5 Max. 520 kV 6.1.6 Max. 2 600 kV 6.1.8 Max. 100 kV, 500 kN 6.1.10 (2 ~ 99) ℃ 6.1.14 (-50 ~ 100) ℃, Max. 300 kN 6.1.17 Max. 2 500 kV/μs 6.1.18 150 kA · cycles 6.3.2 Max. 960 kV |
소재지 |
| ES-5970-0009:2012 |
내염형 주상변압기 부싱(22.9 kV용) 4.2 온도시험 4.3 절연저항시험 4.4 상용주파 내전압시험 4.5 충격전압시험 4.6 가열시험 4.7 냉열시험 4.8 애관의 흡습시험 4.9 과전류 강도시험 4.11 클램프 단자 및 볼트조임 시험 |
온도상승: 단상 Max 40 A IR: Max. 2 000 MΩ AC: Max. 42 kV 60 Hz LI: Max. 125 kV 30 kJ 주수율: (0 ~ 5) mm/min 냉열: - 냉수조: (0 ~ 20) ℃ - 온수조: (60 ~ 100) ℃ 단시간: 1 000 A 이하 조임토크: Max. 4.9 kN·Cm |
소재지-1 |
| ES-5970-0013:2022 |
폴리머 현수애자 6.2.1 외관검사 6.2.3 인장 내하중시험 6.2.4 기계적 하중-시간(Load-Time) 시험 6.2.6 인장 파괴하중시험 6.2.7 전파장애 전압시험 6.2.8 상용주파 건조섬락 전압시험 6.2.9 상용주파 주수섬락 전압시험 6.2.10 뇌충격 내전압시험(정 •부) 6.2.12 접착력 시험 6.2.13 수분침투시험(Water Penetration Test) 6.2.14 수분확산시험(Water Diffusion Test) 6.2.17 난연성시험 6.2.18 내후성 시험 6.2.19 도금시험 6.2.20 경년변화시험 7 표시 |
RIV: Min. 6.5 μV AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ 주수율: (0 ~ 5) mm/min 냉열 - 냉수조: (0 ~ 20) ℃ - 온수조: (60 ~ 100) ℃ 부착량: Max. 1 533 μm (10 900 g/m²) 인장력: Max. 270 kN |
소재지-1 |
| ES-5970-0017:2023 |
폴리머 내오손용 결합애자 6.2.2 구조검사 6.2.3 난연성시험 6.2.4 내후성 시험 6.2.6 상용주파 건조내전압시험 6.2.7 충격내전압시험 6.2.8. 굽힘파괴하중시험 6.2.9 굽힘내하중시험 6.2.10 인장파괴하중 시험 6.2.12 내열성 시험 6.2.13 내한성 시험 6.2.14 수분침투 시험(Water Penetration Test) 6.2.15 수분확산 시험(Water Diffusion Test) 6.2.16 염색 용액침투 시험(Dye Penetration Test) 6.2.17 도금시험 7 표시 |
건조 내전압 : 42 kV 이하 충격 전압: 125 kV 이상 부착량: Max. 1 533 μm (10 900 g/m²) 인장력: Max. 270 kN |
소재지-1 |
| ES-5970-0018:2023 |
인류클램프 절연커버 (폴리머현수애자용) 6. 시험 및 검사 - 외관검사 - 구조검사 - 인장강도시험 - 가열노화시험 - 가열변형시험 - 내전압시험 - 내트래킹시험 - 내한성시험 - 내열성시험 - 내후성시험 - 흡수성시험 - 난연성시험 7 표시 |
인장: 4.9 kN 이하 건조내전압: 30 kV 이하 주수내전압 : 20kV 이하 |
소재지-1 |
| ES-5970-0019:2017 |
배전용 폴리머 라인포스트 애자 6.2.1 외관검사 6.2.2 구조검사 6.2.3 상용주파 건조섬락전압시험 6.2.4 상용주파 주수섬락전압시험 6.2.5 뇌충격 내전압시험(정, 부) 6.2.8 인장파괴하중시험 6.2.9 수분확산시험 6.2.10 수분침투시험 6.2.11 염색용액침투시험 6.2.12 접착력시험 6.2.13 전파장애전압시험 6.2.16 난연성시험 6.2.17 내후성시험 6.2.18 도금시험 6.2.19 복합가속열화시험 7 표시 |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ 주수율: (0 ~ 5) mm/min RIV: Min. 6.5 μV 복합열화시험: 3상 Max. 75 kV 부착량: Max. 1 533 μm (10 900 g/m²) 인장력: Max. 270 kN |
소재지-1 |
| ES-5970-0025:2012 |
주상변압기용 폴리머 부싱(22.9 kV용) 5.1 외관검사 5.2 구조시험 5.3 온도시험 5.4 절연저항시험 5.5 상용주파 내전압시험 5.6 충격내전압시험 5.7 수분확산시험 5.9 내트래킹시험 5.12 접착력시험 5.13 난연성시험 5.14 염색용액침투시험 5.15 수분침투 시험 5.16 과전류강도시험 5.17 내후성시험 5.18 클램프 단자 볼트조임 시험 5.19 가열시험 5.20 냉열시험(자기코어) 5.21 흡습시험(자기코어) 6 표시 |
온도상승: 단상 Max. 40 A IR: Max. 2 000 MΩ AC: Max. 42 kV 60 Hz LI: Max. 600 kV 30 kJ 주수율: (0 ~ 5) mm/min 단시간: 1 000 A 조임토크: Max. 4.9 kN·cm 냉열: - 냉수조: (0 ~ 20) ℃ - 온수조: (60 ~ 100) ℃ 인장력: Max. 270 kN |
소재지-1 |
| ES-5970-0026:2018 |
주상변압기용 폴리머 저압부싱 5.1 외관검사 5.2 구조시험 5.3 온도시험 5.4 절연저항시험 5.5 상용주파 내전압시험 5.6 가열시험 5.7 수분확산시험 (FRP코어) 5.8 접착력시험 5.9 난연성시험 5.10 염색용액침투시험 (FRP코어) 5.11 냉열시험 (자기코어) 5.12 흡습시험 (자기코어) 5.13 과전류강도시험 5.16 내트래킹시험 5.17 클램프단자 및 볼트조임시험 6 표시 |
온도상승: 단상 Max. 500 A IR: Max. 2 000 MΩ AC: Max. 15 kV 60 Hz 냉열: - 냉수조: (0 ~ 20) ℃ - 온수조: (60 ~ 100) ℃ 단시간: 12.5 kA 이하 조임토크: Max. 7.35 kN·cm 인장력: Max. 270 kN |
소재지-1 |
| ES-5975-0002:2012 |
접지동봉 5.3 연결인장시험 5.4 동복 부착력시험 5.5 리드선의 인장시험 5.6 접속저항시험 5.7 전류시험 6 표시 |
인장력: Max. 270 kN |
소재지-1 |
| ES-5975-0003:2017 |
심타용 용융아연도금 접지봉 5.3.1 겉모양검사 및 구조검사 5.3.2 접속저항시험 5.3.3 전류시험 5.3.4 연결 인장시험 5.3.5 리드선 인장시험 5.3.6 용융아연도금시험 6 표시 |
부착량: Max. 1 533 μm (10 900 g/m²) 인장력: Max. 270 kN |
소재지-1 |
| ES-5975-0050:2016 |
쐐기형 인장클램프 5.1.2 도금시험 5.1.3 인장하중시험 5.1.4 선조장악력시험 5.2.3 염수분무시험 6 표시 |
인장력: Max. 270 kN 중성시험: pH (6.5 ~ 7.2) 부착량: Max. 1 533 μm(10 900 g/m²) |
소재지-1 |
| ES-6145-0025:2023 |
22.9 kV 수트리억제 충실 전력케이블 7.1 외관검사 7.2 구조검사 7.3 전기적 특성시험 7.3.1 직류 최대도체저항측정 7.3.1 최소 절연저항측정 7.3.1 최대 정전용량측정 7.3.2 유전정접측정 7.3.3 부분방전특성 7.3.4 교류내전압시험 7.4 물리적 특성시험 7.4.1.(1) 도체 수밀시험 7.4.1.(2) 중성선 수밀시험 7.4.1.(3) 도체수밀 혼화물 적하시험 7.4.2 절연층 및 반도전층 검사 7.4.3 반도전층의 체적저항율 측정 7.4.4 인장강도 및 신율 측정 7.4.5.(1) 절연체 수축(Shrink back) 시험 7.4.5.(2) 가열신축(Hot Creep)특성 시험 7.4.5.(3) 반도전층 시편가열 시험 7.4.5.(4) 가열 변형 시험 (Heat Distortion) 7.4.6 외부 반도전층 박리 시험 7.4.7.(2) 완성품 난연성 시험 7.4.7.(3) 외피 산소지수 시험 7.5 장기 과통전 시험 및 가속 수트리 시험 7.5.1.(1) 케이블 열화 7.5.1.(2) 전기적 특성 측정 7.5.1.(3) 교류 파괴 시험 7.5.1.(4) 물리적특성 시험 7.5.1.(5) 고온 충격전압 시험 7.5.1.(6) 저항안정시험 7.5.2.(1) 가속 수트리 열화 방법 7.5.2.(2) 부분방전 및 유전정접 측정 7.5.2.(3) 교류 파괴시험 7.5.2.(4) 물리적특성 시험 7.5.2.(5) 트리 관찰 7.5.2.(6) V-t 특성 7.6 열정·기계적 특성시험 7.6.2 열화 주기 7.6.3 전기적 특성 측정 7.6.4 물리적 특성 시험 7.7 절연압출공정 적합성시험 7.7.2 열적안정화 7.7.3 유전정접측정 7.7.4 교류파괴시험 |
7.2 Min. 0.001 mm 7.3.1 Min. 1 μΩ Max. 100 GΩ Max. 31.8 mF 7.3.2 Min. 1 x 10^-5 7.3.3 Min. 1 pC 7.3.4 Max. 960 kV 7.4.1.(1) Max. 507 hPa 7.4.1.(2) Max. 3 000 A 7.4.1.(3) Max. 200 ℃ 7.4.2 Min. 0.001 mm 7.4.3 Min. 100 mV Min. 10 mA 7.4.4 Max. 500 N 7.4.5.(1) Max. 200 ℃ Min. 0.01 mm 7.4.5.(2) Max. 200 ℃ Min. 0.01 mm 7.4.5.(3) Max. 190 ℃ 7.4.5.(4) Max. 300 ℃ Min. 0.01 mm 7.4.6 Max. 500 N 7.4.7.(2) Max. 480 s 7.4.7.(3) Min. 28 % 7.5.1.(1) Max. 3 000 A 7.5.1.(2) Min. 1 x 10^-5 Min. 1 pC 7.5.1.(3) Max. 960 kV 7.5.1.(4) Min. 0.001 mm 7.5.1.(5) Max. 2 600 kV Max. 3 000 A 7.5.1.(6) Max. 1 000 Ω·m 7.5.2.(1) Max. 80 kV Max. 3 000 A 7.5.2.(2) Min. 1 x 10^-5 Min. 1 pC 7.5.2.(3) Max. 960 kV 7.5.2.(4) Min. 0.001 mm 7.5.2.(5) Min. 0.001 mm 7.6.2 Max. 3 000 A 7.6.3 Min. 1 x 10^-5 Min. 1 pC 7.6.4 Min. 0.001 mm 7.7.2 Max. 3 000 A 7.7.3 Min. 1 x 10^-5 7.7.4 Max. 960 kV |
소재지 |
| ES-6145-0026:2023 |
22.9 kV 수트리억제 충실 알루미늄 전력케이블 7.1 외관검사 7.2 구조검사 7.3 전기적 특성시험 7.3.1 케이블의 저항 및 정전용량 7.3.1 최소 절연저항측정 7.3.1 최대 정전용량측정 7.3.2 유전정접측정 7.3.3 부분방전특성 7.3.4 교류내전압시험 7.4 물리적 특성시험 7.4.1.(1) 도체 수밀시험 7.4.1.(2) 중성선 수밀시험 7.4.1.(3) 도체수밀 혼화물 적하시험 7.4.2 절연층 및 반도전층 검사 7.4.3 반도전층의 체적저항율 측정 7.4.4 인장강도 및 신율 측정 7.4.5.(1) 절연체 수축(Shrink back) 시험 7.4.5.(2) 가열신축(Hot Creep)특성 시험 7.4.5.(4) 가열 변형 시험 (Heat Distortion) 7.4.6 외부 반도전층 박리 시험 7.5 장기 과통전 시험 및 가속 수트리 시험 7.5.1.(1) 케이블 열화 7.5.1.(2) 전기적 특성 측정 7.5.1.(3) 교류 파괴 시험 7.5.1.(4) 물리적특성 시험 7.5.1.(5) 고온 충격전압 시험 7.5.1.(6) 저항안정시험 7.5.2.(1) 가속 수트리 열화 방법 7.5.2.(2) 부분방전 및 유전정접 측정 7.5.2.(3) 교류 파괴시험 7.5.2.(4) 물리적특성 시험 7.5.2.(5) 트리 관찰 7.5.2.(6) V-t 특성 7.6 열정·기계적 특성시험 7.6.2 열화 주기 7.6.3 전기적 특성 측정 7.6.4 물리적 특성 시험 7.7 절연압출공정 적합성시험 7.7.2 열적안정화 7.7.3 유전정접측정 7.7.4 교류파괴시험 |
7.2 Min. 0.001 mm 7.3.1 Min. 10 μΩ Max. 100 GΩ Max. 31.8 mF 7.3.2 Min. 1 x 10^-5 7.3.3 Min. 1 pC 7.3.4 Max. 960 kV 7.4.1.(1) Max. 507 hPa 7.4.1.(2) Max. 3 000 A 7.4.1.(3) Max. 200 ℃ 7.4.2 Min. 0.001 mm 7.4.3 Min. 100 mV Min. 10 mA 7.4.4 Max. 500 N 7.4.5.(1) Max. 200 ℃ Min. 0.01 mm 7.4.5.(2) Max. 200 ℃ Min. 0.01 mm 7.4.5.(4) Max. 300 ℃ Min. 0.01 mm 7.4.6 Max. 500 N 7.5.1.(1) Max. 3 000 A 7.5.1.(2) Min. 1 x 10^-5 Min. 1 pC 7.5.1.(3) Max. 960 kV 7.5.1.(4) Min. 0.001 mm 7.5.1.(5) Max. 2 600 kV Max. 3 000 A 7.5.1.(6) Max. 1 000 Ω·m 7.5.2.(1) Max. 80 kV Max. 3 000 A 7.5.2.(2) Min. 1 x 10^-5 Min. 1 pC 7.5.2.(3) Max. 960 kV 7.5.2.(4) Min. 0.001 mm 7.5.2.(5) Min. 0.001 mm 7.6.2 Max. 3 000 A 7.6.3 Min. 1 x 10^-5 Min. 1 pC 7.6.4 Min. 0.001 mm 7.7.2 Max. 3 000 A 7.7.3 Min. 1 x 10^-5 7.7.4 Max. 960 kV |
소재지 |
| ES-8030-0001:2016 |
케이블 연소방지재 5.1 표3 시험방법 - 산소지수 - 저염소시험(할로겐화수소) - 냉열특성 - 굴곡특성 - 내유성 - 내염수성 - 내후성 7 표시사항 |
파장: 340 nm 이하 광량: 0.35 W/m² 이하 |
소재지-1 |
| ES-9905-0015:2017 |
광고물부착 방지물 3 재료 및 가공 5.1.1 밀착성 시험 5.1.2 도장막 두께 5.1.3 습도 시험 5.1.4 충돌 시험 5.1.5 내후성 시험 5.1.6 내염수성 시험 5.1.7 내산성 시험 5.1.8 부착력 시험 5.1.9 내열성 시험 5.1.10 내오염성 시험 |
인장하중: Max. 4.9 kN |
소재지-1 |
| GS-6145-0031:2023 |
345 kV/154 kV 가교폴리에틸렌 절연 광복합 전력케이블 및 접속함 6.3.6 인정시험 항목 및 방법 -표 1.1 전기시험전 절연체 두께 점검 1.2 접속함 구조 및 치수 검사 1.6 부분방전 시험 1.7 Tan δ 측정 1.8 열 사이클 전압시험 1.9 개폐 충격 내전압 시험 1.10 뇌 충격 내전압 시험 1.11 육안검사 1.12 반도전층 체적저항율 시험 2.1 광복합 케이블 구조시험 2.2 노화 전후의 절연체에 대한 기계적 성능시험 2.3 노화 전후의 방식층에 대한 기계적 성능시험 2.4 케이블 노화시험 2.5 PVC 방식층에 대한 가열감량 시험 2.6 방식층에 대한 고온 가압 시험 2.8 PVC 방식층에 대한 열충격 시험 2.10 XLPE 절연체에 대한 HOT SET 시험 2.12 XLPE 절연체에 대한 수축시험 2.13 PE방식층에 대한 수축시험 |
1.1: Min. 0.001 mm 1.2: Min. 0.001 mm 1.6: Min. 1 pC 1.7: Min. 5.3 x 10^-4 1.8: Max. 960 kV, Max. 5 000 A 1.9: Max. 1 550 kV 1.10: Max. 2 600 kV 1.12: - 1.13: Min. 100 mV, Min. 10 mA 2.1: Min. 0.001 mm 2.2: Max. 490 N 2.3: Max. 490 N 2.4: Max. 490 N 2.5: Max. 300 g 2.6: Min. 0.001 mm 2.8: Max. 150 ℃ 2.10: Max. 200 ℃, Min. 0.01 mm 2.12: Max. 200 ℃, Min. 0.01 mm 2.13: Max. 200 ℃, Min. 0.01 mm |
소재지 |
| GS-6145-0032:2023 |
345 kV/154 kV 가교폴리에틸렌 절연 전력케이블 및 접속함 6.3.5 인정시험 항목 및 방법 - 표 1.1 전기시험전 절연체 두께 점검 1.2 접속함 구조 및 치수 검사 1.5 부분방전 시험 1.6 Tan δ 측정 1.7 열 사이클 전압시험 1.8 개폐 충격 내전압 시험 1.9 뇌 충격 내전압 시험 1.10 중간접속함 수분침투시험 1.11 육안검사 1.12 반도전층 체적저항율 시험 2.1 케이블 구조시험 2.2 노화 전후의 절연체에 대한 기계적 성능시험 2.3 노화 전후의 방식층에 대한 기계적 성능시험 2.4 케이블 노화시험 2.5 PVC 방식층에 대한 가열감량 시험 2.6 방식층에 대한 고온 가압 시험 2.7 PVC 방식층에 대한 내한성 시험 2.8 PVC 방식층에 대한 열충격 시험 2.10 XLPE 절연체에 대한 HOT SET 시험 2.13 XLPE 절연체에 대한 수축시험 2.14 PE방식층에 대한 수축시험 |
1.1 Min. 0.001 mm 1.2 Min. 0.001 mm 1.5 Min. 1 pC 1.6 Min. 5.3 x 10^-4 1.7 Max. 960 kV, Max. 5 000 A 1.8 Max. 1 550 kV 1.9 Max. 2 600 kV 1.10 Max. 3 000 A 1.12 Min. 100 mV Min. 10 mA 2.1 Min. 0.001 mm 2.2 Max. 490 N 2.3 Max. 490 N 2.4 Max. 490 N 2.5 Max. 300 g 2.6 Max. 50 % 2.7 Min. 100 g Max. -20 ℃ 2.8 Max. 150 ℃ 2.10 Max. 200 ℃ Min. 0.01 mm 2.13 Max. 200 ℃ Min. 0.01 mm 2.14 Max. 200 ℃Min. 0.01 mm |
소재지 |
| GS-6145-0081:2023 |
154 kV 가교폴리에틸렌 절연 평활형 전력케이블 및 접속함 6.3.4 인정시험 항목 및 방법 - 표 1.1 전기시험전 절연체 두께 점검 1.2 접속함 구조 및 치수 검사 1.5 부분방전 시험 1.6 Tan δ 측정 1.7 열 사이클 전압시험 1.8 뇌 충격 내전압 시험 1.9 중간접속함 수분침투시험 1.10 육안검사 1.11 반도전층 체적저항율 시험 2.4 용접부 기계적 특성 시험 2.5 금속시스의 점착강도 시험 2.6 단락시험 3.1 케이블 구조시험 3.2 노화 전후의 절연체에 대한 기계적 성능시험 3.3 노화 전후의 방식층에 대한 기계적 성능시험 3.4 케이블 노화시험 3.5 방식층에 대한 고온 가압 시험 3.7 XLPE 절연체에 대한 HOT SET 시험 3.9 금속차폐층에 대한 수밀시험 3.10 XLPE 절연체에 대한 수축시험 3.11 PE방식층 또는 HFFR에 대한 수축시험 |
1.1 Min. 0.001 mm 1.2 Min. 0.001 mm 1.5 Min. 1 pC 1.6 Min. 5.3 x 10^-4 1.7 Max. 960 kV, Max. 5 000 A 1.8 Max. 2 600 kV 1.9 Max. 3 000 A 1.10 - 1.11 Max. 1 000 Ω·m 2.4 Max. 30 kN 2.5 Max. 30 kN 2.6 Max. 50 kA 3.1 Min. 0.001 mm 3.2 Max. 490 N 3.3 Max. 490 N 3.4 Max. 490 N 3.5 Max. 50 % 3.7 Max. 175 % 3.8 (2.5 ± 0.5) % 3.9 Max. 5 000 A 3.10 Max. (130 ± 3) ℃ 3.11 Max. (80 ± 2) ℃ |
소재지 |
| GS-6145-0097:2024 |
22.9 kV 친환경 충실 알루미늄 전력케이블 7.1 외관검사 7.2 구조검사 7.3 전기적 특성시험 7.4.1 수밀관련 시험 7.4.2 절연층 및 반도전층 검사 7.4.3 반도전층의 체적저항율 측정 7.4.4 인장강도 및 신율 측정 7.4.5 신축 변형 특성 시험 7.4.6 외부 반도전층 박리 시험 7.5.1.1.(1) 전기적 특성 측정 7.5.1.1.(2) 교류 파괴 시험 7.5.1.1.(3) 물리적특성 시험 7.5.1.1.(4) 고온 충격전압 시험 7.5.1.1.(5) 저항안정시험 7.5.1.2.(1) 열화방법 7.5.1.2.(2) 전기적 특성 측정 7.5.1.2.(3) 교류 파괴 시험 7.5.1.2.(4) 물리적특성 시험 7.5.1.2.(5) 고온 충격전압 시험 7.5.1.3.(1) 가속 수트리 열화 방법 7.5.1.3.(2) 전기적 특성측정 7.5.1.3.(3) 부분방전 및 유전정접 측정 7.5.1.3.(4) 교류 파괴시험 7.5.1.3.(5) 물리적특성 시험 7.5.1.3.(6) V-t 특성 (참고시험) 7.5.2.1.(1) 전기적 특성 측정 7.5.2.1.(2) 교류 파괴 시험 7.5.2.1.(3) 물리적특성 시험 7.5.2.1.(4) 고온 충격전압 시험 7.5.2.1.(5) 저항안정시험 7.5.2.2.(3) 전기적 특성 측정 7.5.2.2.(4) 부분방전 및 유전정접 측정 7.5.2.2.(5) 교류 파괴 시험 7.5.2.2.(6) 물리적특성 시험 7.5.2.2.(7) V-t 특성 (참고시험) 7.6.2 열화 주기 7.6.3 전기적 특성 측정 7.6.4 물리적 특성 시험 7.7.2 유전정접측정 7.7.3 교류파괴시험 |
7.2 Min. 0.001 mm 7.3 Min. 1 μΩ Max. 100 GΩ Max. 31.8 mF Min. 1 x 10^-5 Min. 1 pC Max. 960 kV 7.4.1 Max. 507 hPa Max. 3 000 A Max. 200 ℃ 7.4.2 Min. 0.001 mm 7.4.3 Min. 100 mV Min. 10 mA 7.4.4 Max. 500 N 7.4.5 Max. 200 ℃ Min. 0.01 mm 7.4.6 Max. 500 N- 7.5.1.1.(1) Min. 1 x 10^-5 Min. 1 pC 7.5.1.1.(2) Max. 960 kV 7.5.1.1.(3) Min. 0.001 mm 7.5.1.1.(4) Max. 2 600 kV Max. 3 000 A 7.5.1.1.(5) Max. 1 000 Ω·m 7.5.1.2.(1) Max. 3 000 A 7.5.1.2.(2) Min. 1 x 10^-5 Min. 1 pC 7.5.1.2.(3) Max. 960 kV 7.5.1.2.(4) Min. 0.001 mm 7.5.1.2.(5) Max. 2 600 kV Max. 3 000 A 7.5.1.3.(1) Max. 80 kV Max. 3 000 A 7.5.1.3.(2) Min. 1 x 10^-5 Min. 1 pC 7.5.1.3.(3) Min. 1 x 10^-5 Min. 1 pC 7.5.1.3.(4) Max. 960 kV 7.5.1.3.(5) Min. 0.001 mm 7.5.2.1.(1) Min. 1 x 10^-5 Min. 1 pC 7.5.2.1.(2) Max. 960 kV 7.5.2.1.(3) Min. 0.001 mm 7.5.2.1.(4) Max. 2 600 kV Max. 3 000 A 7.5.2.1.(5) Max. 1 000 Ω·m 7.5.2.2.(3) Min. 1 x 10^-5 Min. 1 pC 7.5.2.2.(4) Min. 1 x 10^-5 Min. 1 pC 7.5.2.2.(5) Max. 960 kV 7.5.2.2.(6) Min. 0.001 mm 7.6.2 Max. 3 000 A 7.6.3 Min. 1 x 10^-5 Min. 1 pC 7.6.4 Min. 0.001 mm 7.7.2 Min. 1 x 10^-5 7.7.3 Max. 960 kV |
소재지 |
| IEC 60099-4:2014 |
Surge arresters - part 4: Metal-oxide surge arresters without gaps for a.c. systems Ⅰ. Porcelain-housed arresters 8.2 Insulation withstand tests 8.3 Residual voltage tests 8.4 Test to verify long term stability under continuous operating voltage 8.5 Test to verify the repetitive charge transfer rating, Ors 8.6 Heat dissipation behaviour of test sample 8.7 Operating duty test 8.8 Power-frequency voltage-versus-time test 8.9 Tests of arrester disconnector 8.10 Short-circuit tests 8.11 Test of the bending moment 8.12 Environmental tests 8.14 Radio interference voltage (RIV) test Ⅱ. Polymer-housed surge arresters 10.8.2 Insulation withstand tests 10.8.3 Residual voltage tests 10.8.4 Test to verify long term stability under continuous operating voltage 10.8.5 Test to verify the repetitive charge transfer rating, Qrs 10.8.6 Heat dissipation behaviour of test sample 10.8.7 Operating duty tests 10.8.8 Power frequency voltage-versus-time test 10.8.9 Tests of arrester disconnector 10.8.10 Short-circuit tests 10.8.11 Test of the bending moment 10.8.14 Radio interference voltage (RIV) test 10.8.17 Weather ageing test Ⅲ. Gas-insulated metal enclosed arresters(GIS-arresters) 11.8.2 Insulation withstand tests 11.8.3 Residual voltage tests 11.8.4 Test to verify long term stability under continuous operating voltage 11.8.5 Test to verify the repetitive charge transfer rating, Qrs 11.8.6 Heat dissipation behaviour of test sample 11.8.7 Operating duty tests 11.8.8 Power-frequency voltage-versus-time test 11.8.10 Short-circuit tests11.8.14 Radio interference voltage (RIV) test |
8.2 Max. 960 kV Max. 2 600 kV(LI) Max. 1 550 kV(SI) 8.3 Max. 20 kA 8.4 1 000 h 8.5 Max. 20 kA 8.6 140 ℃ 8.7 Max. 100 kA 8.8 Max. 20 kA 8.9 Max. 800 A 8.10 Max. 80 kA 8.11 Max. 100 kN 8.12 10 cycles, 96 h, 10 pC 8.14 Max. 600 kV, 0.5 MHz ~ 2 MHz 10.8.2 Max. 960 kV Max. 2 600 kV(LI) Max. 1 550 kV(SI) 10.8.3 Max. 20 kA 10.8.4 1 000 h 10.8.5 Max. 20 kA 10.8.6 140 ℃ 10.8.7 Max. 20 kA 10.8.8 Max. 20 kA 10.8.9 Max. 800 A 10.8.10 Max. 80 kA 10.8.11 Max. 100 kN 10.8.14 Max. 600 kV, 0.5 MHz ~ 2 MHz 10.8.17 1 000 h 11.8.2 Max. 960 kV Max. 2 600 kV(LI) Max. 1 550 kV(SI) 11.8.3 Max. 20 kA 11.8.4 1 000 h 11.8.5 Max. 20 kA 11.8.6 140 ℃ 11.8.7 Max. 100 kA 11.8.8 Max. 20 kA 11.8.10 Max. 80 kA 11.8.14 Max. 600 kV,0.5 MHz ~ 2 MHz |
소재지 |
| IEC 60137:2017 |
Insulated bushings for alternating voltages above 1 000 V 8.2 Dry or wet power-frequency voltage withstand test 8.3 Long duration power-frequency voltage withstand test (ACLD) 8.4 Dry lightning impulse voltage withstand test 8.8 Temperature rise test 8.9 Verification of thermal short-time current withstand |
8.2 Max. 960 kV (dry) Max. 520 kV(wet) 8.3 Max. 520 kV 8.4 Max. 2 600 kV 8.8 Max. 8 000 A 8.9 single-phase 100 kVA, 5 000 A |
소재지 |
| IEC 60137:2017 |
Insulated bushings for alternating voltages above 1 000 V 8.2 Dry or wet power-frequency voltage withstand test 8.4 Dry lightning impulse voltage withstand test 8.7 Electromagnetic compatibility tests (EMC) 8.8 Temperature rise test 8.9 Verification of thermal short-time current withstand 8.14 Verification of dimensions |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ Wet: (0 ~ 5) mm/min Temperature rise: 1Փ Max. 8 000 A Short-time current: Max. 600 V 100 kA |
소재지-1 |
| IEC 60383-1:2023 |
Insulators for overhead lines with a nominal voltage above 1 000 V - part 1: Ceramic or glass insulator units for AC systems - Definitions, test methods and acceptance criteria 12 Dry Lightning impulse voltage tests 13 Wet power-frequency voltage tests 17 Verification of the dimensions 18 Electro-mechanical failing load test 19 Mechanical failing load test 20 Thermal-mechanical performance test 24 Temperature cycle test |
12 : Max. 2 600 kV 13 : Max. 520 kV 18 : Max. 100 kV 500 kN 19 : Max. 500 kN 20 : (-50 ~ 100) ℃ Max. 300 kN 24 : (2 ~ 99) ℃ |
소재지 |
| IEC 60502-2:2024 |
Power cables with extruded insulation and their accessories for rated voltages from 1 kV(Um = 1.2 kV) up to 30 kV(Um = 36 kV) - Part 2: Cables for rated voltages of 6 kV(Um = 7.2 kV) up to 30 kV(Um = 36 kV) 18.2.5 Partial discharge test 18.2.6 Tan δ measurement for cables of rated voltage 6/10 (12) kV and above 18.2.7 Heating cycle test 18.2.8 Impulse test followed by a voltage test 18.2.9 Voltage test for 4 h 18.2.10 Resistivity of semi-conducting screens 18.3.2 Insulation resistance measurement at ambient temperature 18.3.3 Insulation resistance measurement at maximum conductor temperature 18.3.4 Voltage test for 4 h 18.3.5 Impulse test 19.2 Measurement of thickness of insulation 19.3 Measurement of thickness of non-metal sheaths (including extruded separation sheaths, but excluding inner coverings) 19.4 Measurement of thickness of lead sheath 19.5 Tests for determining the mechanical properties of insulation before and after ageing 19.6 Tests for determining the mechanical properties of non-metal sheaths before and after ageing 19.7 Additional ageing test on pieces of completed cables 19.9 Pressure test at high temperature on insulations and non-metal sheaths 19.11 Test for resistance of PVC insulation and sheaths to cracking (heat shock test) 19.13 Hot set test for EPR, HEPR and XLPE insulations and elastomeric sheaths 19.18 Shrinkage test for XLPE insulation 19.22 Shrinkage test for PE and halogen free oversheaths 19.23 Strippability test for insulation screen19.24 Water penetration test |
18.2.5 Min. 1 pC 18.2.6 Min. 1 x 10^-5 18.2.7 Max. 3 000 A 18.2.8 Max. 800 kV 18.2.9 Max. 300 kV 18.2.10 Min. 100 mV Min. 10 mA 18.3.2 Max. 100 GΩ 18.3.3 Max. 100 GΩ 18.3.4 Max. 300 kV 18.3.5 Max. 800 kV 19.2 Min. 0.001 mm 19.3 Min. 0.001 mm 19.4 Min. 0.001 mm 19.5 Max. 500 N 19.6 Max. 500 N 19.7 Max. 500 N 19.9 Max. 200 ℃ Min. 0.001 mm 19.11 Max. 200 ℃ 19.13 Max. 200 ℃ Min. 0.01 mm 19.18 Max. 200 ℃ Min. 0.01 mm 19.22 Max. 200 ℃ Min. 0.01 mm 19.23 Max. 500 N 19.24 Max. 3 000 A |
소재지 |
| IEC 60840:2023 |
Power cables with extruded insulation and their accessories for rated voltages above 30 kV(Um = 36 kV) up to 150 kV(Um = 170 kV) - Test methods and requirements 12.4.4 Partial discharge tests 12.4.5 Tan δ measurement 12.4.6 Heating cycle voltage test 12.4.7 Lightning impulse voltage test followed by a power frequency voltage test 12.4.8 Examination 12.4.9 Resistivity of semi-conducting screens 12.5.1 Check of cable construction 12.5.2 Tests for determining the mechanical properties of insulation before and after ageing 12.5.3 Tests for determining the mechanical properties of oversheaths before and after ageing 12.5.4 Ageing tests on pieces of complete cable to check compatibility of materials 12.5.5 Loss of mass test on PVC oversheaths of type ST2 12.5.6 Pressure test at high temperature on oversheaths 12.5.7 Test on PVC oversheaths (ST1, ST2) at low temperature 12.5.8 Heat shock test for PVC oversheaths (ST1 and ST2) 12.5.10 Hot set test for EPR, HEPR and XLPE insulations 12.5.15 Water penetration test 12.5.17 Shrinkage test for PE, HDPE and XLPE insulations 12.5.18 Shrinkage test for PE oversheaths (ST3 and ST7) and LSHF oversheaths (ST12) |
12.4.4 Min. 1 pC 12.4.5 Min. 1 x 10^-5 12.4.6 Max. 960 kV Max. 5 000 A 12.4.7 Max. 960 kV 12.4.9 Min. 100 mV Min. 10 mA 12.5.2 Min. 0.001 mm 12.5.3 Max. 500 N 12.5.4 Max. 500 N 12.5.5 Max. 500 N 12.5.6 Max. 210 g 12.5.7 Max. 200 ℃ Min. 0.001 mm 12.5.8 Max. -40 ℃ 12.5.9 Max. 200 ℃ 12.5.15 Max. 5 000 A 12.5.17 Max. 200 ℃ Min. 0.01 mm 12.5.18 Max. 200 ℃ Min. 0.01 mm |
소재지 |
| IEC 61109:2025 |
Insulators for overhead lines - Composite suspension and tension insulators for a.c. systems with a nominal voltage greater than 1 000 V - Definitions, test methods and acceptance criteria 9.3 Product specific pre-stressing for tests on interfaces and connections of end fittings 9.4 Assembled core load-time tests 10.2 Electrical tests on string insulator units 10.3 Damage limit proof test and test of the tightness of the interface between end fittings and insulator housing 11.2 Verification of dimensions (E1 + E2) 11.3 Verification of the end fittings (E2) 11.4 Verification of tightness of the interface between end fittings and insulator housing (E2) and of the specified mechanical load, SML (E1) 11.5 Galvanizing test (E2) 11.6 Minimum sheath thickness(E1) 11.7 Re-testing procedure 12.1 Mechanical routine test 12.2 Visual examination |
Load : Max. 270 kN AC: Max. 300 kV 60 Hz LI: Max. 600 kV Wet condition: (0 ~ 5) mm/min adhesion amount : Max. 1 521 μm (10 860 g/m²) |
소재지-1 |
| IEC 61467:2008 |
Insulators for overhead lines - Insulator strings and sets for lines with a nominal voltage greater than 1 000 V - AC power arc tests |
single-phase 50 kA |
소재지 |
| IEC 61952:2008 |
Insulators for overhead lines - Composite line post insulators for A.C. systems with a nominal voltage greater than 1 000 V - Definitions, test methods and acceptance criteria 10.2.1 Tests on interfaces and connections of end fittings 10.2.2 Tracking and erosion test 10.2.3 Tests on core material 11.1 Electric tests - Dry lightning impulse withstand voltage test 11.1 Electric tests - Wet power-frequency test 11.1 Electric tests - Wet switching impulse withstand voltage test for insulators intended for systems with Um 300 kV 11.2 Mechanical tests 12.2 Verification of dimensions 12.4 Verification of the SCL |
10.2.1 : (-50 ~ 100) ℃, Max. 300 kN / (2 ~ 99) ℃/ Max. 2 600 kV / Max 960 kV 10.2.2 : Max. 100 kV 10.2.3 : Max. 22 kV 11.1(Electric tests - Dry lightning impulse withstand voltage test) : Max. 2 600 kV 11.1(Electric tests - Wet power-frequency test) : Max. 520 kV 11.1(Electric tests - Wet switching impulse withstand voltage test) : Max. 1 550 kV 11.2 : Max. 500 kN 12.4 : Max. 500 kN |
소재지 |
| IEC 61952:2008 |
Insulators for overhead lines - Composite line post insulators for A.C. systems with a nominal voltage greater than 1 000 V - Definitions, test methods and acceptance criteria 10.2 Test specimens for IEC 62217 10.4.2 Tensile load test 11.1 Electrical tests 11.2 Mechanical tests 12.2 Verification of dimensions (E1 + E2) 12.3 Galvanizing test (E1 + E2) 12.4 Verification of the SCL (E1) 12.5 Re-testing procedure 13.1 Tensile load test 13.2 Visual examination |
Tensile force: Max. 270 kN AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ Wet: (0 ~ 5) mm/min |
소재지-1 |
| IEC 62067:2022 |
Power cables with extruded insulation and their accessories for rated voltages above 150 kV (Um = 170 kV) up to 500 kV(Um = 550 kV) - Test methods and requirements 12.4.4 Partial discharge tests 12.4.5 Tan δ measurement 12.4.6 Heating cycle voltage test 12.4.7 Impulse voltage tests 12.4.8 Examination 12.4.9 Resistivity of semi-conducting screens 12.5.2 Check of cable construction 12.5.3 Tests for determining the mechanical properties of insulation before and after ageing 12.5.4 Tests for determining the mechanical properties of oversheaths before and after ageing 12.5.5 Ageing tests for pieces of cable to check compatibility of materials 12.5.6 Loss of mass test on PVC oversheaths of type ST2 12.5.7 Pressure test at high temperature on oversheaths 12.5.8 Test on PVC oversheaths (ST1, ST2) at low temperature 12.5.9 Heat shock test for PVC oversheaths (ST1 and ST2) 12.5.11 Hot set test for EPR and XLPE insulations 12.5.15 Water penetration test |
12.4.4 Min. 1 pC 12.4.5 Min. 5.3 x 10^-4 12.4.6 Max. 960 kV, Max. 5 000 A 12.4.7 Max. 960 kV 12.4.9 Min. 100 mV Min. 10 mA 12.5.2 Min. 0.001 mm 12.5.3 Max. 490 N 12.5.4 Max. 490 N 12.5.5 Max. 490 N 12.5.6 Max. 300 g 12.5.7 Max. 200 ℃ Min. 0.001 mm 12.5.8 Max. -20 ℃ 12.5.9 Max. 200 ℃ 12.5.11 Max. 200 ℃ Min. 0.01 mm 12.5.15 Max. 5 000 A |
소재지 |
| IEC 62196-1:2022 |
Plugs, socket-outlets, vehicle connectors and vehicle inlets - Conductive charging of electric vehicles - Part 1: General requirements 9 Dimensions 12 Provisions forprotective earthing 15 Resistance to ageingof rubber andthermoplastic material 20 Degrees ofprotection 21 Insulation resistanceand dielectric strength 23.3 No-load endurance test 24 Temperature rise 26.2 Degree ofprotection 26.3 Drop test 26.4 Flexing test 26.5 Cable gland test 27 Screws, currentcarrying parts andconnections 33.2 Vehicle drive over 34 Thermal cycling 36 Misalignment 37 Contact endurance test |
Rated voltage : Less than or equal to AC 690 V Less than or equal to DC 1 500 V Rated current : Less than or equal to AC 250 A Less than or equal to DC 400 A IR: Max. 2 000 MΩ Temperature rise: 8 000A 60 Hz |
소재지-1 |
| IEC 62196-2:2022 |
Plugs, socket-outlets, vehicle connectors and vehicle inlets – Conductive charging of electric vehicles – Part 2: Dimensional compatibility requirements for AC pin and contact-tube accessories 9 Dimensions 12 Provisions forprotective earthing 15 Resistance to ageingof rubber andthermoplastic material 20 Degrees ofprotection 21 Insulation resistanceand dielectric strength 23.3 No-load endurance test 24 Temperature rise 26.2 Ball impact 26.3 Drop test 26.4 Flexing test 26.5 Cable gland test 27 Screws, currentcarrying parts andconnections 33.2 Vehicle drive over 34 Thermal cycling 36 Misalignment 37 Contact endurance test |
Rated voltage : Equal to or less than AC 480 V Rated current : Equal to or less than AC 70 A IR: Max. 2 000 MΩ Temperature rise: 8 000A 60 Hz |
소재지-1 |
| IEC 62196-3:2022 |
Plugs, socket-outlets, vehicle connectors and vehicle inlets – Conductive charging of electric vehicles – Part 3: Dimensional compatibility requirements for DC and AC/DC pin and contact-tube vehicle couplers 9 Dimensions 12 Provisions forprotective earthing 15 Resistance to ageingof rubber andthermoplastic material 20 Degrees ofprotection 21 Insulation resistanceand dielectric strength 23.3 No-load endurance test 24 Temperature rise 26.2 Ball impact 26.3 Drop test 26.4 Flexing test 26.5 Cable gland test 27 Screws, currentcarrying parts andconnections 33.2 Vehicle drive over 34 Thermal cycling 36 Misalignment 37 Contact endurance test |
Rated voltage : Less than or equal to AC 1 500 V Less than or equal to DC 1 500 V Rated current : Less than or equal to AC 250 A Less than or equal to DC 250 A IR: Max. 2 000 MΩ Temperature rise: 8 000A 60 Hz |
소재지-1 |
| IEC 62217:2012 |
Polymeric HV insulators for indoor and outdoor use - General definitions, test methods and acceptance criteria 9.2 Tests on interfaces and connections of end fittings 9.3 Tests on shed and housing material 9.4 Tests on the core material |
AC: Max. 300 kV, 60 Hz LI: Max. 600 kV, 30 kJ |
소재지-1 |
| IEC 62895: 2017 |
High voltage direct current (HVDC) power transmission - Cables with extruded insulation and their accessories for rated voltages up to 320 kV for land applications - Test methods and requirements 12.4.4 Heating cycle voltage test 12.4.6 Examination 12.4.7 Resistivity of semi-conducting screens 12.5.2 Check of cable construction 12.5.3 Tests for determining the mechanical properties of insulation before and after ageing 12.5.4 Tests for determining the mechanical properties of oversheaths before and after ageing 12.5.5 Ageing tests on pieces of complete cable to check compatibility of materials 12.5.6 Loss of mass test on PVC oversheaths of type ST2 12.5.7 Pressure test at high temperature on oversheaths 12.5.8 Test on PVC oversheaths (ST1 and ST2) at low temperature 12.5.9 Heat shock test for PVC oversheaths (ST1 and ST2) 12.5.11 Hot set test for EPR and XLPE insulations 12.5.12 Measurement of density of HDPE insulation 12.5.13 Measurement of carbon black content of black PE oversheaths (ST3 and ST7) 12.5.14 Test under fire conditions |
12.4.4 Max. DC 700 kV, Max. AC 5 000 A 12.4.7 Min. 100 mV, Min. 10 mA 12.5.2 Min. 0.001 mm 12.5.3 Max. 500 N 12.5.4 Max. 500 N 12.5.5 Max. 500 N 12.5.6 Max. 210 g 12.5.7 Max. 200 ℃, Min. 0.001 mm 12.5.8 Max. -40 ℃ 12.5.9 Max. 200 ℃ 12.5.11 Max. 200 ℃, Min. 0.01 mm 12.5.12 Max. 300 g 12.5.13 Max. 1 000 ℃ 12.5.14 480 s |
소재지 |
| IEC TS 62196-3-1:2020 |
Plugs, socket-outlets, vehicle connectors and vehicle inlets – Conductive charging of electric vehicles – Part 3-1: Vehicle connector, vehicle inlet and cable assembly for DC charging intended to be used with a thermal management system 9 Dimensions 12 Provisions for protective earthing 15 Resistance to ageing of rubber and thermoplastic material 20 Degrees of protection 21 Insulation resistance and dielectric strength 24 Temperature rise 26.2 Degree of protection 26.3 Rewirable plugs and vehicle connectors 26.4 Non-rewirable accessories 26.5 Cable gland test 27 Screws, current carrying parts and connections 33.2 Vehicle drive over |
Rated voltage : Less than or equal to AC 1 500 V Less than or equal to DC 1 500 V Rated current : Less than or equal to AC 250 A Less than or equal to DC 250 A IR: Max. 2 000 MΩ Temperature rise: 8 000A 60 Hz |
소재지-1 |
| IEEE Std 386:2016 |
IEEE Standard for Separable Insulated Connector Systems for Power Distribution Systems Rated 2.5 kV through 35 kV 7.1 Production tests 7.2 Design tests 7.3 Test conditions 7.4 Partial discharge test 7.5 Dielectric tests 7.9 Current-cycling test for uninsulated components of 600-A amd 900-A insulated connectors 7.10 Current-cycling test for 200-A insulated connectors 7.11 Current-cycling test for 600-A and 900-A insulated connectors 7.12 Accelerated sealing life test 7.13 Cable pull-out test (tensile strength 7.14 Operating-force test for seperable connectors with an operating eye 7.15 Operating-eye test 7.16 Test point cap test 7.17 Test point tests 7.19 Bushing well stud torque test 7.20 Thermal cycle withstand test 7.21 Tee separable insulated connector interchangeability test |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ Temperature rise: 8 000 A 60 Hz |
소재지-1 |
| IEEE Std 404:2012 |
IEEE standard for Extruded and Laminated Dielectric Shielded Cable Joints Rated 2.5 kV to 500 kV 7.1 Design tests and testing sequence for all joint types 7.2 Design test conditions 7.3 Dielectric integrity tests 7.4 Voltage tests 7.6 Cyclic aging test for extruded dielectric and transition joints 7.7 High-voltage time test 7.8 Sectionalizer tests 7.9 Shielding test 7.10 Joint metallic-shield and jacketing components 7.11 Connector thermal and mechanical tests |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ |
소재지-1 |
| KS C 3104:2019 |
전기용 경동 연선 8.1 겉모양 8.2 구조 8.3 인장하중 12 표시 |
인장하중: Max. 270 kN 저항: 1 mΩ ~ 10 Ω |
소재지-1 |
| KS C 4307:2013 |
주상 변압기부싱 7.1 구조시험 7.2 온도상승시험 7.3 절연저항시험 7.4 상용주파내전압시험 7.5 충격내전압시험 7.9 과전류강도시험 |
7.2 Max. 8 000 A 7.3 (250 V, 500 V, 1 000 V) 2 000 ㏁ 7.4 Max. 960 kV 7.5 Max. 2 600 kV 7.9 Max. 63 kA |
소재지 |
| KS C 4315:1998 |
내염형 일단 접지 주상 변압기 부싱(22.9 kV) 6.1 구조검사 6.2 온도시험 6.3 절연저항시험 6.4 상용주파내전압시험 6.5 충격내전압시험 6.9 과전류강도시험 |
6.2 Max. 8 000 A 6.3 (1 000 V) 2 000 ㏁ 6.4 Max. 960 kV 6.5 Max. 2 600 kV 6.9 Max. 63 kA |
소재지 |
| KS C 4315:1998 |
내염형 일단 접지 주상 변압기 부싱(22.9 kV) 6.1 구조검사 6.2 온도 시험 6.3 절연 저항 시험 6.4 상용 주파 내전압 시험 6.5 충격 내전압 시험 6.6 가열 시험 6.7 에관의 냉열 시험 6.8 에관의 흡습 시험 6.9 과전류 강도 시험 |
온도상승: 단상 Max. 40 A IR: Max. 2 000 MΩ AC: Max. 42 kV 60 Hz LI: Max. 125 kV 30 kJ 주수율: (0 ~ 5) mm/min 냉열: - 냉수조: (0 ~ 20) ℃ - 온수조: (60 ~ 100) ℃ 단시간: 1 000 A 이하 |
소재지-1 |
| KS C IEC 61109:2008 |
가공 선로용 애자 – 공칭 전압 1 000 V를 초과하는 교류 시스템용 복합 현수애자 및 인류애자 - 정의, 시험방법 및 허용 기준
10.2 IEC 62217:2005에 따른 시험품 10.3 IEC 62217:2005에 따른 제품 특성 사전 스트레스 11.1 전기적 시험 11.2 단말 연결체와 애자 하우징 사이의 계면에 대한 손상 한계 12 샘플시험 |
하중 Max. 270 kN AC: Max. 300 kV, 60 Hz LI: Max. 600 kV, 30 kJ 주수: (0 ~ 5) mm/min |
소재지-1 |
| ▶ 대전력, 고전압 기기 |
| ES-5920-0002:2023 |
특고압 컷아우트 스위치 6.1.1 구조 및 외관검사(부속품 포함) 6.1.2 상용주파 내전압시험(건조) 6.1.3 상용주파 내전압시험(주수) 6.1.4 충격내전압시험 6.1.6 전파장애시험 6.1.7 온도상승시험 6.1.8 무전압개폐시험 6.1.9 열적 사이클시험 6.1.10 냉열시험 6.1.11 흡습시험 6.1.12 하중시험 6.1.13 퓨즈홀더 호환사용시험 6.1.14 도금시험 |
부착량: Max. 1 533 μm (10 900 g/m²) RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz 주수율: (0 ~ 5) mm/min 온도상승: 8 000 A 60Hz 챔버 : (-40 ~ 100) ℃ |
소재지-1 |
| ES-5920-0011:2020 |
25.8 kV 폴리머 컷아우트 스위치 6.1.1 구조 및 외관검사 6.1.2 상용주파 내전압시험(건조) 6.1.3 상용주파 내전압시험(주수) 6.1.4 충격내전압시험 6.1.5 차단시험 6.1.6 전파장애시험 6.1.7 온도상승시험 6.1.8 무전압개폐시험 6.1.9 열적 사이클시험 6.1.10 내오손시험 6.1.11.a 수분침투시험 6.1.11.b 염색용액침투시험 6.1.11.c 수분확산시험 6.1.12 접착력시험 6.1.13 하중시험 6.1.16 퓨즈홀더 호환사용시험 6.1.17 복합가속열화시험 |
6.1.2 Max. 300 kV 6.1.3 Max. 300 kV 6.1.4 Max. 800 kV 6.1.5 63 kA 6.1.6 Max. 600 kV, 0.5 MHz ~ 2 MHz 6.1.7 Max. 8 000 A 6.1.9 (4 ~ 99) ℃ 6.1.10 Max. 33 kV 6.1.11.a 100 h , 2 500 kV/us, Max. 300 kV 6.1.11.c 100 h 6.1.13 Max. 100 kN 6.1.16 8 000A 6.1.17 33 kV 2 A, (-20 ~ 80) ℃, UV B lamp 50 kN |
소재지 |
| ES-5920-0011:2020 |
25.8 kV 폴리머 컷아우트 스위치 6.1.1 구조 및 외관검사 6.1.2 상용주파 내전압시험(건조) 6.1.3 상용주파 내전압시험(주수) 6.1.4 충격내전압시험 6.1.6 전파장애시험 6.1.7 온도상승시험 6.1.8 무전압개폐시험 6.1.9 열적 사이클시험 6.1.11 절연재료시험 6.1.12 접착력 시험 6.1.13 하중시험 6.1.14 도금시험 6.1.15 절연커버 성능시험 6.1.16 퓨즈홀더 호환사용시험 6.1.17 복합가속열화시험 |
전류: Max. 12 000 A 부착량: Max. 1 533 μm (10 900 g/m²) RIV: Min. 6.5 μV AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ 주수율: (0 ~ 5) mm/min 온도상승: 8 000 A 60 Hz |
소재지-1 |
| ES-5925-0002:2022 |
25.8 kV 가스절연 부하개폐기(지중용) 7.2.1 구조 및 외관검사 7.2.2 절연내력시험 7.2.3 주회로 저항측정 7.2.5 단시간전류시험 7.2.7 기밀시험 7.2.10 전류개폐용량시험 7.2.11 정격투입전류시험 7.2.12 무전압개폐 및 환경시험 7.2.13 온도안정화시험 7.2.15 절연저항측정 7.2.16 직류내전압시험 7.2.17 부분방전시험 7.2.25 내부고장 아크시험 7.2.26 제어함 구조 및 외관시험 7.2.28 제어회로 내환경시험 7.2.29 제어기능 확인시험 7.2.30 시스템연결 동작시험 |
7.2.2 Max. 230 kV Max. 670 kV 7.2.3 1 μΩ ~ 1 Ω 7.2.5 Max. 180 kA 7.2.7 Min. 0.1 mL/m3 7.2.10 Max. 1 600 A 7.2.11 Max. 63 kA 7.2.13 Max. 8 000 A 7.2.15 Max. 2 000 MΩ 7.2.16 Max. 400 kV 7.2.17 Min. 1 pC 7.2.25 Max. 63 kA 7.2.28 (-30 ~ 105) ℃, Max. 95 % R.H. |
소재지 |
| ES-5925-0002:2022 |
25.8 kV 가스절연부하개폐기(지중용) 7.2.1 구조 및 외관검사 7.2.2 절연내력시험 7.2.3 주회로 저항측정 7.2.4 연속전류(온도상승)시험 7.2.6 보호등급검증시험 7.2.7 기밀시험 7.2.8 전자기적합성(EMC) 시험 7.2.9 보조 및 제어회로 추가시험 7.2.12 무전압개폐 및 환경시험 7.2.13 온도안정화시험 7.2.15 절연저항측정 7.2.16 직류내전압시험 7.2.17 부분방전시험 7.2.18 압력시험 7.2.20 표면거칠기시험 7.2.21 밀봉제(O-링) 재질시험 7.2.22 PT의 50kV 유도내전압시험 7.2.23 PT의 부분방전시험 7.2.24 가스방출장치 동작시험 7.2.26 제어함 구조 및 외관시험 7.2.27 제어회로 절연 및 기타시험 7.2.28 제어회로 내환경시험 7.2.29 제어기능 확인시험 7.2.30 시스템연결 동작시험 7.2.31 전압계측 정밀도 시험 7.2.32 전류계측 정밀도 시험 7.2.35 가스순도시험 7.2.36 압력저하표시 및 잠금시험 7.2.37 도장시험 7.2.38 제어장치 진동시험 7.2.39 제어장치 충격시험 7.2.40 장기신뢰성 시험 |
전압: 25.8 kV 이하 전류: 600 A 이하 AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ DC: Max. 100 kV 온도상승: 8 000 A 60Hz |
소재지-1 |
| ES-5925-0003:2016 |
25.8 kV 가스절연부하개폐기(가공용) 7.3.1 구조 및 외관검사 7.3.2 절연내력시험 7.3.3 주회로 저항측정 7.3.4 연속전류(온도상승)시험 7.3.6 보호등급검증시험 7.3.7 기밀시험 7.3.8 전자기적합성(EMC) 시험 7.3.9 보조 및 제어회로 추가시험 7.3.12 무전압개폐 및 환경시험 7.3.14 부분방전시험 7.3.15 압력시험 7.3.17 제어함 구조 및 외관검사 7.3.18 제어회로 절연 및 기타시험 7.3.19 충격시험 7.3.20 조작확인시험 7.3.21 취부금구 도금시험 7.3.22 압력저하표시 및 잠금(Lock)시험 7.3.23 가스방출장치 동작시험 7.3.24 자기재 부싱시험 7.3.26 가스순도시험 7.3.27 구출선 및 몰드콘시험 7.3.28 절연저항측정 7.3.30 전류계측 정밀도 시험 7.3.31 전압계측 정밀도 시험 7.3.32 제어회로 내환경시험 7.3.33 시스템연결동작시험 7.3.34 제어기능확인시험 7.3.36 복합열화 시험 7.3.37 절연커버 성능시험 7.3.38 장기신뢰성 시험 7.2.39 제어장치 진동시험 7.2.40 제어장치 충격시험 |
전압: 25.8 kV 이하 전류: 630 A 이하 부착량: Max. 1 533 μm (10 900 g/m²) AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ 온도상승: 8 000 A 60 Hz |
소재지-1 |
| ES-5925-0008:2017 |
25.8 kV 가스절연 다회로차단기(지중용) 7.2.1 구조 및 외관검사 7.2.2 절연내력시험 7.2.3 주회로 저항측정 7.2.4 연속전류(온도상승)시험 7.2.6 보호등급검증시험 7.2.7 기밀시험 7.2.8 전자기적합성(EMC)시험 7.2.9 선로, 케이블 충전전류시험 7.2.14 부분방전시험 7.2.15 서어지 전류시험 7.2.17 무전압 개폐시험 7.2.18 빙설하중시험 7.2.19 서지방지장치 동작시험 7.3.1 구조 및 외관검사 7.3.2 절연시험 7.3.3 주회로 저항측정 7.3.4 연속전류(온도상승)시험 7.3.6 보호등급검증시험 7.3.7 기밀시험 7.3.8 전자기적합성(EMC) 시험 7.3.9 보조 및 제어회로 추가시험 7.3.12 무전압개폐 및 환경시험 7.4.1 온도안정화시험 7.4.3 절연저항측정 7.4.4 직류 내전압 시험 7.4.5 압력시험 7.4.7 부싱시험 7.4.8 밀봉재(O-Ring) 재질시험 7.4.9 가스방출장치 동작시험 7.4.10 제어함 구조 및 외관검사 7.4.11 제어회로 절연 및 기타시험 7.4.12 제어장치 진동시험 7.4.13 제어장치 충격시험 7.4.14 시스템연결 동작시험 7.4.15 전압계측 정밀도 시험 7.4.16 전류계측 정밀도 시험 7.4.17 제어회로 내환경시험 7.4.19 도장시험 7.4.20 가스순도시험 7.4.21 PT의 50kV 유도내전압시험 7.4.22 PT의 부분방전시험 |
전압: 25.8 kV 이하 전류: 600 A 이하 AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ 온도상승: 8 000 A 60 Hz |
소재지-1 |
| ES-5925-0009:2017 |
25.8 kV 배전자동화용 폴리머 Recloser - 구조 및 외관검사 - 절연내력시험 - 주회로저항측정 - 연속전류(온도상승)시험 - 보호등급검증시험 - 전자기적합성시험 - 진공차단부 X-선 측정시험 - 선로, 케이블충전전류시험 - 임계전류시험 - 최소동작전류시험 - 부분방전 시험 - 서지전류시험 - 무전압 개폐시험 - 서지방지장치동작시험 - 절연저항 측정 - 폴리머부싱시험(X선투과 시험 제외) - 제어함 구조 및 외관검사 - 제어회로 절연 및 기타시험 - 제어회로 내환경 시험 - Sequence Test - 부동작 특성 시험 - 제어기능 확인시험 - 시스템 연결 동작시험 - 전류계측 정밀도 시험 - 전압계측 정밀도 시험 - 복합 열화시험 - 취부금구 도금시험 - 제어장치 진동시험 - 제어장치 충격시험 - 특고압 인하용 전선 성능시험 |
전압: 25.8 kV 이하 전류: 630 A 이하 부착량: Max. 1 533 μm (10 900 g/m²) AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| ES-6110-0001:2022 |
25.8 kV 가스절연개폐장치 6.3 구조 및 외관검사 6.4 전기적 절연시험 6.5 주회로저항측정 6.6 온도상승시험 6.9 기계적동작시험(대기온도조건) 6.10 보조회로의 보호등급 확인시험 6.11 외함시험 6.13 외함압력시험 6.14 기밀시험 6.15 보조기기시험 6.16 절연저항시험 6.18 CT, PT시험 6.20 연속개폐시험 6.22 소음시험 6.23 설치후 시험 |
전압: 25.8 kV 이하 전류: 3 000 A 이하 AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| ES-6110-0002:2025 |
72.5kV 이상 가스절연개폐장치 6.3.1 구조 및 외관검사 6.3.2 전기적 절연시험 6.3.3 RIV 시험 6.3.4 온도상승시험 6.3.5 주회로 저항 측정 6.3.6 단시간 전류 시험 6.3.7 투입 및 차단 능력시험 6.3.8 기계적 동작시험(대기온도조건) 6.3.10 접지 개폐기 및 800 kV HSES 투입능력 확인시험 6.3.11 보조회로의 보호등급 확인시험 6.3.16 보조기기시험 6.3.17 절연저항시험 6.3.18 단로기 모선루프전류 개폐성능 확인시험 6.3.19 기밀시험 6.3.23 Local Control Panel 시험 6.3.25 피뢰기 시험 6.3.31 접지개폐기 유도전압 전류 개폐시험 |
6.3.2 Max. 960 kV, Max. 2 600 kV, Max. 1 550 kV 6.3.3 Max. 600 kV, 0.5 MHz ~ 2 MHz 6.3.4 Max. 8 000 A 6.3.5 1 μΩ ~ 1 Ω 6.3.6 Max. 180 kA 6.3.7 Max. 80 kA 6.3.10 Max. 80 kA 6.3.11 IP 4 X 6.3.18 Max. 8 kA 6.3.19 Min. 0.1 mL/m3 6.3.31 Max. 10 kA |
소재지 |
| ES-6110-0002:2025 |
72.5 kV 이상 가스절연개폐장치 6.3.1 구조 및 외관검사 6.3.2 전기적 절연시험 6.3.3 RIV 시험 6.3.4 온도상승시험 6.3.5 주회로 저항 측정 6.3.8 기계적 동작시험(대기온도조건) 6.3.9 기계적 동작시험(내환경 조건) 6.3.11 보조회로의 보호등급 확인시험 6.3.12 외함시험 6.3.13 내후성 시험 6.3.15 외함 압력시험 6.3.16 보조기기시험 6.3.17 절연저항시험 6.3.19 기밀시험 6.3.21 BCT 시험 6.3.22 P.T 시험 6.3.23 Local Control Panel 시험 6.3.26 도금시험 6.3.28 소음시험 6.3.33 GIS용 절연물 시험 |
전압: 72.5 kV 이하 전류: 4 000 A 이하 부착량: Max. 1 533 μm (10 900 g/m²) RIV: Min. 6.5 μV AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| ES-6110-0003:2013 |
단로기 표 10 1. 구조외관 검사 2. 절연내력 시험 1) 뇌임펄스내전압 시험 3) 상용주파전압 시험 5) 보조 및 제어회로시험 3. 주회로 저항측정 4. 온도상승 시험 7. 연속개폐조작시험 10. 도금시험 |
전압: 72.5 kV 이하 전류: 4 000 A 이하 부착량: Max. 1 533 μm (10 900 g/m²) RIV: Min. 6.5 μV AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| GS-5925-0011:2022 |
25.8 kV 에폭시 절연 부하개폐기(지중용) 7.2.1 구조 및 외관검사 7.2.2 주회로 저항측정 7.2.3 전류개폐용량시험 7.2.6 절연내력시험 7.2.7 온도안정화 시험 7.2.8 무전압 개폐시험 7.2.9 절연저항측정 7.2.10 직류 내전압 시험 7.2.11 연속전류(온도상승)시험 7.2.12 부분방전시험 7.2.13 밀봉재(O-ring)의 재질시험 7.2.14 본체 밀봉 시험 7.2.15 상연결 접속재 시험 7.2.16 과전압 수명 시험 7.2.17 제어함 구조 및 외관시험 7.2.18 제어회로 절연 및 전자파적합성 시험 7.2.19 내환경시험 7.2.20 제어기능 확인시험 7.2.21 시스템연결동작시험 7.2.22 전압계측 정밀도 시험 7.2.23 전류계측 정밀도 시험 7.2.26 도장시험 7.2.27 PT의 50kV 유도내전압시험 및 부분방전시험 7.2.29 누유시험 7.2.30 제어장치 진동시험 7.2.31 제어장치 충격시험 7.2.32 제어장치 부가시험 7.2.33 진공개폐부(VI) 방사선 측정시험 |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ DC: Max. 100 kV 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| GS-5925-0012:2021 |
25.8 kV 에폭시 절연 다회로 차단기(지중용) 7.2.2 전류개폐용량시험(개폐부) 7.2.5 온도안정화시험 7.2.6 무전압 개폐시험 7.2.7 절연저항측정 7.2.8 절연내력 시험 7.2.9 직류 내전압 시험 7.2.10 부분방전시험 7.2.11 연속전류(온도상승)시험 7.2.12 주회로 저항측정 7.2.14 밀봉재(O-ring)의 재질시험 7.2.15 본체 밀봉 시험 7.2.16 상연결 접속재 시험 7.2.17 과전압 수명시험 7.2.18 제어함 구조 및 외관검사 7.2.19 최소동작전류 시험 7.2.21 제어회로 절연 및 전자기적합성 시험 7.2.22 시스템연결 동작시험 7.2.23 전압계측 정밀도시험 7.2.24 전류계측 정밀도시험 7.2.25 제어회로 내환경시험 7.2.27 제어장치 진동시험 7.2.28 제어장치 충격시험 7.2.29 도장시험 7.2.30 PT의 50kV 유도내전압시험 및 부분방전시험 |
전압: 25.8 kV 이하 전류: 600 A 이하 AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ DC: Max. 100 kV 온도상승: 8 000 A 60Hz IR: Max. 2 000 MΩ |
소재지-1 |
| GS-5925-0128:2024 |
25.8 kV 친환경 가스 및 고체절연 개폐장치 5.3 구조 및 외관검사 5.4 전기적 절연시험 5.5 주회로 저항측정 5.6 온도상승시험 5.9 기계적 동작시험(대기온도조건) 5.10 보조회로의 보호등급 확인시험 5.11 외함시험 5.13 외함 압력시험 5.14 기밀시험 5.15 보조기기시험(조작 및 제어회로) 5.16 절연저항시험 5.18 CT, PT시험 5.20 연속개폐시험 5.22 소음시험 5.24 장기과전압 시험 5.25 매입금구 체부시험 5.26 도체굽힘시험 5.28 가속열화시험 (Accelerated Sealing Life Test) 5.29 내환경시험 5.30 전기적 충격 시험 (Electric Shock Test) 5.31 고저온 동작특성시험 |
전압: 25.8 kV 이하 전류: 3 150 A 이하 AC: Max. 300 kV 60 Hz LI: Max. 600 kV 30 kJ 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ 챔버 : (-40 ~ 100) ℃ |
소재지-1 |
| GS-5925-0148:2022 |
25.8 kV 퓨즈부착형 부하개폐기 (지중용) 7.2.1 구조 및 외관검사 7.2.2 절연시험 7.2.3 전자파 장애전압(RIV)시험 7.2.4 주회로 저항측정 7.2.5 연속전류(온도상승)시험 7.2.7 보호등급시험 7.2.8 전자기 적합성(EMC)시험 7.2.9 보조 및 제어회로 추가시험 7.2.10 진공개폐부(VI) 방사선 측정시험 7.2.13 무전압개폐 및 환경시험 7.2.15 기계적 동작시험 7.2.16 퓨즈에 대한 기계적 충격시험 7.2.17 온도안정화시험 7.2.18 절연저항측정 7.2.19 직류내전압시험 7.2.20 부분방전시험 7.2.21 제어함 구조 및 외관검사 7.2.22 제어회로 절연 및 기타시험 7.2.23 제어회로 내환경시험 7.2.24 제어기능 확인시험 7.2.25 시스템연결동작시험 7.2.26 전압계측정밀도시험 7.2.27 전류계측정밀도시험 7.2.29 O-링(밀봉재) 재질시험 7.2.30 도장시험 7.2.31 PT 50㎸ 유도내전압시험 및 부분방전시험 7.2.32 제어장치 진동시험 7.2.33 제어장치 충격시험 7.2.34 퓨즈시험 7.2.35 직결용 Solid Link시험 7.2.37 기밀시험 7.2.38 압력시험 7.2.40 표면거칠기시험 7.2.41 가스방출장치 동작시험 7.2.43 가스순도시험 7.2.44 압력저하표시시험 7.2.45 부싱시험 7.2.46 본체 밀봉시험 7.2.47 상연결 접속재시험 7.2.48 과전압 수명시험 7.2.49 부싱 및 접속재시험 7.2.50 절연유 특성 및 시험 7.2.51 누유시험 7.2.52 절연유 절연강도 특성 |
전압: 25.8 kV 이하 전류: 630 A 이하 LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz DC: Max. 100 kV 온도상승: 8 000 A 60Hz IR: Max. 2 000 MΩ |
소재지-1 |
| IEC 60137:2017 |
Insulated bushings for alternating voltagesabove 1 000 V 8.9 Verification of thermal short-time current withstand |
8.9 Max 85 kA |
부속시설-1 |
| IEC 60282-1:2020 |
High-Voltage Fuses - Part 1: Current-Limiting Fuses 7.4 dielectric tests 7.5 temperature-rise tests and power-dissipation measurement 7.7 tests for time-current characteristics |
LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Precipitation rate: (0 ~ 5) mm/min Temperature rise: 8 000 A 60Hz |
소재지-1 |
| IEC 60282-2:2008 |
High-voltage fuses - Part 2: Expulsion fuses 8.1 Conditions for performing the tests 8.2 List of type tests and test reports 8.3 Common test practices for all type tests 8.4 Dielectric tests 8.5 Temperature-rise tests 8.7 Time-current characteristics tests 8.8 Mechanical tests (for distribution fuse-cutouts) |
RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Precipitation rate: (0 ~ 5) mm/min Temperature rise: 8 000 A 60Hz Chamber :(-40 ~ 100) ℃ |
소재지-1 |
| IEC 60947-2:2024 |
Low-voltage switchgear and controlgear – Part 2: Circuit-breakers 9.3.5.2 Test of rated service short-circuit breaking capacity 9.3.6.3 Test of rated ultimate short-circuit breaking capacity 9.3.7.3 Test of rated short-time withstand current 9.3.7.5 Test of short-circuit breaking capacity at the maximum short-time withstand current 9.3.9.3 Test of rated short-time withstand current 9.3.9.4 Test of rated service short-circuit breaking capacity |
Short-time withstand current : Max. 85 kA Short-circuit breaking capacity : Max. 690 V 85 kA |
부속시설-1 |
| IEC 62271-1:2021 |
High-voltage switchgear and controlgear – Part 1: Common specifications for alternating current switchgear and controlgear 7.2 Dielectric tests 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.7 Verification of the protection 7.8 Tightness tests 7.9 Electromagnetic compatibility tests (EMC) 7.10 Additional tests on auxiliary and control circuits 7.11 X-radiation test for vacuum interrupters |
Voltage: Max. 72.5 kV Current: Max. 4 000 A RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Temperature rise: 8 000 A 60Hz Chamber : (-40 ~ 100) ℃ |
소재지-1 |
| IEC 62271-100:2024 |
High-voltage switchgear and controlgear – part 100: Alternating-current circuit-breakers 7.2 Dielectric tests 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current & peak withstand current tests 7.102 Miscellaneous provision for making and breaking tests 7.103 General considerations for making and breaking tests 7.105 Short-circuit test quantities 7.106 Short-circuit test procedure 7.107 Terminal fault tests 7.108 Additional short-circuit tests 7.109 Short-line fault tests 7.110 Out-of-phase making and breaking tests 7.111 Capacitive current tests 7.112 Requirements for making and breaking tests on class E2 circuit-breakers |
7.2 Max. 960 kV, Max. 2 600 kV, Max. 1 550 kV 7.3 Max. 600 kV, 0.5 MHz ~ 2 MHz 7.4 1 μΩ ~ 1 Ω 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.102 Max. 80 kA 7.103 Max. 80 kA 7.105 Max. 80 kA 7.106 Max. 80 kA 7.107 Max. 80 kA 7.108 Max. 80 kA 7.109 Max. 80 kA 7.110 Max. 63 kA 7.111 Max. 3 000 A 7.112 Max. 80 kA |
소재지 |
| IEC 62271-100:2024 |
High-voltage switchgearand controlgear - Part100: Alternating-currentcircuit-breakers 7.6 Short-time withstand current and peak withstand current tests |
7.6 Max 85 kA |
부속시설-1 |
| IEC 62271-100:2021 |
High-voltage switchgearand controlgear - Part100: Alternating-currentcircuit-breakers 7.6 Short-time withstand current and peak withstand current tests |
7.6 Max 85 kA |
부속시설-1 |
| IEC 62271-100:2024 |
High-voltage switchgear and controlgear - Part 100: Alternating-current circuit-breakers 7.2 Dielectric tests 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.7 Verification of the protection 7.8 Tightness tests 7.9 Electromagnetic compatibility tests (EMC) 7.10 Additional tests on auxiliary and control circuits 7.11 X-radiation test procedure for vacuum interrupters 7.101 Mechanical and environmental tests |
AC Voltage: MAX 300 kV - Impulse Voltage: Max 600 kV RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Temperature rise: 8 000 A 60Hz Chamber : (-40 ~ 100) ℃ |
소재지-1 |
| IEC 62271-102:2022 |
High-voltage switchgearand controlgear - Part102: Alternating currentdisconnectors andearthing switches 7.6 Short-time withstand current and peak withstand current tests |
7.6 Max 85 kA |
부속시설-1 |
| IEC 62271-102:2018 |
High-voltage switchgearand controlgear - Part102: Alternating currentdisconnectors andearthing switches 7.6 Short-time withstand current and peak withstand current tests |
7.6 Max 85 kA |
부속시설-1 |
| IEC 62271-102:2022 |
High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors and earthing switches 7.2 Dielectric tests 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.7 Verification of the protection 7.8 Tightness tests 7.9 Electromagnetic compatibility tests (EMC) 7.10 Additional tests on auxiliary and control circuits 7.11 X-ray radiation test for vacuum interrupters 7.102 Operating and mechanical endurance tests 7.103 Operation under severe ice conditions 7.104 Low- and high-temperature tests 7.105 Tests to verify the proper functioning of the position-indicating device |
Voltage: (3.6 ~ 100) kV Current: (10 ~ 8 000) A RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Temperature rise: : 8 000 A 60Hz Chamber : (-40 ~ 100) ℃ |
소재지-1 |
| IEC 62271-102:2022 |
High-voltage switchgear and controlgear - part 102: Alternating current disconnectors and earthing switches 7.2 Dielectric tests 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.101 Tests to prove the short-circuit making performance of earthing switches 7.106 Bus-transfer current switching tests on disconnectors 7.107 Induced current switching tests on earthing switches |
7.2 Max. 960 kV, Max. 2 600 kV, Max. 1 550 kV 7.3 Max. 600 kV, 0.5 MHz ~ 2 MHz 7.4 1 μΩ ~ 1 Ω 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.101 Max. 80 kA 7.106 Max. 8 kA 7.107 Max. 1 600 A |
소재지 |
| IEC 62271-103:2021 |
High-voltage switchgear and controlgear - Part 103: Alternating current switches for rated voltages above 1 kV up to and including 52 kV 7.2 Dielectric tests 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.8 Tightness tests 7.101 Making and breaking tests |
7.2 Max. 230 kV, Max. 670 kV 7.4 1 μΩ ~ 1 Ω 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.8 Min. 0.1 mL/m3 7.101 Max. 80 kA |
소재지 |
| IEC 62271-103:2021 |
High-voltage switchgearand controlgear - Part103: Alternating currentswitches for ratedvoltages above 1 kV upto and including 52 kV 7.6 Short-time withstand current and peak withstand current tests 7.101 Making and breaking tests |
7.6 Max 85 kA 7.101 Max 25.8 kV 1 200 A 60 Hz |
부속시설-1 |
| IEC 62271-103:2021 |
High-voltage switchgear and controlgear - Part 103: Alternating current switches for rated voltages above 1 kV up to and including 52 kV 7.2 Dielectric tests 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.7 Verification of the protection 7.8 Tightness tests 7.9 Electromagnetic compatibility (EMC) tests 7.10 Additional tests on auxiliary and control circuits 7.11 X-radiation test for vacuum interrupters 7.102 Mechanical and environmental tests 7.103 Common checks after tests |
RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Temperature rise: 8 000 A 60Hz Chamber : (-40 ~ 100) ℃ |
소재지-1 |
| IEC 62271-105:2021 |
High-voltage switchgear and controlgear – part 105: Alternating current switch-fuse combinations for rated voltages above 1 kV up to and including 52 kV 7.2 Dielectric tests 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.101 Making and breaking tests 7.105 Extention of validity of type tests |
7.2 Max. 230 kV, Max. 670 kV 7.4 1 μΩ ~ 1 Ω 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.101 Max. 80 kA |
소재지 |
| IEC 62271-105:2021 |
High-voltage switchgear and controlgear – Part 105: Alternating current switch-fuse combinations for rated voltages above 1 kV up to and including 52 kV 7.6 Short-time withstand current and peak withstand current tests |
7.6 Max 85 kA |
부속시설-1 |
| IEC 62271-105:2021 |
High-voltage switchgear and controlgear - Part 105: Alternating current switch-fuse combinations for rated voltages above 1 kV up to and including 52 kV 7.2 Dielectric tests 7.3 Radio interference voltage (r.i.v.) tests 7.4 Resistance measurement 7.5 Continuous current tests 7.7 Verification of the protection 7.8 Tightness tests 7.9 Electromagnetic compatibility tests (EMC) 7.10 Additional tests on auxiliary and control circuits 7.11 X-radiation test for vacuum interrupters 7.102 Mechanical operation tests 7.103 Mechanical shock tests on fuses 7.104 Thermal test with long pre-arcing time of fuse |
RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Precipitation rate: (0 ~ 5) mm/min Temperature rise: 8 000 A 60Hz Chamber : (-40 ~ 100) ℃ |
소재지-1 |
| IEC 62271-106:2021 |
High-voltage switchgear and controlgear - part 106 : Alternating current contactors, contactor-based controllers and motor-starters 7.2 Dielectric tests 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.101 Additional tests required for contactors and contactor based equipment 7.102 Mechanical tests 7.103 Verification of rated making and breaking capacity and reversibility 7.104 Overload current withstand tests 7.105 Short-circuit current making and breaking tests 7.106 Verification of operating limits and characteristics of overload relays 7.107 Verification of coordination with SCPDs 7.108 Electrical endurance tests 7.109 High-voltage motor current switching tests 7.110 Capacitive current switching tests |
7.2 Max. 230 kV, Max. 670 kV 7.4 1 μΩ ~ 1 Ω 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.101 1 μΩ ~ 1 Ω, Max. 230 kV 7.103 Max. 80 kA 7.104 Max. 1 800 A 7.105 Max. 80 kA 7.107 Max. 80 kA 7.108 Max. 80 kA 7.109 Max. 1 600 A 7.110 Max 3 000 A |
소재지 |
| IEC 62271-106:2021 |
High-voltage switchgear and controlgear - Part 106: Alternating current contactors, contactor-based controllers and motor-starters 7.6 Short time withstand current and peak withstand current tests 7.104 Overload current withstand tests |
7.6 Max 85 kA 7.104 Max 25.8 kV 1 200 A 60 Hz |
부속시설-1 |
| IEC 62271-106:2021 |
High-voltage switchgear and controlgear - Part 106: Alternating current contactors, contactor-based controllers and motor-starters 7.2 Dielectric tests 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.7 Verification of the protection 7.8 Tightness tests 7.9 Electromagnetic compatibility tests (EMC) 7.10 Additional tests on auxiliary and control circuits 7.11 X-radiation test for vacuum interrupters 7.101 Additional tests required for contactors and contactor based equipment 7.102 Mechanical tests 7.106 Verification of operating limits and characteristics of overload relays |
RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Precipitation rate: (0 ~ 5) mm/min Temperature rise: 8 000 A 60Hz Chamber : (-40 ~ 100) ℃ |
소재지-1 |
| IEC 62271-107:2019 |
High-voltage switchgear and controlgear - part 107: Alternating current fused circuit-switchers for rated voltages above 1 kV up to and including 52 kV 7.2 Dielectric tests 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.101 Making and breaking tests |
7.2 Max. 230 kV, Max. 670 kV 7.4 1 μΩ ~ 1 Ω 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.101 Max. 80 kA |
소재지 |
| IEC 62271-108:2020 |
High-voltage switchgear and controlgear – Part 108: High-voltage alternating current disconnecting circuit-breakers for rated voltages above 52 kV 7.2 Dielectric tests 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.102 Miscellaneous provision for making and breaking tests 7.103 General considerations for making and breaking tests 7.105 Short-circuit test quantities 7.106 Short-circuit test procedure 7.107 Terminal fault tests 7.108 Additional short-circuit tests 7.109 Short-line fault tests 7.110 Out-of-phase making and breaking tests 7.111 Capacitive tests |
7.2 Max. 960 kV, Max. 2 600 kV, Max. 1 550 kV 7.3 Max. 600 kV, 0.5 MHz ~ 2 MHz 7.4 1 μΩ ~ 1 Ω 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.102 Max. 80 kA 7.103 Max. 80 kA 7.105 Max. 80 kA 7.106 Max. 80 kA 7.107 Max. 80 kA 7.108 Max. 80 kA 7.109 Max. 80 kA 7.110 Max. 63 kA 7.111 Max. 3 000 A |
소재지 |
| IEC 62271-109:2019 |
High-voltage switchgear and controlgear – part 109: Alternating-current series capacitor by-pass switches 7.2 Dielectric tests 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.102 Miscellaneous provisions for by-pass making and insertion tests |
7.2 Max. 960 kV, Max. 2 600 kV, Max. 1 550 kV 7.3 Max. 600 kV, 0.5 MHz ~ 2 MHz 7.4 1 μΩ ~ 1 Ω 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.102 Max. 80 kA 7.103 Max. 80 kA 7.105 Max. 80 kA 7.106 Max. 80 kA 7.107 Max. 80 kA 7.108 Max. 80 kA 7.109 Max. 80 kA 7.110 Max. 63 kA 7.111 Max. 3 000 A |
소재지 |
| IEC 62271-110:2023 |
High-voltage switchgear and controlgear - part 110: Inductive load switching 4.2 Miscellaneous provisions for inductive load switching tests 4.3 High-voltage motor current switching tests 4.4 Shunt reactor current switching tests |
4.2 Max. 63 kA 4.3 Max. 2 000 A 4.4 Max. 2 000 A |
소재지 |
| IEC 62271-111:2019 |
High voltage switchgear and controlgear - Part111: Overhead, pad-mounted, dry vault and submersible automatic circuit reclosers and fault interrupters for AC systems up to 38 kV 7.2 Dielectric tests 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.101 Line-charging current and cable-charging current interruption tests 7.102 Making current capability 7.103 Rated short-circuit breaking current tests 7.104 Low current tests 7.106 Partial discharge(corona) tests 7.109 Mechanical duty test |
7.2 Max. 230 kV, Max. 670 kV 7.4 1 μΩ ~ 1 Ω 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.101 Max. 2 000 A 7.102 Max. 63 kA 7.103 Max. 63 kA 7.104 Max. 63 kA 7.106 Min. 1 pC |
소재지 |
| IEC 62271-111:2019 |
High-voltage switchgearand controlgear - Part111: Automatic circuitreclosers for alternatingcurrent systems up toand including 38 kV 7.6 Short-time withstand current and peak withstand current tests |
7.6 Max 85 kA |
부속시설-1 |
| IEC 62271-111:2019 |
High-voltage switchgear and controlgear - Part 111: Automatic circuit reclosers for alternating current systems up to and including 38 kV 7.2 Dielectric tests 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.7 Verification of the protection 7.8 Tightness tests 7.9 Electromagnetic compatibility tests (EMC) 7.10 Additional tests on auxiliary and control circuits 7.11 X-radiation test procedure for vacuum interrupters 7.106 Partial discharge (corona) tests 7.107 Surge current test; series-trip reclosers 7.108 Time-current tests 7.109 Mechanical duty test 7.111 Control electronic elements surge withstand capability (SWC) tests 7.113 Thermal runaway test |
RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Precipitation rate: (0 ~ 5) mm/min Temperature rise: 8 000 A 60Hz Chamber : (-40 ~ 100) ℃
7.108 : Max. 16 kA |
소재지-1 |
| IEC 62271-200:2024 |
High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV 7.2 Dielectric tests 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.101 Verification of making and breaking capacities 7.105 Internal arc test |
7.2 Max. 230 kV, Max. 670 kV 7.4 1 μΩ ~ 1 Ω 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.101 Max. 80 kA 7.105 Max. 80 kA |
소재지 |
| IEC 62271-200:2024 |
High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV 7.2 Dielectric tests 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.7 Verification of the protection 7.10 Additional tests on auxiliary and control circuits 7.11 X-radiation test for vacuum interrupters 7.101 Verification of making and breaking capacities 7.102 Mechanical operation tests |
LI: Max. 300 kV AC: Max. 100 kV 60 Hz Continuous current: Max. 8 000 A 60Hz Short-time withstand current : Max. 85 kA Making and breaking capacity : Max. 25.8 kV 1 200 A 60 Hz |
부속시설-1 |
| IEC 62271-200:2021 |
High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV 7.2 Dielectric tests 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.7 Verification of the protection 7.10 Additional tests on auxiliary and control circuits 7.11 X-radiation test for vacuum interrupters 7.101 Verification of making and breaking capacities 7.102 Mechanical operation tests |
LI: Max. 300 kV AC: Max. 100 kV 60 Hz Continuous current: Max. 8 000 A 60Hz Short-time withstand current : Max. 85 kA Making and breaking capacity : Max. 25.8 kV 1 200 A 60 Hz |
부속시설-1 |
| IEC 62271-200:2024 |
High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV 7.2 Dielectric tests 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.7 Verification of the protection 7.8 Tightness tests 7.10 Additional tests on auxiliary and control circuits 7.11 X-radiation test for vacuum interrupters 7.102 Mechanical operation tests 7.103 Pressure withstand test for gas-filled compartments |
RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz 온도상승: 8 000 A 60Hz |
소재지-1 |
| IEC 62271-201:2014 |
High-voltage switchgear and controlgear - Part 201: AC solid-insulation enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV 6.2 Dielectric tests 6.4 Measurement of the resistance of circuits 6.5 Temperature-rise tests 6.6 Short-time withstand current and peak withstand current tests 6.101 Verification of making and breaking capacities 6.102 Mechanical operation tests 6.103 Pressure withstand test for gas-filled compartments 6.104 Tests to prove the protection of persons against electric shock 6.105 Internal arcing test 6.106 Thermal stability test |
6.2 Max. 230 kV, Max. 670 kV 6.5 Max. 8 000 A 6.6 Max. 180 kA 6.101 Max. 80 kA 6.105 Max. 80 kA |
소재지 |
| IEC 62271-201:2014 |
High-voltage switchgear and controlgear - Part 201: AC solid-insulation enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV 6.2 Dielectric tests 6.3 Radio interference voltage (r.i.v.) test 6.4 Measurement of the resistance of circuits 6.5 Temperature-rise tests 6.7 Verification of the protection 6.8 Tightness tests 6.9 Electromagnetic compatibility tests (EMC) 6.10 Additional tests on auxiliary and control circuits 6.11 X-radiation test procedures for vacuum interrupters 6.102 Mechanical operation tests 6.103 Pressure withstand test for gas-filled compartments 6.104 Tests to prove the protection of persons against electric shock 6.106 Thermal stability test 6.107 Humidity test |
RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Temperature rise: 8 000 A 60Hz |
소재지-1 |
| IEC 62271-202:2022 |
High-voltage switchgear and controlgear – Part 202: AC prefabricated substations for rated voltages above 1 kV and up to and including 52 kV 7.2 Dielectric tests 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.101 Calculations and mechanical tests 7.102 Internal arc test |
7.2 Max. 230 kV, Max. 670 kV 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.102 Max. 80 kA |
소재지 |
| IEC 62271-202:2022 |
High-voltage switchgear and controlgear – Part 202: AC prefabricated substations for rated voltages above 1 kV and up to and including 52 kV 7.2 Dielectric tests 7.3 Radio interference voltage (r.i.v.) test 7.4 Resistance measurement 7.5 Continuous current tests 7.7 Verification of the protection 7.8 Tightness tests 7.9 Electromagnetic compatibility tests (EMC) 7.10 Additional tests on auxiliary and control circuits 7.11 X-radiation test for vacuum interrupters 7.101 Calculations and mechanical tests |
RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Temperature rise: 8 000 A 60Hz |
소재지-1 |
| IEC 62271-203:2022 |
High-voltage switchgear and controlgear - Part 203 : AC Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV 7.2 Dielectric tests 7.3 Radio interference voltage(RIV) test 7.4 Resistance measurement 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.101 Verification of making and breaking capacities 7.105 Test under conditions of arcing due to an internal fault |
7.2 : Max. 960 kV, Max. 2 600kV, Max. 1 550 kV 7.3 : Max. 600 kV, 0.5 MHz ~ 2 MHz 7.4 : 1 μΩ ~ 1 Ω 7.5 : Max. 8 000 A 7.6 : Max. 180 kA 7.101 : Max. 80 kA 7.105 : Max. 80 kA |
소재지 |
| IEC 62271-204:2022 |
High-voltage switchgear and controlgear – part 204: Rigid gas-insulated transmission lines for rated voltage above 52kV 7.2 Dielectric tests 7.4 Measurement of the resistance of circuits 7.5 Continuous current test 7.6 Short-time withstand current and peak withstand current tests 7.105 Test under conditions of arcing due to an internal fault |
7.2 : Max. 960 kV, Max. 2 600kV, Max. 1 550 kV 7.4 : 1 μΩ ~ 1 Ω 7.5 : Max. 8 000 A 7.6 : Max. 180 kA 7.105 : Max. 80 kA |
소재지 |
| IEC 62271-205:2008 |
High-voltage switchgear and controlgear - Part 205: Compact switchgear assemblies for rated voltages above 52 kV 6.2 Dielectric tests 6.3 Radio interference voltage (r.i.v.) test 6.4 Measurement of the resistance of circuits 6.5 Temperature-rise tests 6.101 Mechanical and environmental tests |
RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Temperature rise: 8 000 A 60Hz Chamber : (-40 ~ 100) ℃ |
소재지-1 |
| IEC 62501:2024 |
Voltage sourced converter(VSC) valves for high-voltage direct current (HVDC) power transmission - Electrical testing 7. Dielectric tests on valve support structure 7.3.3 Valve support AC voltage test 7.3.4 Valve support switching impulse test 7.3.5 Valve support lightning impulse test 8. Dielectric tests on multiple valve unit 8.4.2 MVU support a.c. voltage test 8.4.3 MVU support switching impulse test 8.4.4 Valve support lightning impulse test |
7.3.3 Max. 960 kV 7.3.4 Max. 1 550 kV 7.3.5 Max. 2 600 kV 8.4.2 Max. 960 kV 8.4.3 Max. 1 550 kV 8.4.4 Max. 2 600 kV |
소재지 |
| IEC 62505-1:2016 |
Railway applications – Fixed installations – Particular requirements for AC switchgear – Part 1: Circuit-breakers with nominal voltage above 1 kV 7.2.3 Lightning and switching impulse voltage tests 7.2.2 Power-frequency voltage tests 7.6 Test circuits for short-circuit making and breaking tests 7.7 Short-circuit test quantities 7.8 Basic short circuit tests duties 7.11 Out-of-phase making and breaking tests 7.12 Capacitive current switching test |
7.2.3 Max. 2 600 kV, Max. 1 550 kV 7.2.2 Max. 960 kV 7.8 Max. 63 kA 7.11 Max. 63 kA 7.12 Max. 2 000 A |
소재지 |
| IEC 62505-2:2016 |
Railway applications – Fixed installations – Particular requirements for AC switchgear – Part 2: Disconnectors, earthing switches and switches with nominal voltage above 1 kV 7.1 General 7.2 Test voltages 7.3 Mechanical operation test at ambient air temperature |
- |
소재지 |
| IEEE Std 1247:2005 |
IEEE Standard for Interrupter Switches for Alternating Current, Rated Above 1000 V 8.1 Withstand voltage tests 8.2 Continuous current tests 8.3 Switching tests 8.4 Short-time withstand current tests 8.5 Fault-making current test 8.8 Mechanical operation tests 8.10 Radio-influence tests 8.11 Partial discharge tests |
8.1 : Max. 960 kV, Max. 2 600 kV, Max. 1 550 kV 8.2 : Max. 8 000 A 8.3 : Max. 1 600 A 8.4 : Max. 180 kA 8.5 : Max. 80 kA 8.10 : Max. 600 kV, 0.5 MHz ~ 2 MHz 8.11 : Min. 1 pC |
소재지 |
| IEEE Std 386:2016 |
IEEE Standard for Separable InsulatedConnector Systems for Power DistributionSystems Rated 2.5 kV through 35 kV 7.6 Short-time current test |
7.6 Max 85 kA |
부속시설-1 |
| IEEE Std 404:2012 |
IEEE standard forExtruded and LaminatedDielectric Shielded CableJoints Rated 2.5 kV to500 kV 7.5 Short-time currenttest |
7.5 Max 85 kA |
부속시설-1 |
| IEEE Std C37.09:2018 |
IEEE Standard Test Procedures for AC High-Voltage Circuit Breakers with Rated Maximum Voltage Above 1000 V 4.4 Continuous current-carrying tests 4.5 Dielectric withstand tests 4.6 Standard operating duty (standard duty cycle) tests 4.7 Interrupting time tests 4.8 Short-circuit current making and breaking tests 4.9 Load current switching tests 4.10 Capacitance current switching tests 4.12 Out-of-phase switching current tests 4.13 Mechanical endurance and environmental tests |
4.4 Max. 8 000 A 4.5 Max. 960 kV, Max. 2 600 kV, Max. 1 550 kV 4.6 Max. 80 kA 4.8 Max. 80 kA 4.9 Max. 8 000 A 4.10 Max. 2 000 A 4.12 Max. 16 kA |
소재지 |
| IEEE Std C37.20.2:2015 |
IEEE Standard for Metal-Clad Switchgear 6.2.1 Dielectric tests 6.2.2 Rated continuous current tests 6.2.3 Momentary withstand current tests 6.2.4 Short-time withstand current tests 6.2.5 Auxiliary equipment primary disconnecting device momentary current withstand test 6.2.6 Mechanical endurance tests |
6.2.1 Max. 230 kV, Max. 670 kV 6.2.2 Max. 8 000 A 6.2.3 Max. 180 kA 6.2.4 Max. 180 kA 6.2.5 Max. 180 kA |
소재지 |
| IEEE Std C37.20.3:2023 |
IEEE Standard for Metal-Enclosed Interrupter Switchgear Rated above 1 kV AC up to and Including 48.3 kV AC 6.2.2 Dielectric tests 6.2.3 Rated continuous current (Ir) tests 6.2.5 Short-time withstand current tests 6.2.8.2 Dielectric test for bus-bar insulation |
6.2.2 Max. 230 kV, Max. 670 kV 6.2.3 Max. 8 000 A 6.2.5 Max. 180 kA 6.2.8.2 Max. 300 kV |
소재지 |
| IEEE Std C37.20.4:2013 |
IEEE Standard for Indoor AC Switches (1 kV to 38 kV) for Use in Metal-Enclosed Switchgear 6.2 Dielectric tests 6.5 Temperature-rise tests 6.6 Short-time withstand current and peak withstand current tests 6.12 Mechanical operation test 6.13 Fault-making current test 6.14 Load Switching current test 6.15 Cable-charging current switching test 6.16 Unloaded transformer switching test 6.17 Direct acting fuse tripping current test |
6.2 Max. 230 kV, Max. 670 kV 6.5 Max. 8 000 A 6.6 Max. 180 kA 6.13 Max. 80 kA 6.14 Max. 1 600 A 6.15 Max. 2 000 A 6.16 Max. 1 600 A |
소재지 |
| IEEE Std C37.34:1994 |
IEEE Standard Test Code for High-Voltage Air Switches 4 Dielectric withstand voltage tests 6 Temperature rise test 7 Switch performance tests 8 Test for peak withstand and short-time (symmetrical) withstand current ratings 9 Interrupting tests 11 Mechanical operations test |
4 Max. 960 kV, Max. 2 600 kV, Max.1 550 kV 6 Max. 8 000 A 8 Max. 180 kA 9 Max. 80 kA |
소재지 |
| IEEE Std C37.60:2019 |
IEC/IEEE International Standard - High-voltage switchgear and controlgear - Part 111: Automatic circuit reclosers for alternating current systems up to and including 38 kV 7.2 Dielectric tests 7.5 Continuous current tests 7.6 Short-time withstand current and peak withstand current tests 7.101 Line-charging current and cable-charging current interruption tests 7.102 Making current capability 7.103 Rated short-circuit breaking current tests 7.104 Low current tests 7.106 Partial discharge (corona) tests 7.109 Mechanical duty test |
7.2 Max. 230 kV, Max. 670 kV 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.101 Max. 2 000 A 7.102 Max. 63 kA 7.103 Max. 63 kA 7.104 Max. 63 kA 7.106 Min. 1 pC |
소재지 |
| IEEE Std C37.60:2019 |
High-voltage switchgear and controlgear – Part 111: Automatic circuit reclosers and fault interrupters for alternating current systems up to 38 kV 6.2 Dielectric tests 6.3 Radio intereference voltage (RIV) test 6.4 Measurement of the resistance of circuits 6.5 Temperature-rise tests 6.7 Verification of the protection 6.8 Tightness tests 6.9 Electromagnetic compatibility tests (EMC) 6.10 Additional tests on auxiliary and control circuits 6.11 X-radiation test procedure for vacuum interrupters 6.106 Partial discharge (corona) tests 6.107 Surge current test; series-trip reclosers/FIs 6.108 Time-current tests 6.109 Mechanical duty test 6.110 Ice loading test 6.111 Control electronic elements surge withstand capability (SWC) tests 6.112 Condition of recloser/FI after each test of 6.101, 6.103 and 6.104 |
RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Precipitation rate: (0 ~ 5) mm/min Temperature rise: 8 000 A 60Hz Chamber : (-40 ~ 100) ℃ |
소재지-1 |
| IEEE Std C37.62:2020 |
IEEE Standard for Pad-Mounted Dry Vault, Submersible, and Overhead Fault Interrupters for Alternating Current Systems Up to and Including 38 kV 7.3 Insulation (dielectric) tests 7.5 Measurement of the resistance of circuits 7.6 Continuous current tests 7.7 Short-time withstand current and peak withstand current tests 7.13 Line-charging current and cable-charging current interruption tests 7.14Making current capability 7.15 Rated symmetrical interrupting current tests7.16 Low current tests |
7.3 Max. 230 kV, Max. 670 kV 7.5 Max. 8 000 A 7.7 Max. 180 kA 7.13 Max. 2 000 A 7.14 Max. 63 kA 7.15 Max. 63 kA 7.16 Max. 63 kA |
소재지 |
| IEEE Std C37.63:2024 |
IEEE Standard Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for Alternating Current Systems up to and Including 38 kV 7.3 Insulation(dielectric) tests 7.5 Temperature-rise tests 7.6 Short-time withstand current and peak withstand current tests 7.12 Switching tests 7.13 Fault-making tests 7.14 Condition of the sectionalizer after switching tests and fault-making current tests 7.15 Mechanical operation tests 7.16 Partial discharge tests 7.17 Operating duty tests 7.20 Minimum actuating current tests |
7.3 Max. 230 kV, Max. 670 kV 7.5 Max. 8 000 A 7.6 Max. 180 kA 7.13 Max. 80 kA 7.16 Min. 1 pC |
소재지 |
| IEEE Std C37.63:2024 |
IEEE Standard Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for Alternating Current Systems up to and Including 38 kV 7.6 Short-time withstand current and peak withstand current tests 7.12 Switching tests |
7.6 Max 85 kA 7.12 Max 25.8 kV 1 200 A 60 Hz |
부속시설-1 |
| IEEE Std C37.63:2024 |
IEEE Standard Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for Alternating Current Systems up to and Including 38 kV 7.1 General conditions for tests 7.3 Insulation (dielectric) tests 7.4 Measurement of the resistance of circuits 7.5 Temperature rise test 7.7 Verification of the degrees of protection provided by enclosures 7.8 Tightness tests 7.9 Electromagnetic compatibility tests 7.10 Additional tests on auxiliary and control circuits 7.11 X-radiation test procedure for vacuum interrupters 7.15 Mechanical operation tests 7.16 Partial discharge tests 7.19 Control element tests 7.20 Minimum actuating current tests |
RIV: Min. 6.5 μV LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz DC: Max. 200 kV Precipitation rate: (0 ~ 5) mm/min Temperature rise: 8 000 A 60Hz Chamber : (-40 ~ 100) ℃ |
소재지-1 |
| IEEE Std C37.74:2014 |
IEEE Standard Requirements for Subsurface, Vault, and Pad-Mounted Load-Interrupter Switchgear and Fused Load-Interrupter Switchgear for Alternating Current Systems Up to 38 kV 6.7.2 Dielectric tests 6.7.3 Continuous current test 6.7.6 Thermal runaway test 6.7.7 Partial discharge tests 6.7.8 DC withstand voltage test 6.7.9 Tightness test (sealed tank pressure test) 6.7.10 Mechanical operations test |
LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz Temperature rise: 8 000 A 60Hz DC: Max. 100 kV |
소재지-1 |
| KS C 4315:1998 |
내염형 일단 접지 주상 변압기 부싱(22.9 kV) 6.9 과전류 강도 시험 |
6.9 Max 85 kA |
부속시설-1 |
| SPS-KEMC 1108-0567:2007 |
전동기제어반 9.1 (1) 구조시험 9.1 (2) 기구동작시험 9.1 (3) 개폐동작시험 9.1 (4) 온도상승시험 9.1 (5) 내전압시험 9.1 (6) 단시간내전류시험 9.1 (7) 차단성능시험 9.1 (8) 배선의 확인 및 전기적 동작시험 |
LI: Max. 300 kV AC: Max. 100 kV 60 Hz 온도상승시험전류: Max. 8 000 A 60Hz 단시간내전류 : Max. 85 kA 차단성능시험 : Max. 690 V 85 kA 보호등급 : IP (1X ∼ 4X) |
부속시설-1 |
| SPS-KEMC 1126-0585:2021 |
고장구간 자동개폐기 8.7 단시간 전류 시험 8.13 전류 개폐 용량 시험 8.14 과부하 차단 시험 |
8.7 Max 85 kA 8.13 Max 25.8 kV 1 200 A 60 Hz 8.14 Max 25.8 kV 1 200 A 60 Hz |
부속시설-1 |
| SPS-KEMC 1126-0585:2021 |
고장구간 자동개폐기 8.2 구조 및 치수검사 8.3 절연 내력 시험 8.4 부분방전 시험 8.5 주회로 저항 측정 8.6 온도상승 시험 8.8 IP 보호등급의 검증 8.9 기밀 시험 8.10 전자기 적합성(EMC) 시험 8.11 보조 및 제어회로에 대한 추가시험 8.15 기계적 시험 및 환경 시험 8.16 최소 동작 전류 시험 8.18 과전류 쇄정(Lock) 시험 8.19 트립 프리 기능 시험 8.20 돌입전류 억제 기능 시험 8.21 압력 저하 표시 및 동작 잠금 시험 8.22 가스 방출 장치 동작 시험 8.24 구출선 및 몰드콘 시험 8.25 도장 시험 8.26 도금 시험 |
LI: Max. 600 kV 30 kJ AC: Max. 300 kV 60 Hz 주수율: (0 ~ 5) mm/min 온도상승: 8 000 A 60Hz 챔버 : (-40 ~ 100) ℃ |
소재지-1 |
| SPS-KEMC 2101-0609:2016 |
고압배전반 6.2.절연시험 6.3 회로저항측정 6.4 온도상승시험 6.5 단시간내전류 및 파고내전류시험 6.6 보호등급의 검증 6.11 기계적동작시험 6.13 비금속 칸막이 및 셔터에 대한 시험 |
LI: Max. 300 kV AC: Max. 100 kV 60 Hz 온도상승시험전류: Max. 8 000 A 60 Hz 단시간내전류 : Max. 85 kA IP (1X ∼ 4X) |
부속시설-1 |
| SPS-KEMC 2102-0610:2016 |
저압배전반 8.2.1 구조검사 8.2.2 온도상승한도의 검증 8.2.3 절연특성의 검증 8.2.4 단락강도의 검증 8.2.5 보호회로 효과의 검증 8.2.6 공간거리 및 연면거리의 검증 8.2.7 기계적 동작의 검증 8.2.8 보호등급의 검증 |
LI: Max. 300 kV AC: Max. 100 kV 60 Hz 온도상승시험전류: Max. 8 000 A 60 Hz 단락강도의 검증 : Max. 690 V 85 kA 보호등급 : IP (1X ∼ 4X) |
부속시설-1 |
| SPS-KEMC 2104-0612:2002 |
분전반 8.2.1 구조검사 8.2.2 온도상승한도의 검증 8.2.3 절연특성의 검증 8.2.4 단락강도의 검증 8.2.5 보호회로 효과의 검증 8.2.6 공간거리 및 연면거리의 검증 8.2.7 기계적 동작의 검증 8.2.8 보호등급의 검증 |
전압: Max. 1 kV 전류: Max. 6 300 A LI: Max. 300 kV AC: Max. 100 kV 60 Hz 온도상승시험전류: Max. 8 000 A 60Hz 단락강도의 검증 : Max. 690 V 85 kA 보호등급 : IP (1X ∼ 4X) |
부속시설-1 |
| SPS-KEMC-2101-0609:2016 |
고압배전반 6.2 절연시험 6.3.1 주 회로 6.4 온도상승시험 6.5 단시간내전류 및 파고내전류시험 6.10 투입용량 및 차단용량의 검증 6.11 기계적동작시험 7.5 구조 및 외관검사 |
6.2 Max. 230 kV, Max. 670 kV 6.3.1 1 μΩ ~ 1 Ω 6.4 Max. 8 000 A 6.5 Max. 180 kA 6.10 Max. 63 kA |
소재지 |
| ▶ 전기재료 및 부품 |
| IEC 61951-1:2023 |
Secondary cells and batteries containing alkaline or other non-acid electrolytes - Secondary sealed cells and batteries for portable applications - Part 1: Nickel-Cadmium 7. Electrical test |
Max. DC 60 V, 500 A |
소재지 |
| IEC 61951-2:2022 |
Secondary cells and batteries containing alkaline or other non acid electrolytes - Secondary sealed cells and batteries for portable applications - Part 2: Nickel-metal hydride 7. Electrical test |
Max. DC 60 V, 500 A |
소재지 |
| IEC 62259:2003 |
Secondary cells and batteries containing alkaline or other non-acid electrolytes - Nickel-cadmium prismatic secondary single cells with partial gas recombination 7. Electrical test |
Max. DC 60 V, 500 A |
소재지 |
| IEC 62619:2022 |
Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety requirements for secondary lithium cells and batteries, for use in industrial applications 7.2.1 External short-circuit test(cell or cell block) 7.2.2 Impact test(cell or cell block) 7.2.3 Drop test(cell or cell block, and battery system) 7.2.4 Thermal abuse test(cell or cell block) 7.2.5 Overcharge test(cell or cell block) 7.2.6 Forced discharge test(cell or cell block) 7.3.3 Propagation test(battery system) 8.2.2 Overcharge control of voltage(battery system) 8.2.3 Overcharge control of current(battery system) 8.2.4 Overheating control(battery system) |
Max. DC 1 000 V, 800 A |
소재지 |
| IEC 62619:2022 |
Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety requirements for secondary lithium cells and batteries, for use in industrial applications 7.2.1 External short-circuit test(cell or cell block) 7.2.5 Overcharge test(cell or cell block) 7.2.6 Forced discharge test(cell or cell block) 7.3.3 Propagation test(battery system) 8.2.2 Overcharge control of voltage(battery system) 8.2.3 Overcharge control of current(battery system) 8.2.4 Overheating control(battery system) |
Max. DC 1 500 V, 2 400 A |
부속시설-2 |
| IEC 62620:2023 |
Secondary cells and batteries containing alkaline or other non-acid electrolytes - Secondary lithium cells and batteries for use in industrial applications |
Max. DC 1 000 V, 800 A |
소재지 |
| IEC 62620:2023 |
Secondary cells and batteries containing alkaline or other non-acid electrolytes - Secondary lithium cells and batteries for use in industrial applications |
Max. DC 1 500 V, 2 400 A |
부속시설-2 |
| KR 2025(GC-23-K) |
선박용 배터리시스템 지침 표1 배터리셀 표2 배터리시스템 1 과충전 전압제어 시험 2 과충전 전류제어 시험 3 과열 제어 시험 13 방전성능시험 14 열폭주 확산시험 |
직류 1 500 V, 800 A 이하 |
소재지 |
| KR 2025(GC-23-K) |
선박용 배터리시스템 지침 표1 배터리셀 1 외부 단락시험 3 과충전 시험 4 강제 방전 시험 표2 배터리시스템 1 과충전 전압제어 시험 2 과충전 전류제어 시험 3 과열 제어 시험 13 방전성능시험 14 열폭주 확산시험 |
직류 1 500 V, 800 A 이하 |
부속시설-2 |
| KS C 8504:2015 |
자동차용 납축전지 9.1 5시간율 용량(Ah) 9.2 20시간율 용량(Ah) 9.4 저온시동 성능 9.5 충전수입성시험 9.6 보존특성시험 9.7 수명시험 9.9 건식상온 시동능력시험 |
직류 60 V, 500 A 이하 |
소재지 |
| KS C 8505:2024 |
고정형 납축전지 9.1 용량시험 9.3.2 과충전시험 9.4 용량보존성능시험 9.5 단락 전류 및 내부저항 시험 |
직류 60 V, 500 A 이하 |
소재지 |
| KS C 8510:2024 |
이륜자동차용 납축전지 |
직류 60 V, 500 A 이하 (50 ∼ 500) Hz 68.6 m/s² |
소재지 |
| KS C 8511:2024 |
동차용 납축전지 |
직류 60 V, 500 A 이하 (32 ± 2) Hz (34.3 ± 1.96) m/s² |
소재지 |
| KS C 8518:2023 |
밀폐 고정형 납축전지 8.2.1 용량시험 8.2.2 과충전수명시험 8.2.3 용량보존성능시험 8.2.4 최대방전전류시험 8.2.7 과충전성능시험 |
직류 60 V, 500 A 이하 |
소재지 |
| KS C 8575:2021 |
태양광 시스템용 이차전지 8.1 용량 시험 8.3 용량 보존 시험 8.4 저온방전 시험 8.5 사이클 내구성 시험(극한 조건) |
직류 60 V, 500 A 이하 |
소재지 |
| KS C IEC 62619:2022 |
알칼리 또는 기타 비산성 전해질을 포함하는 이차전지 셀 및 전지 — 산업용 리튬이차전지 셀 및 전지의 안전 요구사항
7.2.1 외부단락 시험(셀 또는 셀 블록) 7.2.2 충돌 시험(셀 또는 셀 블록) 7.2.3 낙하 시험(셀/셀 블록 및 전지 시스템) 7.2.4 고온 시험(셀 또는 셀 블록) 7.2.5 과충전 시험(셀 또는 셀 블록) 7.2.6 강제방전 시험(셀 또는 셀 블록) 7.3.3 열 폭주 전이 시험(전지 시스템) 8.2.2 과충전 전압 제어(전지 시스템) 8.2.3 과충전 전류 제어(전지 시스템) |
직류 1 000 V, 800 A 이하 |
소재지 |
| KS C IEC 62619:2022 |
알칼리 또는 기타 비산성 전해질을 포함하는 이차전지 셀 및 전지 — 산업용 리튬이차전지 셀 및 전지의 안전 요구사항
7.2.1 외부단락 시험(셀 또는 셀 블록) 7.2.5 과충전 시험(셀 또는 셀 블록) 7.2.6 강제방전 시험(셀 또는 셀 블록) 7.3.3 열 폭주 전이 시험(전지 시스템) 8.2.2 과충전 전압 제어(전지 시스템) 8.2.3 과충전 전류 제어(전지 시스템) 8.2.4 과열 제어(전지시스템) |
직류 1 500 V, 2 400 A 이하 |
부속시설-2 |
| KS C IEC 62620:2023 |
알칼리 또는 기타 비산성 전해질을 포함하는 이차전지 셀 및 전지 - 산업용으로 사용되는 리튬이차전지 셀 및 전지 |
직류 1 000 V, 800 A 이하 |
소재지 |
| KS C IEC 62620:2023 |
알칼리 또는 기타 비산성 전해질을 포함하는 이차전지 셀 및 전지 - 산업용으로 사용되는 리튬이차전지 셀 및 전지 |
직류 1 500 V, 2 400 A 이하 |
부속시설-2 |
| KS C IEC 62932-2-1:2020 |
고정형 흐름전지 에너지 시스템 – 제2-1부: 성능 일반 요구사항 및 시험방법 |
직류 1 500 V, 2 400 A 이하 |
부속시설-2 |
| KS C IEC 62932-2-2:2020 |
고정형 흐름전지 에너지 시스템 – 제2-2부: 안전 요구사항 |
직류 1 500 V, 2 400 A 이하 |
부속시설-2 |
| UL 1642:2022 |
Standard for Safety Lithium Batteries (exception) 15.ShockTest 19.LowPressure(AltitudeSimulation)Test 20.ProjectileTest |
Max. DC 60 V, 500 A |
소재지 |
| UL 2054:2022 |
Standard for Safety Household and Commercial Batteries (exception) 20.ShockTest 21.VibrationTest 26.ProjectileTest 29.LabelPermanenceTest |
Max. DC 60 V, 500 A |
소재지 |
| ▶ 산업용 전기기기 |
| DIN Spec. 70121:2014 |
Electromobility – Digital communication between a d.c. EV charging station and an electric vehicle for control of d.c. charging in the Combined Charging System |
- |
소재지-1 |
| DIN Spec. 70122:2018 |
Electromobility – Conformance tests for digital communication between a d.c. EV charging station and an electric vehicle for control of d.c. charging in the Combined Charging System |
- |
소재지-1 |
| ES-5945-0001:2022 |
과전류 계전기 6.5.1 구조검사 6.5.2 절연저항 측정 6.5.3 동작특성시험 6.5.4 과부하 내량시험 6.5.5 접점용량시험 6.5.6 전기적 시험 6.5.7 EMC 시험 6.5.8 제어전원 이상시험 6.5.9 환경시험 6.5.10 개체시험 |
전류입력정격: 32 A 이하 |
소재지-1 |
| ES-5945-0002:2022 |
재폐로부 과전류 계전기 6.5.1 구조검사 6.5.2 절연저항 측정 6.5.3 동작특성시험 6.5.4 과부하 내량시험 6.5.5 접점용량시험 6.5.6 전기적 시험 6.5.7 EMC 시험 6.5.8 제어전원 이상시험 6.5.9 환경시험 6.5.10 개체시험 |
전류입력정격: 32 A 이하 |
소재지-1 |
| ES-5945-0003:2013 |
과전압 계전기 6.4.1 구조검사 6.4.2 절연저항 측정 6.4.3 동작특성시험 6.4.4 과부하 내량시험 6.4.5 접점용량시험 6.4.6 전기적 시험 6.4.7 EMC 시험 6.4.8 제어전원 이상시험 6.4.9 환경시험 6.4.10 개체시험 |
전압입력정격: 300 V 이하 |
소재지-1 |
| ES-5945-0004:2013 |
저전압 계전기 6.4.1 구조검사 6.4.2 절연저항 측정 6.4.3 동작특성시험 6.4.4 과부하 내량시험 6.4.5 접점용량시험 6.4.6 전기적 시험 6.4.7 EMC 시험 6.4.8 제어전원 이상시험 6.4.9 환경시험 6.4.10 개체시험 |
전압입력정격: 300 V 이하 |
소재지-1 |
| ES-5945-0005:2012 |
역상전류 계전기 6.4.1 구조검사 6.4.2 절연저항 측정 6.4.3 동작특성시험 6.4.4 과부하 내량시험 6.4.5 접점용량시험 6.4.6 내구성시험 6.4.7 온도특성시험 6.4.8 상용주파 내전압시험 6.4.9 Impulse 내전압시험 6.4.10 Surge 강도시험 6.4.11 무선주파 방사내력시험 6.4.12 무선주파 전도내성시험 6.4.13 Burst 강도시험 6.4.14 합성 Surge 시험 6.4.15 정전기시험 6.4.16 진동 및 충격시험 6.4.17 제어전원 이상시험 6.4.18 정격부담 측정시험 6.4.19 정정기능시험 |
전류입력정격: 32 A 이하 |
소재지-1 |
| ES-5945-0006:2022 |
방향성 과전류 계전기 6.5.1 구조검사 6.5.2 절연저항 측정 6.5.3 동작특성시험 6.5.4 과부하 내량시험 6.5.5 접점용량시험 6.5.6 전기적 시험 6.5.7 EMC 시험 6.5.8 제어전원 이상시험 6.5.9 환경시험 6.5.10 개체시험 |
전류입력정격: 32 A 이하 |
소재지-1 |
| ES-5945-0007:2008 |
선택지락 계전기 5.1 구조검사 5.2 절연저항측정 5.3 절연내력시험 5.4 방향요소시험 5.5 동작표시기 및 보조접촉기 동작시험 |
전류입력정격: 32 A 이하 |
소재지-1 |
| ES-5945-0008:2022 |
전류비율 차동 계전기 5.1 구조검사 5.2 절연저항측정 5.3 절연내력시험 5.4 최소동작 전류시험 5.5 동작비율특성시험 5.6 고조파 저지특성시험 5.7 동작표시기 동작시험 |
전류입력정격: 32 A 이하 |
소재지-1 |
| ES-5945-0009:2008 |
재폐로 계전기 5.1 구조검사 5.2 절연저항측정 5.3 절연내력시험 5.4 재폐로시간 또는 지연시간 및 복귀시간시험 |
전류입력정격: 32 A 이하 |
소재지-1 |
| ES-5950-0005:2018 |
계기용변압기 7.2.1 구조 및 외관검사 7.2.2 극성시험 7.2.3 단락강도시험 7.2.4 온도상승시험 7.2.5 뇌임펄스 내전압시험 7.2.6 상용주파내전압시험 7.2.7 유도내전압시험 7.2.8 부분방전시험 7.2.15 개폐임펄스 내전압시험 |
7.2.2 Max. 100 V 7.2.3 Max. 120 MVA 7.2.4 Max. 290 A, Max. 6.6 kV 7.2.5 Max. LI 800 kV, Max. 80 kJ 7.2.6 Max. AC 300 kV, Max. 1 A 7.2.7 Max. 15 kVA, Max. 180 Hz, Max. 500 V 7.2.8 Min. 1 pC 7.2.15 Max. 800 kV, Max. 80 kJ |
소재지 |
| ES-5950-0005:2018 |
계기용변압기 7.2.1 구조 및 외관검사 7.2.2 극성시험 7.2.3 단락강도시험 7.2.4 온도상승시험 7.2.5. 뇌임펄스내전압시험 7.2.6 상용주파내전압시험 7.2.7 유도내전압시험 7.2.8. 부분방전시험 7.2.9 잔류전압시험 7.2.10 오차시험 7.2.11 재단파 뇌임펄스내전압시험 7.2.12 유리 전이온도시험(T.G.T) 7.2.13 정전용량 및 유전정접시험 7.2.14 냉열시험 7.2.15 개폐임펄스내전압시험 7.2.16 철공진시험 7.2.17 과도응답특성 7.2.18 주수시험 7.2.19 가스기밀시험 7.2.20 외함시험 7.2.21 외함압력시험 7.2.22 내부고장시 아크상태시험 7.2.23 절연유시험 7.2.24 절연유중 PCB 분석시험 7.2.25 2차 여자특성 knee-point 전압 |
전압: (7.2 ~ 25.8) kV |
소재지-1 |
| ES-5950-0006:2019 |
변류기 6.2.1 구조 및 외관검사 6.2.2 극성시험 6.2.3 온도상승시험 6.2.4 상용주파내전압시험 6.2.5 임펄스내전압시험 6.2.6 허용오차시험 6.2.7 과전류강도시험 6.2.8 2차 개로시험 6.2.9 과전류정수시험 6.2.10 부분방전시험 6.2.11 2차 권선저항측정시험 6.2.12 여자전류특성시험 6.2.13 유도내전압시험 6.2.14 변류기 유도전류 확인시험 |
전압: (0.23 ~ 25.8) kV 전류: (25 ~ 8 000) A |
소재지-1 |
| ES-5950-0006:2019 |
변류기 6.2.7 과전류강도시험 6.2.14 변류기 유도전류 확인시험 |
6.2.7 전류 : 85 kA 이하 6.2.14 전류 : 85 kA 이하 |
부속시설-1 |
| ES-5950-0010:2008 |
변압기 단락강도 시험규격 |
Max. 120 MVA |
소재지 |
| ES-5950-0016:2023 |
22.9 kV 일반형 주상변압기 6.2 단락강도시험 6.4 충격내전압 6.10 유도내전압 시험 |
6.2 Max. 120 MVA 6.4 Max. 800 kV, Max. 80 kJ 6.10 Max. 15 kVA, Max. 180 Hz,Max. 500 V |
소재지 |
| GS-6130-0053:2020 |
전기자동차용 충전스탠드 5.2.1 구조 및 외관시험 5.2.2 절연저항시험 5.2.3 상용주파내전압시험 5.2.4 뇌임펄스내전압시험 5.2.5 접촉전류시험 5.2.6 환경시험 5.2.7 국제보호등급 지수 시험 5.2.8 기계적 충격시험 5.2.9 커넥터 표면 허용온도 시험 5.2.10 전자기 적합성(EMC) 시험 5.2.11 가혹 환경시험 |
정격출력전압 : 단상 AC 220 V 이하 정격입력전류 : 70 A 이하 버스트 전압 : 1 kV 이하 서지 전압 : 2 kV 이하 |
소재지-1 |
| GS-6130-0054:2025 |
전기자동차용 급속충전기 5.2.1 구조 및 외관시험 5.2.2 절연저항시험 5.2.3 효율 및 역률 시험 5.2.4 상용주파내전압시험 5.2.5 뇌임펄스내전압시험 5.2.6 접촉전류시험 5.2.7 환경시험 5.2.8 국제보호등급 지수 시험 5.2.9 기계적 충격시험 5.2.10 소음레벨 측정 5.2.11 맥동전압 측정 5.2.12 커넥터 표면 허용온도 시험 5.2.13 전자기 적합성(EMC) 시험 5.2.14 고조파 시험 5.2.15 가혹 환경시험 |
정격입력전압 : AC 380 V 이하 정격출력전압 : DC 450 V 이하, AC 380 V 이하 정격입력전류 : 85 A 이하 정격출력전류 : 110 A 이하 버스트 전압 : 1 kV 이하 서지 전압 : 2 kV 이하 |
소재지-1 |
| IEC 60076-1:2011 |
Power transformers - Part 1: General 11.2 Measurement of winding resistance 11.3 Measurement of voltage ratio and check of phase displacement 11.4 Measurement of short-circuit impedance and load loss 11.5 Measurement of no-load loss and current 11.6 Measurement of zero-sequence impedance(s) on three-phase transformers 11.7 Tests on on-load tap-changer - Operation test |
11.2 1 mΩ ~ 100 Ω (Max. 25 A) 11.3 0.8 ~ 9 999, 10 V, 100 V 11.4 Max. 90 A, Max. 6.6 kV 11.5 Max. 90 A, Max. 6.6 kV 11.6 Max. 90 A, Max. 6.6 kV 11.7 Max. 2 kA |
소재지 |
| IEC 60076-1:2011 |
Power transformers - Part 1: General 11.2 Measurement of winding resistance 11.4 Measurement of short-circuit impedance and load loss 11.5 Measurement of no-load loss and current |
Resistance : 10 μΩ ~ 1.0 kΩ Voltage : Max 6.6 kV Ampere : Max 200 A |
소재지-1 |
| IEC 60076-1:2011 |
Power Transformers - Part 1: General 11.1.2.1 Routine test for all transformers 11.1.3 Type tests 11.1.4(g)Short-circuit withstand test |
Max. 24 kV 2000 kVA |
부속시설-1 |
| IEC 60076-10:2016 |
Power Transformers - Part 10: Determination of Sound Levels |
Max. (25 ~ 130) dB |
부속시설-1 |
| IEC 60076-11:2018 |
Power transformers - Part 11: Dry-type transformers 14.2.1 Measurement of winding resistance 14.2.2 Measurement of voltage ratio and check of phase displacement 14.2.3 Measurement of short-circuit impedance and load loss 14.2.4 Measurement of no-load loss and current 14.2.5 Applied voltage test (AV) 14.2.6 Induced voltage withstand test (IVW) 14.2.7 Partial discharge measurement 14.3.1 Full wave lightning impulse test (LI) 14.3.2 Temperature-rise test 14.4.3 Short-circuit test |
14.2.1 1 mΩ ~ 100 Ω (Max. 25 A) 14.2.2 0.8 ~ 9 999, 10 V, 100 V 14.2.3 Max. 90 A, Max. 6.6 kV 14.2.4 Max. 90 A, Max. 6.6 kV 14.2.5 Max. 300 kV, Max. 1 A 14.2.6 Max. 15 kVA, Max. 180 Hz, Max. 500 V 14.2.7 Min. 1 pC 14.3.1 Max. 800 kV, Max. 80 kJ 14.3.2 Max. 90 A, Max. 6.6 kV 14.4.3 Max. 120 MVA |
소재지 |
| IEC 60076-11:2018 |
Power transformers - Part 11: Dry-type transformers 14.2.1 Measurement of winding resistance 14.2.3 Measurement of short-circuit impedance and load loss 14.2.4 Measurement of no-load loss and current |
Resistance : 10 μΩ ~ 1.0 kΩ Voltage : Max 6.6 kV Ampere : Max 200 A |
소재지-1 |
| IEC 60076-11:2018 |
Power transformers Part 11: Dry-type transformers (제외항목) 14.4.4 Climatic tests 14.4.5 Environmental test 14.4.6 Fire behaviour test 14.4.7 Seismic test |
Max. 24 kV 2000 kVA |
부속시설-1 |
| IEC 60076-2:2011 |
Power transformers - Part 2: Temperature rise for Liquid-immersed Transformers |
Max. 90 A, Max. 6.6 kV |
소재지 |
| IEC 60076-2:2011 |
Power Transformers Part 2: Temperature rise for liquid-immersed transformers |
Max. 24 kV 2000 kVA |
부속시설-1 |
| IEC 60076-22-1:2019 |
Power transformer – Part 22-1: Power transformer and reactor fittings – Protective devices 7.4 Direct reading dial type liquid level indicators 7.5 Liquid flow indicators |
7.4: 2.5 kPa (24 h) 100 m/s² 2 Hz ~ 7.5: 250 kPa (2 min) 2 Hz ~ |
소재지-1 |
| IEC 60076-3:2018 |
Power transformers - Part 3: Insulation levels, dielectric tests and external clearances in air |
Max. 300 kV, Max. 1 A |
소재지 |
| IEC 60076-3:2018 |
Power Transformers Part 3: Insulation Levels, Dielectric Tests and External Clearances in Air |
Max. AC : 100 kV LI : 400 kV PD : 50 pC |
부속시설-1 |
| IEC 60076-5:2006 |
Power transformers - Part 5: Ability to withstand short circuit |
Max. 120 MVA |
소재지 |
| IEC 60076-5:2006 |
Power Transformers Part 5: Ability to Withstand Short Circuit |
Max. 24 kV 3 MVA |
부속시설-1 |
| IEC 60255-1:2022 |
Measuring relays and protection equipment - Part 1: Common requirements 6.1 Marking 6.2 Dimensions 6.3 Enclosure protection 6.4 Product safety requirements 6.5 Functional performance requirements 6.6 Communication protocols 6.7 Binary input and output 6.8 Transducer analogue input and output 6.9 Input circuit for energizing quantities 6.10 Burden tests 6.11 Contact performance 6.12 Climatic performance 6.13 Mechanical requirements 6.14 Pollution 6.15 Electromagnetic compatibility (EMC) |
Rated input current: Max. 32 A |
소재지-1 |
| IEC 60529:2013 |
Degrees of protection provided by enclosures (IP Code) 12 Tests for protection against access to hazardous parts indicated by the first characteristic numeral 13 Tests for protection against solid foreign objects indicated by the first characteristic numeral 14 Tests for protection against water indicated by the second characteristic numeral 15 Tests for protection against access to hazardous parts indicated by the additional letter |
IP code: IP11 ∼ IP68 |
소재지-1 |
| IEC 61850-10:2012 |
Communication networks and systems for power utility automation - Part 10: Conformance testing 6 Device related conformance testing 7 Tool related conformance testing 8 Performance tests 9 Additional tests |
- |
소재지-1 |
| IEC 61850-3:2013 |
Communication Networks and Systems for power utility automation - Part 3: General Requirements 6 Design and construction 7.6 Test overview |
- |
소재지-1 |
| IEC 61850-6:2024 |
Communication networks and systems for power utility automation - Part 6: Configuration description language for communication in electrical substations related to IEDs |
- |
소재지-1 |
| IEC 61850-7-1:2020 |
Communication networks and systems for power utility automation - Part 7-1: Basic communication structure - Principles and models |
- |
소재지-1 |
| IEC 61850-7-2:2020 |
Communication networks and systems for power utility automation - Part 7-2: Basic information and communication structure - Abstract communication service interface (ACSI) |
- |
소재지-1 |
| IEC 61850-7-3:2020 |
Communication networks and systems for power utility automation - Part 7-3: Basic communication structure - Common data classes |
- |
소재지-1 |
| IEC 61850-7-4:2020 |
Communication networks and systems for power utility automation - Part 7-4: Basic communication structure - Compatible logical node classes and data object classes |
- |
소재지-1 |
| IEC 61850-8-1:2020 |
Communication networks and systems for power utility automation - Part 8-1: Specific communication service mapping (SCSM) - Mappings to MMS (ISO 9506-1 and ISO 9506-2) and to ISO/IEC 8802-3 |
- |
소재지-1 |
| IEC 61850-9-2:2020 |
Communication networks and systems for power utility automation - Part 9-2: Specific communication service mapping (SCSM) - Sampled values over ISO/IEC 8802-3 |
- |
소재지-1 |
| IEC 61851-1:2017 |
Electric vehicle conductive charging system – Part 1: General requirement 8.2 Stored energy 12.2 Characteristics of mechanical switching devices 12.3 Clearances and creepage distances 12.4 IP degrees 12.5 Insulation resistance 12.6 Touch current 12.7 Dielectric withstand voltage 12.8 Temperature rise 12.9 Damp heat functional test 12.10 Minimum temperature functional test 12.11 Mechanical strength 13.2 Overload protection of the cable assembly 13.3 Short-circuit protection of the charging cable 14 Automatic reclosing of protective devices 15 Emergency switching or disconnect 16 Marking and instructions Annex A Control pilot function through a control pilot circuit using a PWM signal and a control pilot wire |
Rated input voltage : Less than or equal to AC 1 000 V Less than or equal to DC 1 500 V Rated output voltage : Less than or equal to AC 1 000 V, Less than or equal to DC 1 500 V |
소재지-1 |
| IEC 61851-23:2014 |
Electric vehicle conductive charging system – Part 23: DC electric vehicle charging station 6.4.1 Mode 4 charging functions 6.4.3 Details of functions for DC charging 6.4.4 Detail of optional function 101.1 General 101.2 Specific requirements for isolated systems 102 Communication between EV and d.c. EV charging station |
Rated output voltage : Less than or equal to DC 1 500 V |
소재지-1 |
| IEC 61869-2:2012 |
Instrument transformers - Part 2: Additional requirements for current transformers 7.2 Type tests 7.3 Routine tests 7.4 Special tests 7.5 Sample tests |
Voltage: (0.72 ~ 36) kV Current: (5 ~ 20 000) A |
소재지-1 |
| IEC 61869-2:2012 |
Instrument transformers - Part 2: Additional requirements for current transformers 7.2.201 short time current test |
7.2.201 Max. 85 kA |
부속시설-1 |
| IEC 61869-3:2011 |
Instrument transformers - Part 3: Additional requirements for Inductive voltage transformers 7.2 Type tests 7.3 Routine tests 7.4 Special tests |
Voltage: (0.72 ~ 36) kV |
소재지-1 |
| IEC 61869-3:2011 |
Instrument transformers - Part 3: Additional requirements for Inductive voltage transformers 7.2.301 Short-circuit withstand capability test |
7.2.301 Max. 85 kA |
부속시설-1 |
| IEC 61869-4:2013 |
Instrument transformers – Part 4: Additional requirements for combined transformers 7.2 Type tests 7.2.2 Temperature-rise test 7.2.3 Impulse voltage withstand test on primary terminals 7.2.6 Test for accuracy 7.3 Routine tests 7.3.1 Power-frequency voltage withstand tests on primary terminals 7.3.5 Test for accuracy |
Voltage: (0.72 ~ 36) kV Current: (5 ~ 20 000) A |
소재지-1 |
| IEEE Std C57.12.90:2021 |
IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers 5 Resistance measurements 6 Polarity and phase-relation tests 7 Ratio tests 8 No-load losses and excitation current 9 Load losses and impedance voltage 10 Dielectric tests 11 Temperature-rise tests 12 Short-circuit tests |
5 : 1 mΩ ~ 100 Ω (Max. 25 A) 6 : 10 V, 100 V 7 : 0.8 ~ 9 999 8 : Max. 90 A, Max. 6.6 kV 9 : Max. 90 A, Max. 6.6 kV 10 : Max. 300 kV, Max. 1 A 11 : Max. 90 A, Max. 6.6 kV 12 : Max. 120 MVA |
소재지 |
| IEEE Std C57.12.91:2020 |
IEEE Standard Test Code for Dry-Type Distribution and Power Transformers 5 Resistance measurements 6 Polarity and phase-relation tests 7 Ratio tests 8 No-load losses and excitation current 9 Load losses and impedance voltage 10 Dielectric tests 11 Temperature test 12 Short-circuit tests |
5 : 1 mΩ ~ 100 Ω (Max. 25 A) 6 : 10 V, 100 V 7 : 0.8 ~ 9 999 8 : Max. 90 A, Max. 6.6 kV 9 : Max. 90 A, Max. 6.6 kV 10 : Max. 300 kV, Max. 1 A 11 : Max. 90 A, Max. 6.6 kV 12 : Max. 120 MVA |
소재지 |
| IEEE Std C57.13:2016 |
IEEE Standard Requirements for Instrument Transformers 5 Accuracy classes for metering 6 Current transformers 7 Voltage transformers 8 Test procedures applicable to instrument transformers 9 Test procedures applicable to current transformers 10 Test procedures applicable to voltage transformers 11 Type test procedures applicable to instrument transformers 12 Type test procedures applicable to current transformers 13 Type test procedures applicable to voltage transformers |
Voltage: (0.12 ~ 36.5) kV Current: (10 ~ 12 000) A |
소재지-1 |
| IEEE Std C57.13:2016 |
IEEE Standard Requirements for Instrument Transformers 6.6 Short-time current ratings 7.7 Short-circuit capability |
6.6 Max 85 kA 7.7 Max 85 kA |
부속시설-1 |
| ISO 15118-2:2014 |
Road vehicles -- Vehicle-to-Grid Communication Interface -- Part 2: Network and application protocol requirements |
- |
소재지-1 |
| ISO 15118-20:2022 |
Road vehicles — Vehicle to grid communication interface — Part 20: 2nd generation network layer and application layer requirements |
- |
소재지-1 |
| ISO 15118-3:2015 |
Road vehicles -- Vehicle to grid communication interface -- Part 3: Physical and data link layer requirements |
- |
소재지-1 |
| ISO 15118-4:2018 |
Road vehicles -- Vehicle to grid communication interface -- Part 4: Network and application protocol conformance test |
- |
소재지-1 |
| ISO 15118-5:2018 |
Road vehicles -- Vehicle to grid communication interface -- Part 5: Physical layer and data link layer conformance test |
- |
소재지-1 |
| ISO 15118-8:2020 |
Road vehicles -- Vehicle to grid communication interface -- Part 8: Physical layer and data link layer requirements for wireless communication |
- |
소재지-1 |
| KEPIC EMB 5100:2020 |
계기용변성기 |
전압: (0.12 ~ 25.5) kV 전류: (10 ~ 12 000) A |
소재지-1 |
| KS C 1706:2022 |
계기용 변성기(표준용 및 일반 계기용) 9.1 비오차 및 위상각 9.2 주파수 특성 9.3 뇌 임펄스 내전압 시험 9.4 옥외용 변성기에 대한 주수 시험 9.5 1차 단자에 대한 상용주파 내전압 시험 9.6 부분 방전 시험 9.7 섹션 간 상용주파 내전압 시험 9.8 2차 단자에 대한 상용주파 내전압 시험 9.9 턴 간 과전압 시험 9.10 온도 상승 시험 9.13 이상 현상 |
전압: (0.23 ~ 34.5) kV 전류: (5 ~ 20 000) A |
소재지-1 |
| KS C 1706:2022 |
계기용 변성기(표준용 및 일반 계기용) 9.11 단시간 전류 시험 |
9.11항 : 전류 85 kA 이하 |
부속시설-1 |
| KS C 1707:2022 |
계기용 변성기(전력 수급용) 9.1 합성 요차 9.2 전류 특성 9.3 전압 특성 9.4 주파수 특성 9.5 상호 간섭 9.6 내전압 9.7 온도 상승 9.9 시험 항목 |
전압: (0.23 ~ 34.5) kV 전류: (5 ~ 5 000) A |
소재지-1 |
| KS C 1707:2022 |
계기용 변성기(전력 수급용) 5.2.5 단시간 전류 7.2.7 단시간 전류 |
5.2.5항 : 전류 85 kA 이하 7.2.7항 : 전류 85 kA 이하 |
부속시설-1 |
| KS C 4306:2019 |
일단 접지 주상 변압기 7.1 구조검사 7.2 권선저항 측정 7.3 극성 및 변압비 시험 7.4 무부하 전류 및 무부하 손실 시험 7.5 부하 손실 및 임피던스 전압시험 7.6 권선 분할교차시험 7.9 온도상승시험 7.10 상용주파 내전압시험 7.11 유도 내전압시험 7.12 뇌 임펄스 내전압시험 7.13 단락강도시험 |
7.2 1 mΩ ~ 100 Ω (Max. 25 A) 7.3 0.8 ~ 9 999, 10 V, 100 V 7.4 Max. 290 A, Max. 6.6 kV 7.5 Max. 290 A, Max. 6.6 kV 7.6 Max. 290 A, Max. 6.6 kV 7.9 Max. 290 A, Max. 6.6 kV 7.10 Max. 300 kV, Max. 1 A 7.11 Max. 15 kVA, Max. 180 Hz, Max. 500 V 7.12 Max. 800 kV, Max. 80 kJ 7.13 Max. 120 MVA |
소재지 |
| KS C 4309:2011 |
변압기 단락 강도 시험방법 |
Max. 120 MVA |
소재지 |
| KS C 4311:2019 |
3 MVA 이하 배전용 건식 변압기 9.1 권선저항 측정 9.2 변압비, 극성 및 각변위시험 9.3 무부하 전류 및 무부하 손실 시험 9.4 부하 손실 및 임피던스 전압시험 9.7 온도상승 시험 9.8 상용주파 내전압시험 9.9 유도 내전압시험 9.10 뇌임펄스 내전압시험 9.12 부분방전시험 9.13 단락강도시험 |
9.1 1 mΩ ~ 100 Ω (Max. 25 A) 9.2 0.8 ~ 9 999, 10 V, 100 V 9.3 Max. 290 A, Max. 6.6 kV 9.4 Max. 290 A, Max. 6.6 kV 9.7 Max. 290 A, Max. 6.6 kV 9.8 Max. 300 kV, Max. 1 A 9.9 Max. 15 kVA, Max. 180 Hz, Max. 500 V 9.10 Max. 800 kV, Max. 80 kJ 9.12 Min. 1 pC 9.13 Max. 120 MVA |
소재지 |
| KS C 4314:1998 |
내염형 일단 접지 주상변압기(22.9 kV) |
Max. 120 MVA |
소재지 |
| KS C 4316:2011 |
특별 고압 주상변압기 9.1 구조검사 9.2 권선저항 측정 9.3 변압비, 극성시험 9.4 무부하 전류 및 무부하 손실 시험 9.5 부하 손실 및 임피던스 전압시험 9.6 권선의 분할교차시험 9.9 온도상승시험 9.10 상용주파 내전압시험 9.11 유도내전압시험 9.12 뇌임펄스 내전압 시험 9.14 단락강도시험 |
9.2 1 mΩ ~ 100 Ω (Max. 25 A) 9.3 0.8 ~ 9 999, 10 V, 100 V 9.4 Max. 290 A, Max. 6.6 kV 9.5 Max. 290 A, Max. 6.6 kV 9.6 Max. 290 A, Max. 6.6 kV 9.9 Max. 290 A, Max. 6.6 kV 9.10 Max. 300 kV, Max. 1 A 9.11 Max. 15 kVA, Max. 180 Hz, Max. 500 V 9.12 Max. 800 kV, Max. 80 kJ 9.14 Max. 120 MVA |
소재지 |
| KS C 4317:2019 |
3 MVA 이하 배전용 유입식 변압기 9.1 권선저항 측정 9.2 변압비, 극성 및 각 변위시험 9.3 무부하 전류 및 무부하 손실 시험 9.4 부하 손실 및 임피던스 전압시험 9.7 온도상승 시험 9.8 상용주파 내전압시험 9.9 유도 내전압시험 9.10 뇌임펄스 내전압시험 9.12 단락강도시험 |
9.1 1 mΩ ~ 100 Ω (Max. 25 A) 9.2 0.8 ~ 9 999, 10 V, 100 V 9.3 Max. 290 A, Max. 6.6 kV 9.4 Max. 290 A, Max. 6.6 kV 9.7 Max. 290 A, Max. 6.6 kV 9.8 Max. 300 kV, Max. 1 A 9.9 Max. 15 kVA, Max. 180 Hz, Max. 500 V 9.10 Max. 800 kV, Max. 80 kJ 9.12 Max. 120 MVA |
소재지 |
| KS C IEC 60529:2013 |
외함의 밀폐 보호등급 구분(IP코드) 12 제1 특성 숫자로 표시되는 위험한 부분으로의 접근에 대한 보호 시험 13 제1 특성 숫자로 표시되는 외부 분진에 대한 보호 시험 14 제2 특성 숫자로 표시되는 방수 시험 15 추가 문자로 표시되는 위험 부분 접근에 대한 보호 시험 |
IP범위: IP11 ~ IP68 |
소재지-1 |
| KS C IEC 61850-10:2012 |
전력 유틸리티 자동화를 위한 통신 네트워크 및 시스템 – 제10부: 적합성 시험 6 장치 관련 적합성 시험 7 툴 관련 적합성 시험 8 성능시험 9 추가 시험 |
- |
소재지-1 |
| KS C IEC 61850-3:2013 |
전력 유틸리티 자동화를 위한 통신 네트워크 및 시스템 – 제3부: 일반 요구사항 7.6 시험항목 |
- |
소재지-1 |
| KS C IEC 61850-6:2018 |
전력 유틸리티 자동화를 위한 통신 네트워크 및 시스템 – 제6부:IED에 관련된 전력 유틸리티 자동화 시스템내 통신을 위한 구성 기술언어
5 SCL로 구현하는 엔지니어링 프로세스 6 SCL 객체 모델 7 SCL 설명 파일 타입 8 SCL 언어 9 SCL 구문 요소 |
- |
소재지-1 |
| KS C IEC 61850-7-1:2011 |
전력 유틸리티 자동화를 위한 통신 네트워크 및 시스템 – 제7-1부: 기본 통신 구조 – 원리 및 모델 |
- |
소재지-1 |
| KS C IEC 61850-7-2:2020 |
전력 유틸리티 자동화를 위한 통신 네트워크 및 시스템 - 제7-2부: 기본 정보와 통신 구조 - 추상 통신서비스 인터페이스(ACSI) |
- |
소재지-1 |
| KS C IEC 61850-7-3:2020 |
전력 유틸리티 자동화를 위한 통신 네트워크 및 시스템 - 제7-3부: 기본 통신 구조 - 공통 데이터 클래스 |
- |
소재지-1 |
| KS C IEC 61850-7-4:2020 |
전력 유틸리티 자동화를 위한 통신 네트워크 및 시스템 - 제7-4부: 기본 통신 구조 - 호환성 논리노드 클래스와 데이터 객체 클래스 |
- |
소재지-1 |
| KS C IEC 61850-8-1:2011 |
전력 유틸리티 자동화를 위한 통신 네트워크및 시스템 — 제8-1부: 특정 통신 서비스 매핑(SCSM) — MMS(ISO 9506-1과 ISO 9506-2) 및 ISO/IEC 8802-3에 매핑 |
- |
소재지-1 |
| KS C IEC 61850-9-2:2020 |
전력 유틸리티 자동화를 위한 통신 네트워크 및 시스템 ― 제9-2부: 특정 통신 서비스 매핑(SCSM) ― ISO/IEC8802-3에 대한 샘플 값 |
- |
소재지-1 |
| KS R IEC 61851-1:2017 |
전기 자동차 전도성 충전 시스템 - 제1부 : 일반 요구사항 8.2 저장 에너지 12.2 기계적 개폐 장치의 특성 12.3 공간거리와 연면거리 12.4 IP 등급 12.5 절연 저항 12.6 접촉 전류 12.7 내전압 12.8 온도 상승 12.9 내습성 기능 시험 12.10 최저 온도 기능 시험 12.11 기계적 강도 13.2 케이블 어셈블리의 과부하 보호 13.3 충전 케이블의 단락 보호 14 보호 장치의 자동 재투입 15 비상 개폐 또는 단로 16 표시와 설명서 부속서 A PWM 신호와 제어 파일럿 선을 사용하는 제어 파일럿 회로의 제어 파일럿 기능 |
정격입력전압 : AC 1 000 V 이하, DC 1 500 V 이하 정격출력전압 : AC 1 000 V 이하, DC 1 500 V 이하 버스트 전압 : 2 kV 이하 서지 전압 : 2 kV 이하 |
소재지-1 |
| KS R IEC 61851-23:2014 |
전기 자동차 전도성 충전 시스템 - 제23부 : 전기자동차 직류 충전 스테이션 6.4.1 모드 4 충전 기능 6.4.3 직류 충전에 대한 기능의 세부사항 6.4.4 선택적 기능의 세부사항 101.1 일반사항 101.2 절연형 시스템을 위한 특정 요구사항 102 전기자동차와 전기자동차 직류 스테이션 사이의 통신 |
정격입력전압 : AC 1 000 V 이하, DC 1 500 V 이하 정격출력전압 : DC 1 500 V 이하 |
소재지-1 |
| KS R ISO 15118-2:2014 |
도로 차량 — V2G 통신 인터페이스 — 제2부: 네트워크 및 응용 프로토콜 요구사항 |
- |
소재지-1 |
| KS R ISO 15118-3:2015 |
도로 차량 ― V2G 통신 인터페이스 ― 제3부: 물리 및 데이터 링크 계층 요구사항 |
- |
소재지-1 |
| KS R ISO 15118-4:2018 |
도로 차량 — V2G 통신 인터페이스 —제4부: 네트워크 및 응용 프로토콜 적합성 시험 |
- |
소재지-1 |
| KS R ISO 15118-5:2018 |
도로 차량 — V2G 통신 인터페이스 —제5부: 물리 계층과 데이터 링크 계층 적합성 시험 |
- |
소재지-1 |
| KS R ISO 15118-8:2020 |
도로 차량 — V2G 통신 인터페이스 — 제8부: 무선 통신용 물리 계층 및 데이터 링크 계층 요구사항 |
- |
소재지-1 |
| SPS-KEMC 1120-0579:2018 |
디지털 보호계전기 6.1 구조 검사 6.2 동작특성 시험 6.3 안전성 시험(절연 시험) 6.4 전자기 적합성(EMC) 시험 6.5 통전 시험 6.6 접점성능 시험 6.7 내환경 시험 6.8 기계적 시험 |
전류입력정격: 32 A 이하 전압입력정격: 300 V 이하 |
소재지-1 |
| ▶ 전자기적합성 |
| CISPR 11:2024 |
Industrial, scientific and medical equipment - Radio - frequency disturbance characteristics - Limits and methods of measurement 7.6.3 Industrial equipment 7.6.4 Scientific, laboratory and measuring equipment 7.6.6 Other equipment in the frequency range 1 GHz to 18 GHz 7.6.8 ISM RF lighting equipment 7.6.9 Medium voltage (MV) and high voltage (HV) switchgear 7.6.10 Grid connected power converters |
CE: 150 kHz ∼ 30 MHz RE: 30 MHz ∼ 1 GHz |
소재지-1 |
| CISPR 32:2019 |
Electromagnetic compatibility of multimedia equipment - Emission requirements 6.2 Host systems and modular EUT 6.3 Measurement procedure |
CE: 150 kHz ∼ 30 MHz RE: 30 MHz ∼ 6 GHz Exception)Annex B, H |
소재지-1 |
| IEC 61000-4-11:2020 |
Electromagnetic compatibility (EMC) - Part 4-11: Testing and measurement techniques – Voltage dips, short interruptions and voltage variations immunity tests for equipment with input current up to 16 A per phase 8.3.2 Voltage dips and short interruptions 8.3.3 Voltage variations |
( 0 ~ 100 ) % single pole 220 V, Max. 16 A |
소재지-1 |
| IEC 61000-4-12:2017 |
Electromagnetic compatibility (EMC) – Part 4-12: Testing and measurement techniques – Ring wave immunity test |
Max. 2.5 kV |
소재지-1 |
| IEC 61000-4-17:2008 |
Electromagnetic compatibility (EMC) – Part 4-17: Testing and measurement techniques – Ripple on d.c. input power port immunity test |
( 2 ~ 15 ) % |
소재지-1 |
| IEC 61000-4-18:2019 |
Electromagnetic compatibility (EMC) – Part 4-18: Testing and measurement techniques – Damped oscillatory wave immunity test |
Max. 4 kV |
소재지-1 |
| IEC 61000-4-2:2025 |
Electromagnetic compatibility (EMC) – Part 4-2: Testing and measurement techniques – Electrostatic discharge immunity test 8.3.1 EUT exercising 8.3.2 Direct application of discharges to the EUT 8.3.3 Indirect application of the discharge |
Contact : Max. 15 kV Air : Max. 15 kV |
소재지-1 |
| IEC 61000-4-29:2000 |
Electromagnetic Compatibility (EMC) - Part 4-29: Testing and Measurement Techniques - Voltage Dips, Short Interruptions and Voltage Variations on d.c. Input Power Port Immunity Tests 8.2.1 Voltage dips and short interruptions 8.2.2 Voltage variation |
( 0 ~ 100 ) % |
소재지-1 |
| IEC 61000-4-3:2020 |
Electromagnetic compatibility (EMC) - Part 4-3: Testing and measurement techniques - Radiated, radio-frequency, electromagnetic field immunity test |
(80 ∼ 3 000) MHz Max. 10 V/m |
소재지-1 |
| IEC 61000-4-30:2021 |
Electromagnetic compatibility(EMC) - Part4-30: Testing and measurement techniques – Power quality measurement methods 5.1 Power Frequency 5.2 Magnitude of the supply voltage 5.3 Flicker 5.4 Supply voltage dips and swells 5.5 Voltage Interruptions 5.7 Supply voltage unbalance 5.8 Voltage harmonics 5.9 Voltage interharmonics 5.10 Mains signalling voltage on the supply voltage 5.11 Rapid voltage change 5.13 Current |
5.1 (50, 60) Hz 5.2 150 % Udin 5.3 (0.2~10) Pst 5.4 120 % Urms 5.5 % Udin 5.7 U2 ratio 5.8 THD, THDS 5.9 THD, THDS 5.10 < 3 kHz 5.11 Urms(1/2) 5.12 - 5.13 3.0 rms/peak |
소재지-1 |
| IEC 61000-4-4:2012 |
Electromagnetic compatibility (EMC) - Part 4-4: Testing and measurement techniques – Electrical fast transient/burst immunity test |
Max. 4 kV |
소재지-1 |
| IEC 61000-4-5:2017 |
Electromagnetic compatibility (EMC) - Part 4-5: Testing and measurement techniques - Surge immunity test |
Max. 4 kV |
소재지-1 |
| IEC 61000-4-6:2023 |
Electromagnetic compatibility (EMC) – Part 4-6: Testing and measurement techniques – Immunity to conducted disturbances, induced by radio-frequency fields |
150 kHz ∼ 80 MHz, Max. 10 V |
소재지-1 |
| IEC 61000-4-8:2009 |
Electromagnetic compatibility (EMC) - Part 4-8: Testing and measurement techniques - Power frequency magnetic field immunity test |
Max. 1 000 A/m(short duration), 100 A/m(continuous field) |
소재지-1 |
| IEC 61851-21-1:2017 |
Electric vehicle conductive charging system - Part 21-1 Electric vehicle on-board charger EMC requirements for conductive connection to AC/DC supply 5.2.4.3 ESA, separated on-board charger test 5.2.5.3 ESA, separated on-board charger test 5.3.4.3 ESA, separated on-board charger test |
5.2.4.3 Max. 4 kV 5.2.5.3 Max. 4 kV 5.3.4.3 150 kHz ~ 30 MHz |
소재지-1 |
| IEC 61851-21-2:2018 |
Electric vehicle conductive charging system - Part 21-2: Electric vehicle requirements for conductive connection to an AC/DC supply - EMC requirements for off board electric vehicle charging systems |
AC charger(20 kW), DC fast charger(400 kW) |
소재지-1 |
| IEEE Std C37.90.1:2024 |
IEEE Standard for Relays, Relay Systems, and Control Devices used for Protection and Control of Electric Power Apparatus--Surge Withstand Capability (SWC) and Electrical Fast Transient (EFT) Requirements and Tests 8.1 Test types 8.2 Common-mode tests 8.3 Transverse-mode tests |
Max. 4 kV |
소재지-1 |
| IEEE Std C37.90.3:2023 |
IEEE Standard for Electrostatic Discharge Tests for Protective Relays 4.1 a) 1) Contact discharge method 4.1 a) 2) Air discharge method 4.1 b) 1) Direct application 4.1 b) 2) Indirect application |
Contact : Max. 15 kV Air : Max. 15 kV |
소재지-1 |
| IEEE Std C62.45:2002 |
IEEE Recommended Practice on Surge Testing for Equipment Connected to Low-Voltage (1000 V and Less) AC Power Circuits 6. Performance of surge testing: Test procedures (exception) 10.2.2 The 10/1000 µs Long Wave |
Max. 4 kV |
소재지-1 |
| KS C 9610-4-11:2020 |
전자파적합성(EMC) - 제4-11부 : 시험 및 측정 기술 - 전압 강하, 순간 정전, 전압 변동 내성 시험 |
(0 ~ 100) % |
소재지-1 |
| KS C 9610-4-2:2017 |
전자파적합성(EMC)-제4-2부:시험 및 측정기술-정전기 방전 내성시험 |
Contact : Max. 15 kV Air : Max. 15 kV |
소재지-1 |
| KS C 9610-4-3:2017 |
전자파적합성(EMC)-제4-3부:시험 및 측정 기술-방사성 RF 전자기장 내성 시험 |
(80 ∼ 6 000) MHz Max. 10 V/m |
소재지-1 |
| KS C 9610-4-4:2020 |
전자파적합성(EMC)-제4-4부:시험 및 측정 기술-전기적 빠른 과도현상/버스트 내성 시험 |
Max. 4 kV |
소재지-1 |
| KS C 9610-4-5:2023 |
전자파 적합성(EMC)-제4-5부:시험 및 측정 기술-서지 내성 시험 |
Max. 6 kV |
소재지-1 |
| KS C 9610-4-6:2020 |
전자파적합성(EMC)-제4-6부:시험 및 측정 기술-전도성 RF 전자기장 전도 내성 시험 |
150 kHz ∼ 80 MHz, Max. 10 V |
소재지-1 |
| KS C 9610-4-8:2017 |
전자파적합성(EMC)-제4-8부:시험 및 측정기술-전원주파수 자기장 내성 시험 |
Max. 1 000 A/m(short duration), Max.100 A/m(continuous field) |
소재지-1 |
| KS C 9811:2019 |
산업, 과학, 의료용(ISM) 기기 — 무선 주파수 방해 특성 — 허용기준 및 측정방법 |
CE: 150 kHz ∼ 30 MHz, RE: 30 MHz ∼ 6 GHz |
소재지-1 |
| KS C 9832:2024 |
멀티미디어 기기 전자파적합성-방출요구사항 제외)부속서B |
CE: 150 kHz ∼ 30 MHz, RE: 30 MHz ∼ 6 GHz |
소재지-1 |
| KS C IEC 61000-4-12:2006 |
전기자기적합성(EMC)-제4-12부:시험 및 측정 기술-링 파형 내성 시험 |
Max. 2.5 kV |
소재지-1 |
| KS C IEC 61000-4-17:2010 |
전기자기적합성(EMC)-제4-17부:시험 및 측정기술-직류 입력 전원 포트에서의 맥동 내성 시험 |
( 2 ~ 15 ) % |
소재지-1 |
| KS C IEC 61000-4-18:2006 |
전기자기적합성(EMC) — 제4-18부: 시험 및 측정 기술 — 감쇠 진동파 내성시험 |
Max. 4 kV |
소재지-1 |
| KS C IEC 61000-4-29:2014 |
전기자기적합성(EMC) — 제4-29부: 시험 및 측정 기술 — 직류 전원단자에서의 전압 강하, 순시 정전 및 전압 변동 내성 시험 |
( 0 ~ 100 ) % |
소재지-1 |
| KS R IEC 61851-21-1:2017 |
전기자동차 전도성 충전시스템 — 제21-1부: 교류/직류 전원에 전도성 접속을 위한 전기자동차 탑재형 충전기 EMC 요구사항 5.2.4.3 ESA, 분리된 탑재형 충전기 시험 5.2.5.3 ESA, 분리된 탑재형 충전기 시험 5.3.4.3 ESA, 분리된 탑재형 충전기 시험 |
5.2.4.3 Max. 4 kV 5.2.5.3 Max. 4 kV 5.3.4.3 150 kHz ~ 30 MHz |
소재지-1 |
| KS R IEC 61851-21-2:2018 |
전기자동차 전도성 충전시스템 — 제21-2부: 교류/직류 전원에 전도성 접속의 전기자동차 요구사항 — 비탑재형 전기자동차 충전시스템에 대한 EMC 요구사항 |
AC charger(20 kW), DC fast charger(400 kW) |
소재지-1 |
| ▶ 전선, 케이블, 전로용품 |
| ES-5970-0013:2022 |
폴리머 현수애자 6.1 복합가속열화시험 6.2.3 인장 내하중시험 6.2.6 인장 파괴하중시험 6.2.8 상용주파 건조섬락 전압시험 6.2.9 상용주파 주수섬락 전압시험 6.2.10 뇌충격 내전압시험(정‧부) 6.2.13 수분침투시험 (Water Penetration Test) 6.2.15 내 아크(Arc)시험 6.2.20 경년변화시험 |
6.1 Max. 33 kV 2 A, (-20 ~ 80) ℃, UV B lamp, Max. 50 kN 6.2.3 Max. 300 kN 6.2.6 Max. 300 kN 6.2.8 Max. 230 kV 6.2.9 Max. 230 kV 6.2.10 Max. 670 kV 6.2.13 Max. 670 kV, Max. 230 kV 6.2.15 Max. 63 kA 6.2.20 (-70 ~ 120)℃, Max. 300 kN |
소재지 |
| ES-5970-0019:2017 |
배전용 폴리머 라인포스트애자 6.2.3 상용주파 건조섬락 전압시험 6.2.4 상용주파 주수섬락 전압시험 6.2.5 뇌충격 내전압시험(정‧부) 6.2.6 굽힘내하중시험 6.2.7 굽힘파괴하중시험 6.2.8 인장파괴하중시험 6.2.10 수분침투시험 6.2.19 복합가속열화시험 |
6.2.3 Max. 230 kV 6.2.4 Max. 230 kV 6.2.5 Max. 670 kV 6.2.6 Max. 300 kN 6.2.7 Max. 300 kN 6.2.8 Max. 300 kN 6.2.10 Max. 670 kV 6.2.19 Max. 33 kV 2 A, (-20 ~ 80) ℃, UV B lamp |
소재지 |
| ES-5920-0005:2023 |
전력용 피뢰기 7.2 누설전류시험 7.3 기준전압측정 7.4 제한전압시험 7.5 장시간 안정성 검증 7.6 반복전하전송정격시험 7.7 열확산거동검증시험 7.8 동작책무시험 7.9 상용주파전압-시간특성 시험 7.12 절연내력시험 7.15 특성요소의 V-I 특성 7.16 부분방전시험 7.18 RIV 시험 7.20 피뢰기 내부구성품 절연내력 시험 |
7.2 Max. 10 mA 7.3 Max. 230 kV 7.4 Max. 20 kA 7.5 1 000 h 7.6 Max. 20 kA 7.7 Max. 200 ℃ 7.8 Max. 100 kA 7.9 Max. 20 kA 7.12 Max. 960 kV Max. 2 600 kV, Max. 1 500 kV 7.15 Max. 100 kA 7.16 Min. 1 pC 7.18 Max. 600 kV, 0.5 MHz ~ 2 MHz 7.20 Max. 100 kA |
소재지 |
| ES-5920-0008:2022 |
345kV/154kV 지중송전 케이블용방식층 및 절연통 보호장치 7.3.3 기준전압(Uref) 의 측정 7.3.4 절연내력시험 7.3.5 제한전압시험 7.3.6 반복전하전송정격시험 7.3.8 동작책무시험 7.3.9 단락회로 시험 7.3.10 내부 부분방전 시험 7.3.13 상용주파전압 - 시간특성 시험 |
7.3.3 Max. 230 kV 7.3.4 Max. 230 kV(AC), Max. 670 kV(LI) 7.3.5 Max. 20 kA 7.3.6 Max. 20 kA 7.3.8 Max. 20 kV, 100 kA 7.3.9 Max. 80 kA 7.3.10 Min. 1 pC 7.3.13 Max. 20 kV, 100 kA |
소재지 |
| ▶ 대전력, 고전압 기기 |
| ES-5925-0009:2017 |
25.8kV 배전자동화용폴리머Recloser 6.3 시험항목 및 방법 - 절연내력시험 (1) 상용주파내전압시험 (2) 충격파내전압시험 - 주회로저항측정 - 연속전류(온도상승)시험 - 단시간 전류시험 - 투입전류시험 - 전류차단시험 - 부분방전 시험 - 복합 열화시험 |
6.3 - 절연내력시험 (1) Max. 230 kV (2) Max. 670 kV - 주회로저항측정: 1 μΩ ~ 1 Ω - 연속전류(온도상승) 시험 : Max. 8 000 A - 단시간 전류시험 : Max. 180 kA - 투입전류시험 : Max. 63 kA - 전류차단시험 : Max. 63 kA - 부분방전시험 : Min. 1 pC - 복합 열화시험 : Max. 33 kV 2 A (-20 ~ 80) ℃ UV B lamp |
소재지 |
| ES-6110-0001:2021 |
25.8kV 가스절연 개폐장치 6.4 전기적 절연시험 6.5 주회로저항측정 6.6 온도상승시험 6.7 단시간전류시험 6.8 투입 및 차단능력시험 |
6.4 Max. 230 kV, Max. 670 kV, Min. 1 pC 6.5 1 μΩ ~ 1 Ω 6.6 Max. 8 000 A 6.7 Max. 180 kA 6.8 Max. 63 kA |
소재지 |
| ES-6110-0007:2016 |
170kV 이상 GIS용 절연물시험방법 4.2.9 (1) AC 상용주파 내전압 시험 4.2.9 (2) 부분방전 시험 4.2.9 (3) 뇌임펄스 내전압 시험 4.2.9 (4) 개폐임펄스 내전압 시험 4.2.9 (5) “0”기압 AC 내전압 시험 4.2.9 (6) 장기 AC 내전압시험 4.2.11 장기 과전압 시험 |
4.2.9 (1) Max. 960 kV 4.2.9 (2) Min. 1 pC 4.2.9 (3) Max. 2 600 kV 4.2.9 (4) Max. 1 500 kV 4.2.9 (5) Max. 960 kV 4.2.9 (6) Max. 960 kV 4.2.11 Max. 960 kV Max. 2 600 kV, Max. 1 500 kV, Min. 1 pC |
소재지 |
| GS-5925-0011:2022 |
25.8kV 에폭시 절연부하개폐기(지중용) 7.2.2 주회로 저항측정 7.2.3 전류개폐용량시험 7.2.4 단시간전류시험 7.2.5 정격 투입전류시험 7.2.6 절연내력시험 7.2.10 직류 내전압 시험 7.2.11 연속전류(온도상승)시험 7.2.12 부분방전시험 |
7.2.2 1 μΩ ~ 1 Ω 7.2.3 Max. 1 600 A 7.2.4 Max. 180 kA 7.2.5 Max. 63 kA 7.2.6 Max. 230 kV, Max. 670 kV 7.2.10 Max. DC 170 kV 7.2.11 Max. 8 000 A 7.2.12 Min. 1 pC |
소재지 |
| GS-5925-0128:2024 |
25.8kV 친환경가스및 고체절연개폐장치 5.4 전기적 절연시험 5.5 주회로 저항측정 5.6 온도상승시험 5.7 단시간전류시험 5.8 투입 및 차단능력시험 5.24 장기과전압시험 |
5.4 Max. 230 kV, Max. 670 kV, Min. 1 pC 5.5 1 μΩ ~ 1 Ω 5.6 Max. 8 000 A 5.7 Max. 180 kA 5.8 Max. 63 kA 5.24 Max. 230 kV, Min. 1 pC |
소재지 |
| GS-5925-0139:2021 |
25.8kV 배전자동화용폴리머절연 방향성Recloser 7.3.2 (1) 상용주파내전압 7.3.2 (2) 충격내전압시험 7.3.3 주회로저항측정 7.3.4 연속전류(온도상승)시험 7.3.5 단시간전류시험 7.3.9 정격 투입전류시험 7.3.10 전류 차단시험 7.3.12 부분방전시험 7.3.29 복합 가속 열화 시험 |
7.3.2 (1) Max. 230 kV 7.3.2 (2) Max. 670 kV 7.3.3 1 μΩ ~ 1 Ω 7.3.4 Max. 8 000 A 7.3.5 Max. 180 kA 7.3.9 Max. 63 kA 7.3.10 Max. 63 kA 7.3.12 Min. 1 pC 7.3.29 Max. 33 kV 2 A, (-20 ~ 80) ℃, UV B lamp |
소재지 |
| GS-5925-0151:2024 |
72.5kV 이상 친환경가스절연개폐장치 6.3.2 전기적 절연시험 6.3.3 RIV 시험 6.3.4 온도상승시험 6.3.5 주회로 저항 측정 6.3.6 단시간 전류 시험 6.3.7 투입 및 차단 능력시험 |
6.3.2 Max. 960 kV Max. 2 600 kV, Max. 1 500 kV, Min. 1 pC 6.3.3 Max. 600 kV, 0.5 MHz ~ 2 MHz 6.3.4 Max. 8 000 A 6.3.5 1 μΩ ~ 1 Ω 6.3.6 Max. 180 kA 6.3.7 Max. 80 kA |
소재지 |
| GS-5925-0158:2022 |
25.8kV 일반형 공기절연 부하개폐기(지중용) 7.2.2 절연내력시험 7.2.3 주회로저항측정 7.2.4 연속전류(온도상승)시험 7.2.5 단시간전류시험 7.2.10 전류개폐용량시험 7.2.11 정격투입전류시험 7.2.16 직류내전압시험 |
7.2.2 Max. 230 kV, Max. 670 kV, Min. 1 pC 7.2.3 1 μΩ ~ 1 Ω 7.2.4 Max. 8 000 A 7.2.5 Max. 180 kA 7.2.10 Max. 1 600 A 7.2.11 Max. 63 kA 7.2.16 Max. DC 170 kV |
소재지 |
| ES-5925-0004:2022 |
25.8kV Eco-부하개폐기(가공용) 7.3.2 전류개폐용량시험 7.3.3 단시간전류시험 7.3.4 정격 투입전류시험 7.3.6 (1) 상용주파내전압시험 7.3.6 (2) 충격내전압시험 7.3.7 연속전류(온도상승)시험 7.3.8 부분방전시험 7.3.10 주회로저항측정 7.3.25 복합열화시험 |
7.3.2 Max. 1 600 A 7.3.3 Max. 180 kA 7.3.4 Max. 63 kA 7.3.6 (1) Max. 230 kV 7.3.6 (2) Max. 670 kV 7.3.7 Max. 8 000 A 7.3.8 Min. 1 pC 7.3.10 1 μΩ ~ 1 Ω 7.3.25 Max. 33 kV 2 A, (-20 ~ 80) ℃, UV B lamp |
소재지 |
| KRSA-3117-R4:2023 |
25.8kV 철도용 개폐장치 6.4.1.2 전기적 절연 시험 6.4.1.3 주회로 저항 측정 시험 6.4.1.4 온도상승 시험 |
6.4.1.2 Max. 230 kV(AC), Max. 670 kV(LI), Min. 1 pC(PD) 6.4.1.3 1 μΩ ~ 1 Ω 6.4.1.4 Max. 8 000 A |
소재지 |
| KRSA-3120-R4:2023 |
전기철도용 친환경 절연 개폐장치(29kV) 6.4.1.2 전기적 절연시험 6.4.1.3 온도상승시험 6.4.1.4 주회로저항 측정 시험 |
6.4.1.2 Max. 230 kV(AC), Max. 670 kV(LI), Min. 1 pC(PD) 6.4.1.3 Max. 8 000 A 6.4.1.4 1 μΩ ~ 1 Ω |
소재지 |
| KRSA-T-2024-3011-R0:2024 |
친환경 가스절연개폐장치(170, 72.5kV) 6.4.1.2 전기적 절연시험 6.4.1.3 RIV 시험 6.4.1.4 온도상승시험 6.4.1.5 주회로 저항 측정 |
6.4.1.2 Max. 960 kV(AC), Max. 2 600 kV(LI), Min. 1 pC(PD) 6.4.1.3 Max. 600 kV, 0.5 MHz ~ 2 MHz 6.4.1.4 Max. 8 000 A 6.4.1.5 1 μΩ ~ 1 Ω |
소재지 |
| GS-5925-0012:2021 |
25.8 kV 에폭시 절연 다회로차단기(지중용) 7.2.2 전류개폐용량시험(개폐부) 7.2.3 단시간 및 정격투입전류시험 7.2.4 부하개폐 및 전류차단시험(차단부) 7.2.8 절연내력시험 7.2.9 직류내전압시험 7.2.10 부분방전시험 7.2.11 연속전류(온도상승)시험 7.2.12 주회로저항측정 |
7.2.2 Max. 1 600 A 7.2.3 Max. 63 kA 7.2.4 Max. 63 kA 7.2.8 Max. 230 kV, Max. 670 kV 7.2.9 Max. DC 170 kV 7.2.10 Min. 1 pC 7.2.11 Max. 8 000 A 7.2.12 1 μΩ ~ 1 Ω |
소재지 |
| ES-5925-0004:2022 |
25.8kV Eco-부하개폐기(가공용)
7.3.5 무전압개폐시험 7.3.6 절연내력시험 7.3.8 부분방전시험 7.3.15 제어회로 절연 및 전자기적합성 시험 7.3.17 절연저항시험 7.3.19 전류계측 정밀도 시험 7.3.20 전압계측 정밀도 시험 7.3.21 내환경시험 7.3.22 시스템연결동작시험 7.3.23 제어기능 확인시험 7.3.25 복합열화시험 7.3.28 취부금구 도금시험 7.3.29 제어장치 진동시험 7.3.30 제어장치 충격시험 |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV DC: Max. 100 kV 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| GS-5925-0158:2022 |
25.8kV 일반형 공기절연 부하개폐기(지중용)
7.2.2 절연내력시험 7.2.3 주회로저항측정 7.2.4 연속전류(온도상승)시험 7.2.8 전자기적합성(EMC)시험 7.2.9 보조 및 제어회로 추가시험 7.2.12 무전압개폐 및 환경시험 7.2.13 진공개폐부(VI) 방사선 측정시험 7.2.15 절연저항측정 7.2.16 직류내전압시험 7.2.25 제어회로 절연강도 및 기타 시험 7.2.26 제어회로 내환경시험 7.2.27 제어기능 확인시험 7.2.28 시스템연결 동작시험 7.2.29 전압계측 정밀도시험 7.2.30 전류계측 정밀도시험 7.2.36 제어장치 진동시험 7.2.37 제어장치 충격시험 7.2.38 장기신뢰성시험 |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV DC: Max. 100 kV 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| GS-5925-0135:2018 |
25.8kV 에폭시절연 고장구간 차단기(가공용)
6.3.6 무전압 개폐시험 6.3.7 절연내력시험 6.3.8 연속전류(온도상승)시험 6.3.9 부분방전시험 6.3.11 주회로저항측정 6.3.13 최소Trip 전류 및 T-C시험 6.3.14 동작기능시험 6.3.15 조작확인시험 6.3.17 제어장치 진동시험 6.3.18 제어장치 충격시험 6.3.19 제어함 내환경시험 6.3.20 제어회로 절연 및 전자기적합성 시험 6.3.26 전류계측 정밀도 시험 6.3.27 전압계측 정밀도 시험 6.3.28 시스템연결 동작시험 6.3.30 취부금구 도금시험 6.3.31 복합 가속 열화 시험 |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV DC: Max. 100 kV 온도상승: 8 000 A 60 Hz TC : 16 kA IR: Max. 2 000 MΩ |
소재지-1 |
| GS-5925-0151:2024 |
72.5kV이상친환경가스절연개폐장치
6.3.2 전기적 절연시험 6.3.4 온도상승시험 6.3.5 주회로 저항 측정 6.3.8 기계적 동작시험(대기온도조건) |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV DC: Max. 100 kV 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| GS-5925-0157:2021 |
25.8kV Dry air 절연 부하개폐기(지중용)
7.2.2 절연내력시험 7.2.3 주회로저항측정 7.2.4 연속전류(온도상승)시험 7.2.6 보호등급검증시험 7.2.7 기밀시험 7.2.8 전자기적합성(EMC)시험 7.2.9 보조 및 제어회로 추가시험 7.2.12 무전압개폐 및 환경시험 7.2.13 진공개폐부(VI) 방사선 측정시험 7.2.15 절연저항측정 7.2.16 직류내전압시험 7.2.25 제어회로 절연강도 및 기타 시험 7.2.26 제어회로 내환경시험 7.2.27 제어기능 확인시험 7.2.28 시스템연결 동작시험 7.2.29 전압계측 정밀도시험 7.2.30 전류계측 정밀도시험 7.2.36 제어장치 진동시험 7.2.37 제어장치 충격시험 7.2.38 장기신뢰성시험 |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV DC: Max. 100 kV 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| GS-5925-0153:2021 |
25.8kV Eco-부하개폐기(입상주용)
7.3.5 무전압개폐시험 7.3.6 절연내력시험 7.3.7연속전류(온도상승)시험 7.3.8 부분방전시험 7.3.10 주회로저항측정 7.3.13 조작확인시험 7.3.15 제어회로 내전압 및 전자기적합성 시험 7.3.17 절연저항시험 7.3.19 전류계측 정밀도 시험 7.3.20 전압계측 정밀도 시험 7.3.21 제어장치 내환경시험 7.3.22 시스템연결동작시험 7.3.23 제어기능 확인시험 7.3.25 복합열화시험 7.3.29 제어장치 진동시험 7.3.30 제어장치 충격시험 |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV DC: Max. 100 kV 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| GS-5925-0139:2021 |
25.8kV 배전자동화용 폴리머절연방향성 Recloser
7.3.2 절연내력시험 7.3.3 주회로저항측정 7.3.4연속전류(온도상승)시험 7.3.6 전자기적합성(EMC) 시험 7.3.7 진공차단부 X-선 측정시험 7.3.11 최소동작전류 시험 7.3.12 부분방전시험 7.3.13 T-C특성시험 7.3.14 무전압 개폐시험 7.3.15 절연저항측정 7.3.20 제어회로 절연 및 기타시험 7.3.21 제어함 내환경시험 7.3.22 Sequence Test 7.3.23 부동작 특성시험 7.3.24 제어기능 확인시험 7.3.25 시스템연결 동작시험 7.3.26 전류계측 정밀도 시험 7.3.27 전압계측 정밀도 시험 7.3.29 복합 가속 열화 시험 7.3.30 취부금구 도금시험 7.3.31 제어장치 진동시험 7.3.32 제어장치 충격시험 |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV DC: Max. 100 kV 온도상승: 8 000 A 60 Hz TC : 16 kA IR: Max. 2 000 MΩ |
소재지-1 |
| GS-5925-0141:2020 |
25.8kV 배전자동화용 에폭시절연 방향성다회로차단기(지중용)
7.2.5 온도안정화시험 7.2.6 무전압 개폐시험 7.2.7 절연저항측정 7.2.8 절연내력 시험 7.2.9 직류 내전압 시험 7.2.10 부분방전시험 7.2.11 온도상승시험 7.2.12 주회로 저항측정 7.2.17 과전압 수명 시험 7.2.19 최소동작전류 시험 7.2.20 T-C 특성시험 7.2.21 제어회로 내전압 시험 7.2.22 시스템연결 동작시험 7.2.23 전압계측 정밀도시험 7.2.24 전류계측 정밀도시험 7.2.25 내환경시험 7.2.27 제어장치 진동시험 7.2.28 제어장치 충격시험 |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV DC: Max. 100 kV 온도상승: 8 000 A 60 Hz TC : 16 kA IR: Max. 2 000 MΩ |
소재지-1 |
| ES-5925-0001:2025 |
교류차단기
6.2.2 전기적 절연시험 6.2.4 주회로저항 측정 6.2.5 온도상승시험 6.2.8 기계적 동작시험(대기온도조건) 6.2.12 주수시험 |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV DC: Max. 100 kV 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| GS-5925-0152:2022 |
25.8kV 지하매입형 에폭시 절연 부하개폐기
7.2.2 절연내력시험 7.2.3 주회로 저항측정 7.2.4 연속전류(온도상승)시험 7.2.7 전자기 적합성(EMC)시험 7.2.8 보조 및 제어회로시험 7.2.9 진공개폐부(VI) 방사선 측정시험 7.2.13 절연저항측정 7.2.14 직류 내전압 시험 7.2.15 부분방전시험 7.2.17 제어회로 절연 및 전자기 적합성시험 7.2.18 제어회로 내환경시험 7.2.19 제어기능 확인시험 7.2.20 시스템연결동작시험 7.2.21 전압계측 정밀도 시험 7.2.22 전류계측 정밀도 시험 7.2.27 제어장치 진동시험 7.2.28 제어장치 충격시험 7.2.30 과전압 수명 시험 |
AC: Max. 300 kV 60 Hz LI: Max. 600 kV DC: Max. 100 kV 온도상승: 8 000 A 60 Hz IR: Max. 2 000 MΩ |
소재지-1 |
| ▶ 산업용 전기기기 |
| GS-5945-0023:2022 |
변압기 전류비율차동보호 IED 5.2 (2) 절연저항시험 (3) 전기적 시험 (가) 상용주파내전압 시험 (나) 뇌임펄스내전압 시험 (5) 과부하 내량 시험 (6) 접점용량시험 (7) EMC 시험 (8) 환경시험 (가) 진동 및 충격시험 (나) 온도성능시험 (다) 온·습도 성능시험 (9) IEC 61850 통신서비스 시험 |
5.2 (2) DC 500 V (3) 전기적 시험 (가) (0.5 ~ 2.0) kV (나) (1.0 ∼ 5.0) kV (5) 1 kA 이하, 300 V 이하 (8) 환경시험 (나) (-40 ∼ 70) ℃ (다) (25, 40) ℃ / (90 ∼ 96) % |
소재지-1 |
| GS-5945-0025:2024 |
재폐로부 방향성 과전류보호 IED 5.2 (2) 절연저항시험 (3) 전기적 시험 (가) 상용주파내전압 시험 (나) 뇌임펄스내전압 시험 (5) 과부하 내량 시험 (6) 접점용량시험 (7) EMC 시험 (8) 환경시험 (가) 진동 및 충격시험 (나) 온도성능시험 (다) 온·습도 성능시험 (9) IEC 61850 통신서비스 시험 |
5.2 (2) DC 500 V (3) 전기적 시험 (가) (0.5 ~ 2.0) kV (나) (1.0 ∼ 5.0) kV (5) 1 kA 이하, 300 V 이하 (8) 환경시험 (나) (-40 ∼ 70) ℃ (다) (25, 40) ℃ / (90 ∼ 96) % |
소재지-1 |
| GS-5945-0028:2022 |
170kV용 과전류보호 IED 5.2 (2) 절연저항시험 (3) 전기적 시험 (가) 상용주파내전압 시험 (나) 뇌임펄스내전압 시험 (5) 과부하 내량 시험 (6) 접점용량시험 (7) EMC 시험 (8) 환경시험 (가) 진동 및 충격시험 (나) 온도성능시험 (다) 온·습도 성능시험 (9) IEC 61850 통신서비스 시험 |
5.2 (2) DC 500 V (3) 전기적 시험 (가) (0.5 ~ 2.0) kV (나) (1.0 ∼ 5.0) kV (5) 1 kA 이하, 300 V 이하 (8) 환경시험 (나) (-40 ∼ 70) ℃ (다) (25, 40) ℃ / (90 ∼ 96) % |
소재지-1 |
| GS-5945-0031:2024 |
재폐로부 방향성 과전류계전기 6.5 6.5.1 구조 및 치수검사 6.5.2 절연저항시험 6.5.3 동작특성시험 6.5.4 과부하 내량 시험 6.5.5 접점용량시험 6.5.6 전기적 시험 (1) 상용주파내전압 시험 (2) 뇌임펄스내전압 시험 6.5.7 EMC 시험 6.5.8 제어전원 이상 시험 6.5.9 환경시험 (1) 진동 및 충격시험 (2) 온도성능시험 (3) 온·습도 성능시험 6.5.10 개체시험 |
6.5 6.5.1 육안 검사 6.5.3 DC 500 V 6.5.4 1 kA 이하, 300 V 이하 6.5.6 전기적 시험 (1) (0.5 ~ 2.0) kV (2) (1.0 ∼ 5.0) kV 6.5.8 300 V 이하 6.5.9 환경시험 (2) (-40 ∼ 70) ℃ (3) (25, 40) ℃ / (90 ∼ 96) % 6.5.10 육안검사 |
소재지-1 |
| GS-6110-0030:2022 |
345kV 변압기보호배전반 6.2.2 (2) 절연저항시험 (3) 과부하 내량 시험 (4) 접점용량시험 (5) 전기적시험 (가) 상용주파내전압 시험 (나) 뇌임펄스내전압 시험 (6) EMC 시험 (7) 환경시험 (가) 진동 및 충격시험 (나) 온도성능시험 (다) 온·습도 성능시험 |
6.2.2 (2) DC 500 V (3) 1 kA 이하, 300 V 이하 (5) 전기적 시험 (가) (0.5 ~ 2.0) kV (나) (1.0 ∼ 5.0) kV (7) 환경시험 (나) (-40 ∼ 70) ℃ (다) (25, 40) ℃ / (90 ∼ 96) % |
소재지-1 |
| GS-6110-0039:2022 |
154kV 송전선로 보호배전반 6.2.2 (2) 절연저항시험 (3) 과부하 내량 시험 (4) 접점용량시험 (5) 전기적시험 (가) 상용주파내전압 시험 (나) 뇌임펄스내전압 시험 (6) EMC 시험 (7) 제어전원 이상 시험 (8) 환경시험 (가) 진동 및 충격시험 (나) 온도성능시험 (다) 온·습도 성능시험 |
6.2.2 (2) DC 500 V (3) 1 kA 이하, 300 V 이하 (5) 전기적 시험 (가) (0.5 ~ 2.0) kV (나) (1.0 ∼ 5.0) kV (7) 300 V 이하 (8) 환경시험 (나) (-40 ∼ 70) ℃ (다) (25, 40) ℃ / (90 ∼ 96) % |
소재지-1 |
| GS-6110-0059:2022 |
345kV 송전선로 보호배전반 6.2.2 (2) 절연저항시험 (3) 과부하 내량 시험 (4) 접점용량시험 (5) 전기적시험 (가) 상용주파내전압 시험 (나) 뇌임펄스내전압 시험 (6) EMC 시험 (7) 환경시험 (가) 진동 및 충격시험 (나) 온도성능시험 (다) 온·습도 성능시험 |
6.2.2 (2) DC 500 V (3) 1 kA 이하, 300 V 이하 (5) 전기적 시험 (가) (0.5 ~ 2.0) kV (나) (1.0 ∼ 5.0) kV (7) 환경시험 (나) (-40 ∼ 70) ℃ (다) (25, 40) ℃ / (90 ∼ 96) % |
소재지-1 |
| GS-6110-0097:2022 |
154 kV 디지털 변전소 혼용 운영시스템 5.4 1) 구조 및 치수검사 2) 절연저항측정 3) 상용주파내전압시험 4) 뇌임펄스내전압시험 5) EMC시험 a) 정전기 방전 내성시험 b) 방사 무선주파수 전기자기장 내성시험 c) 전기적 빠른 과도현상 내성시험 d) 서지 내성시험 e) 전자기장 전도 내성 f) 전원주파수 자계 내성시험 g) 전압강하, 순시정전 및 전압변동 내성시험 h) 상용주파수 전도성 공통모드 방해 내성시험 i) 감쇄 진동서지 내성시험 j) 전기자기 장해 측정시험 6) 진동 및 충격성능시험 7) 온도 및 습도성능시험 8) 부담측정 9) 과부하내량시험 10) 접점용량시험 11) 시스템기능 및 성능시험 12) IEC61850통신서비스시험(client) 13) IEC61850통신기능 및 성능확인시험 14) 온습도사이클시험 15) IEC61850통신서비스시험(server) |
5.4 1) 구조 육안검사 및 치수 측정 2) DC 500 V 인가, ≥ 100 MΩ 3) 2 kV, 500 V 인가 4) 5 kV 인가 5) a) 6 kV(접촉), 8 kV(기중) b) 10 V/m 스윕: 80 MHz ∼ 1 GHz 스팟: (80, 160, 380, 450, 900) MHz c) 4 kV 이하 반복주파수: 5 kHz d) 4 kV 이하, 1.2 x 50 μs e) 10 V 스윕: 150 kHz ∼ 80 MHz 스팟: (27, 68) MHz f) (100, 1 000) A/m g) (0 ∼ 1.1)Vn, (0.05 ∼ 10) s, (1 ~ 5) cyc 리플(0.1 Vn, 60 Hz) 60 s h) (3, 30) V i) (1, 1.5) kV, 100 kHz, 1 MHz j) 잡음단자전압: (0.15 ∼ 30) MHz 잡음전계강도: (30 ∼ 1 000) MHz 7) 온도 및 습도성능시험 a) 저온시험: (-40 ∼ 15) ℃ b) 고온시험: (30 ∼ 70) ℃ c) 고온고습시험: 40 ℃ 9) 전압회로: 1.15 Vn 전류회로: 60 A (0.2 s) 14) 시험범위 : 25, 55 ℃ / (90 ∼ 96) % |
소재지-1 |
| GS-6110-0098:2018 |
345 kV 디지털 변전소 혼용 운영시스템 5.4 1) 구조 및 치수검사 2) 절연저항측정 3) 상용주파내전압시험 4) 뇌임펄스내전압시험 5) EMC시험 a) 정전기 방전 내성시험 b) 방사 무선주파수 전기자기장 내성시험 c) 전기적 빠른 과도현상 내성시험 d) 서지 내성시험 e) 전자기장 전도 내성 f) 전원주파수 자계 내성시험 g) 전압강하, 순시정전 및 전압변동 내성시험 h) 상용주파수 전도성 공통모드 방해 내성시험 i) 감쇄 진동서지 내성시험 j) 전기자기 장해 측정시험 6) 진동 및 충격성능시험 7) 온도 및 습도성능시험 8) 부담측정 9) 시스템기동 및 저장장치 동작시험 10) IEC61850통신서비스시험(client) 11) IEC61850통신기능 및 성능확인시험 12) 온습도사이클시험 13) IEC61850통신서비스시험(server) |
5.4 1) 구조 육안검사 및 치수 측정 2) DC 500 V 인가, ≥ 100 MΩ 3) 2 kV, 500 V 인가 4) 5 kV 인가 5) a) 6 kV(접촉), 8 kV(기중) b) 10 V/m 스윕: 80 MHz ∼ 1 GHz 스팟: (80, 160, 380, 450, 900) MHz c) 4 kV 이하 반복주파수: 5 kHz d) 4 kV 이하, 1.2 x 50 μs e) 10 V 스웹: 150 kHz ∼ 80 MHz 스팟: (27, 68) MHz f) (100, 1 000) A/m g) (0 ∼ 1.1)Vn, (0.05 ∼ 10) s, (1 ~ 5) cyc 리플(0.1 Vn, 60 Hz) 60 s h) (3, 30) V i) (1, 1.5) kV, 100 kHz, 1 MHz j) 잡음단자전압: (0.15 ∼ 30) MHz 잡음전계강도: (30 ∼ 1 000) MHz 7) 온도 및 습도성능시험 a) 저온시험: (-40 ∼ 15) ℃ b) 고온시험: (30 ∼ 70) ℃ c) 고온고습시험: 40 ℃ 8) 직류/교류전원 9) 전압회로: 1.15 Vn 전류회로: 60 A (0.2 s) 11) 시험범위 : 25, 55 ℃ / (90 ∼ 96) % |
소재지-1 |
| GS-6110-0239:2022 |
154kV 모선 보호배전반 6.2.2 (2) 절연저항시험 (3) 과부하 내량 시험 (4) 접점용량시험 (5) 전기적시험 (가) 상용주파내전압 시험 (나) 뇌임펄스내전압 시험 (6) EMC 시험 (7) 제어전원 이상 시험 (8) 환경시험 (가) 진동 및 충격시험 (나) 온도성능시험 (다) 온·습도 성능시험 |
6.2.2 (2) DC 500 V (3) 1 kA 이하, 300 V 이하 (5) 전기적 시험 (가) (0.5 ~ 2.0) kV (나) (1.0 ∼ 5.0) kV (7) 300 V 이하 (8) 환경시험 (나) (-40 ∼ 70) ℃ (다) (25, 40) ℃ / (90 ∼ 96) % |
소재지-1 |
| GS-6110-0265:2022 |
154kV 변압기 보호IED반 6.2.2 (2) 절연저항시험 (3) 과부하 내량 시험 (4) 접점용량시험 (5) 전기적시험 (가) 상용주파내전압 시험 (나) 뇌임펄스내전압 시험 (6) EMC 시험 (7) 제어전원 이상 시험 (8) 환경시험 (가) 진동 및 충격시험 (나) 온도성능시험 (다) 온·습도 성능시험 |
6.2.2 (2) DC 500 V (3) 1 kA 이하, 300 V 이하 (5) 전기적 시험 (가) (0.5 ~ 2.0) kV (나) (1.0 ∼ 5.0) kV (7) 300 V 이하 (8) 환경시험 (나) (-40 ∼ 70) ℃ (다) (25, 40) ℃ / (90 ∼ 96) % |
소재지-1 |
| GS-5895-0019:2024 |
배전 자동화용 다기능 단말장치 7.2 1) 구조 및 외관검사 2) 내진동시험 3) 내환경시험 (1) 상용주파내전압시험 (2) 충격파 내전압 (3) SWC시험 (4) 절연저항시험 (5) 전자파 방사내력시험 (6) 내한성 및 내열성시험 4) 기능시험 |
7.2 1) 육안검사 3) 내환경시험 (1) 2 kV (2) 6 kV / 3 kA, 4 kV / 2 kA (3) Level 3, 1 MHz, Level 4, 5 kHz (4) ≥ 500 MΩ (5) 20 V/m, 1 GHz 이하 (6) (-25 ~ 70) ℃ 4) (1) 0.4 A, ≤ ±1 % (2) 4 V, ≤ ±1 % |
소재지-1 |
| GS-5895-0021:2024 |
배전 자동화용 제어 단말장치 7.2 1) 구조 및 외관검사 2) 내진동시험 3) 충격시험 4) 상용주파내전압시험 5) 충격내전압시험 6) SWC시험 7) 절연저항시험 8) 전자파 방사내력시험 9) 내환경시험 10) 전류계측정밀도시험 11) 전압계측정밀도시험 12) 시스템연결동작시험 |
7.2 1) 육안검사 4) 2 kV, 1 min 5) 6 kV / 3 kA, 4 kV / 2 kA 6) Level 3, 1 MHz, Level 4, 5 kHz 7) ≥ 500 MΩ 8) 20 V/m, 1 GHz 이하 9) (-25 ~ 70) ℃ 10) 0.4 A, ≤ ±3 % 11) 4 V, ≤ ±3 % |
소재지-1 |
| GS-5895-0038:2024 |
배전자동화용 Door 부착형 단말장치 7.2 1) 구조 및 외관검사 2) 내진동시험 3) 내환경시험 (1) 상용주파내전압시험 (2) 충격파 내전압 (3) SWC시험 (4) 절연저항시험 (5) 전자파 방사내력시험 (6) 내한성 및 내열성시험 4) 기능시험 |
7.2 1) 육안검사 3) 내환경시험 (1) 2 kV, 1 min (2) 6 kV / 3 kA, 4 kV / 2 kA (3) Level 3, 1 MHz, Level 4, 5 kHz (4) ≥ 500 MΩ (5) 20 V/m, 1 GHz 이하 (6) (-30 ~ 70) ℃ 4) (1) 0.4 A, ≤ ±1 % (2) 4 V, ≤ ±1 % |
소재지-1 |
| SPS-R KSGA-034-33-7651:2025 |
전기자동차 전도성 충전시스템 – 연결인식 자동충전을 위한 인증서 운용 기능 시험방법 5.2 시험케이스 5.2.1 인증서 설치 5.2.2 인증서 갱신 5.2.3 인증서 확인 |
- |
소재지-1 |
| KSGA-034-35:2025 |
전기자동차 전도성 충전시스템의 교류 양방향 전력전송을 위한 계통지원기능 요구사항 및 시험방법 7 기능 시험방법 7.2 AC-BPT EV의 기능 시험방법 7.3 AC-BPT EVSE의 기능 시험방법 |
정격입력전압 : AC 500 V 이하 정격출력전압 : AC 500 V 이하 DC 1 000 V 이하 |
소재지-1 |
| KSGA-034-5:2023 |
전기자동차 전도성 충전시스템 - 고장 식별번호 및 시험방법 7. 고장 정의 및 시험 방법 7.1 입력부 7.2 출력부 7.3 전력변환부 7.4 통신부 및 제어부 7.5 기타 |
정격입력전압 : AC 1 000 V 이하, DC 1 500 V 이하 정격출력전압 : AC 1 000 V 이하, DC 1 500 V 이하 |
소재지-1 |
| ▶ 대전력, 고전압 기기 |
| ES-5925-0004:2022 |
25.8kV Eco-부하개폐기(가공용) (Eco-designed Epoxy Insulated Load Break Switch for 25.8kV Overhead Line) 7.3.2 전류개폐용량시험 7.3.3 단시간전류시험 |
7.3.2 Max. 25.8 kV 900 A 60 Hz 7.3.3 Max. 85 kA |
부속시설-1 |
| GS-5925-0011:2022 |
25.8 kV 에폭시 절연 부하개폐기(지중용) (Polymer Insulated Load Break Switches for 25.8kV Underground Line) 7.2.3 전류개폐용량시험 7.2.4 단시간전류시험 |
7.2.3 Max. 25.8 kV 900 A 60 Hz 7.2.4 Max. 85 kA |
부속시설-1 |
| GS-5925-0012:2021 |
25.8kV 에폭시 절연 다회로 차단기(지중용) (Polymer Insulated Multi-Way Fault Interrupters for 22.9kV Underground Line) 7.2.2 전류개폐용량시험(개폐부) 7.2.3 단시간 및 정격투입전류시험(1)(3) |
7.2.2 Max. 25.8 kV 900 A 60 Hz 7.2.3 Max. 85 kA |
부속시설-1 |
| GS-5925-0135:2018 |
25.8kV 에폭시절연 고장구간 차단기(가공용) (Epoxy Insulated Fault Interrupters for Distribution Automation of 25.8kV Overhead Line) 6.3.2 전류 및 개폐용량시험 6.3.3 단시간전류시험 |
6.3.2 Max. 25.8 kV 900 A 60 Hz 6.3.3 Max. 85 kA |
부속시설-1 |
| ES-5925-0002:2022 |
25.8kV 가스절연부하개폐기(지중용) (Gas Insulated Load Break Switches for 25.8kV Underground Line) 7.2.5 단시간전류시험 7.2.10 전류개폐용량시험 |
7.2.5 Max. 85 kA 7.2.10 Max. 25.8 kV 900 A 60 Hz |
부속시설-1 |
| GS-5925-0157:2021 |
25.8kV Dry air 절연 부하개폐기(지중용) (Dry air Insulated Load Break Switches for 25.8kV Underground Line) 7.2.5 단시간전류시험 7.2.10 전류개폐용량시험 |
7.2.5 Max. 85 kA 7.2.10 Max. 25.8 kV 900 A 60 Hz |
부속시설-1 |
| GS-5925-0158:2022 |
25.8kV 일반형 공기절연부하개폐기(지중용)(General Type Dry air Insulated Load break Switches for 25.8kV Underground Line) 7.2.5 단시간전류시험 7.2.10 전류개폐용량시험 |
7.2.5 Max. 85 kA 7.2.10 Max. 25.8 kV 900 A 60 Hz |
부속시설-1 |
| GS-5925-0128:2024 |
25.8kV 친환경 가스 및 고체절연 개폐장치 (25.8kV Environment-Friendly Gas or Solid Insulated Switchgear) 5.7 단시간전류시험 |
5.7 Max. 85 kA |
부속시설-1 |
| ▶ 산업용 전기기기 |
| ES-5950-0010:2008 |
변압기 단락강도 시험규격(Transformaer Short-Circuit Test Code) 5.1 육안검사 5.2 내전압 시험(유도, 상용주파, 뇌임펄스 내전압 시험) 5.3 단락강도시험(단자전압과 전류의 파형) 5.4 임피던스 변화 5.5 저압충격시험 5.6 여자전류(무부하전류) |
AC: Max. 100 kV LI: Max. 300 kV 단락강도: Max. 2 MVA 부하손실 및 무부하손실: Max. 2 MVA |
부속시설-1 |
| GS-5950-0514:2024 |
고효율 아몰퍼스 주상변압기(High Efficiency Amorphous Pole Transformers) 4 겉모양 및 구조검사 4.6 변압기외함시험(동압력시험) 4.6 변압기외함시험(정압력시험) 4.6 변압기외함시험(고정장치 및 인상고리 강도시험) 5 특성시험(권선저항측정, 극성시험, 변압비시험, 무부하손실, 부하손실) 5 온도상승시험 6.2 단락강도시험(확인시험 포함) 6.3 누유시험 6.4 충격 내전압시험 6.5 도장시험 6.9 소음레벨측정 6.10 유도내전압시험 6.10 상용주파내전압시험 6.11 가속열화시험 |
AC: Max. 100 kV LI: Max. 300 kV 단락강도: Max. 2 MVA 동압력시험: Max. 7.2 kV 25 kA 부하손실 및 무부하손실: Max. 2 MVA 온도상승: Max. 2 MVA 소음레벨: Min. 25dB |
부속시설-1 |
| GS-5950-0513:2024 |
고효율 주상변압기 (High Efficiency Pole Transformers) 4 겉모양 및 구조검사 4.6 변압기외함시험(동압력시험) 4.6 변압기외함시험(정압력시험) 4.6 변압기외함시험(고정장치 및 인상고리 강도시험) 5 특성시험(권선저항측정, 극성시험, 변압비시험, 무부하손실, 부하손실) 5 온도상승시험 6.2 단락강도시험(확인시험 포함) 6.3 누유시험 6.4 충격 내전압시험 6.5 도장시험 6.9 소음레벨측정 6.10 유도내전압시험 6.10 상용주파내전압시험 6.11 가속열화시험 |
AC: Max. 100 kV LI: Max. 300 kV 단락강도: Max. 2 MVA 동압력시험: Max. 7.2 kV 25 kA 부하손실 및 무부하손실: Max. 2 MVA 온도상승: Max. 2 MVA 소음레벨: Min. 25 dB |
부속시설-1 |
| ES-5950-0013:2024 |
22.9kV 내염형 주상변압기(22.9kV Anti-pollution Type Pole Transformers) 4 겉모양 및 구조검사 4.6 변압기외함시험(동압력시험) 4.6 변압기외함시험(정압력시험) 4.6 변압기외함시험(고정장치 및 인상고리 강도시험) 5 특성시험(권선저항측정, 극성시험, 변압비시험, 무부하손실, 부하손실) 5 온도상승시험 6.2 단락강도시험(확인시험 포함) 6.3 누유시험 6.4 충격 내전압시험 6.5 도장시험 6.9 소음레벨측정 6.10 유도내전압시험 6.10 상용주파내전압시험 6.11 가속열화시험 |
AC: Max. 100 kV LI: Max. 300 kV 단락강도: Max. 2 MVA 동압력시험: Max. 7.2 kV 25 kA 부하손실 및 무부하손실: Max. 2 MVA 온도상승: Max. 2 MVA 소음레벨: Min. 25 dB |
부속시설-1 |
| GS-5950-0502:2024 |
22.9kV Compact형 지상변압기(22.9kV Compact Type Pad Mounted Transformers) 6.2.1 겉모양 구조 검사 6.2.2 상용주파 내전압시험 6.2.3 유도내전압시험 6.2.4 충격내전압시험 6.2.5 특성시험(변압기측정, 각변위측정, 권선저항측정, 무부하손실 및 부하손실 측정) 6.2.7 온도상승시험 6.2.8 본체 압력시험(정압력) 6.2.9 가압 누설시험(기밀시험) 6.2.12 단락강도시험(보호장치 제외) 6.2.13 소음레벨시험 6.2.15 부분방전시험(1차부싱) 6.2.16 도장시험 6.2.20 가속열화시험 |
AC: Max. 100 kV LI: Max. 300 kV 단락강도: Max. 2 MVA 부하손실 및 무부하손실: Max. 2 MVA 온도상승: Max. 2 MVA 소음레벨: Min. 25 dB PD: Min. 1 pC |
부속시설-1 |
| GS-5950-0482:2022 |
22.9kV 건식형 변압기 중성점 접지리액터(Dry-Type Neutral Grounding Reactor) 6.3 구조 및 외관검사 6.4 절연저항측정 6.5 권선저항측정 6.6 임피던스 및 손실측정 6.7 유도내전압시험 6.8 절연내력 시험(뇌임펄스 내전압) 6.9 절연내력 시험(상용주파 내전압) 6.10 온도상승시험 6.11 단락강도시험 |
AC: Max. 100 kV LI: Max. 300 kV 단락강도: Max. 25 kA 온도상승: Max. 500 A |
부속시설-1 |
| ES-5950-0018:2024 |
부하개폐형 지상변압기(Load Switching Type Pad Mounted Transformers) 4 겉모양 검사 4 구조검사 4 절연저항시험 6.1.1 및 6.1.2 상용주파 내전압시험 6.1.1 및 6.1.2 유도내전압시험 6.1.1 및 6.1.2 충격내전압시험 5.1.4 특성시험(변압기측정, 각변위측정, 권선저항측정, 무부하손실 및 부하손실 측정) 5.1.1 온도상승시험 6.1.1 및 6.1.2 본체 압력시험(정압력) 6.1.6 단락강도시험(보호장치 제외) 6.1.7 소음레벨시험 6.1.8 부분방전시험 6.1.9 도장시험 |
AC: Max. 100 kV LI: Max. 300 kV 단락강도: Max. 2 MVA 부하손실 및 무부하손실: Max. 2 MVA 온도상승: Max. 2 MVA 소음레벨: Min. 25 dB PD: Min. 1 pC |
부속시설-1 |
| GS-5950-0046:2015 |
고효율지상변압기 (High Efficiency Pad Mounted Transformers) 5 겉모양 검사 5 구조검사 7.1 및 7.2 절연저항시험 7.1 및 7.2 상용주파 내전압시험 7.1 및 7.2 유도내전압시험 7.1 및 7.2 충격내전압시험 6.3 특성시험(변압기측정, 각변위측정, 권선저항측정, 무부하손실 및 부하손실 측정) 6.1 온도상승시험 5.3 본체 압력시험(정압력) 7.6 단락강도시험(보호장치 제외) 7.7 소음레벨시험 7.8 부분방전시험 7.9 도장막 두께시험 7.9 도막의 밀착성 시험 |
AC: Max. 100 kV LI: Max. 300 kV 단락강도: Max. 2 MVA 부하손실 및 무부하손실: Max. 2 MVA 온도상승: Max. 2 MVA 소음레벨: Min. 25dB PD: Min. 1 pC |
부속시설-1 |
| GS-5950-0520:2024 |
22.9kV 내염형 컴팩트 지상변압기(22.9kv Anti-pollution Compact Type Pad Mounted Transformers) 6.2.1 겉모양 구조 검사 6.2.2 상용주파 내전압시험 6.2.3 유도내전압시험 6.2.4 충격내전압시험 6.2.5 특성시험(변압기측정, 각변위측정, 권선저항측정, 무부하손실 및 부하손실 측정) 6.2.7 온도상승시험 6.2.8 본체 압력시험(정압력) 6.2.9 가압 누설시험(기밀시험) 6.2.12 단락강도시험(보호장치 제외) 6.2.13 소음레벨시험 6.2.15 부분방전시험(1차부싱) 6.2.16 본체 도장시험 6.2.21 가속열화시험 |
AC: Max. 100 kV LI: Max. 300 kV 단락강도: Max. 2 MVA 부하손실 및 무부하손실: Max. 2 MVA 온도상승: Max. 2 MVA 소음레벨: Min. 25 dB PD: Min. 1 pC |
부속시설-1 |
| GS-5950-0500:2024 |
지중 매입형 고체절연 변압기(Submersible Solid Insulation Distribution Transformers) 4 겉모양 및 구조 검사 6.1 절연저항시험 6.1 특성시험(변압기측정, 극성측정, 권선저항측정, 무부하손실 및 부하손실 측정) 4.4 상용주파 내전압시험 4.4 유도 내전압시험 4.4 충격 내전압시험 6.3 도금 두께시험 6.4 온도상승시험 6.5 단락강도시험 6.6 소음레벨 측정시험 6.7 부분방전시험 |
AC: Max. 100 kV LI: Max. 300 kV 단락강도: Max. 2 MVA 부하손실 및 무부하손실: Max. 2 MVA 온도상승: Max. 2 MVA 소음레벨: Min. 25 dB PD: Min. 1 pC |
부속시설-1 |